| 2021-04-16 15:19:32 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT-21030177 |
| | 4/16/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS G-1 & G-2: TWO TANKLESS WATER HEATERS WERE |
| | SHOWN ON THE APPROVED MASTER PLANS UNDER |
| | PERMIT-20080095, HOWEVER THE SUBMITTED GAS RISER |
| | INDICATES ONLY ONE. PLEASE REVISE THE RISER DRAWING |
| | (G-2) AND SHOW THE LOCATIONS OF BOTH GAS WATER HEATERS |
| | ON G-1. THE CURRENT G-1 PLAN DOES NOT SHOW A WATER |
| | HEATER IN ANY LOCATION. THE APPROVED MASTER PLANS SHOW |
| | A WATER HEATER IN THE MAIN HOUSE GARAGE AND ONE AT THE |
| | REAR OF THE STUDIO BUILDING. |
| | |
| | 2) G-1: AS NOTED ABOVE THE LOCATIONS OF THE GAS WATER |
| | HEATERS NEED TO BE CLEARLY SHOWN ON THE PLANS WITH |
| | REQUIRED INSTALLATION CLEARANCE MEASUREMENTS AS |
| | RECOMMENDED BY THE MANUFACTURER- SECTION G2448.1, AND |
| | IN ACCORDANCE WITH SECTION G2427.8 FBC RES. BASED ON |
| | THE APPROVED MASTER PLANS, COMBUSTION AIR AND VENTING |
| | ARE REQUIRED FOR THE WATER HEATER IN THE GARAGE. PLEASE |
| | REVIEW THE MANUFACTURER'S SPECIFICATIONS FOR A DIRECT |
| | VENT SYSTEM AND PROVIDE DETAILS ON THE PLAN- TYPES AND |
| | SIZES OF INLET AND OUTLET PIPES, PIPE RUNS, AND |
| | TERMINATION LOCATIONS. INDICATE HOW CONDENSATION AT ALL |
| | WATER HEATER LOCATIONS WILL BE DRAINED TO AN APPROVED |
| | PLACE OF DISPOSAL- SECTION 307.2 FBC FG. |
| | |
| | 3) G-1 & G-2: PLEASE NOTE THAT A SEPARATE PERMIT IS |
| | REQUIRED FOR INSTALLATION OF THE GENERATOR, HOWEVER BE |
| | ADVISED THAT THE GENERATOR EXHAUST SHALL BE LOCATED A |
| | MINIMUM OF 10 FT. FROM MECHANICAL AND GRAVITY AIR |
| | INTAKES INTO THE BUILDING INCLUDING OPERABLE WINDOWS |
| | AND DOORS- SECTION R303.5.1 FBC RES. |
| | |
| | 4) G-1: THE PLAN SHOWS THE BBQ GRILL ADJACENT TO THE |
| | WALL AND IN CLOSE PROXIMITY OF A WINDOW. PLEASE CLARIFY |
| | IF THE WALL IS OF COMBUSTIBLE CONSTRUCTION, OR IF THERE |
| | IS OVERHEAD COMBUSTIBLE CONSTRUCTION. PLEASE REVIEW THE |
| | SUBMITTED MANUFACTURER'S CLEARANCE TO COMBUSTIBLES |
| | SPECIFICATIONS AND PROVIDE CLEARANCE DISTANCE |
| | MEASUREMENTS ON THE PLAN- SECTION G2447.1 FBC RES. |
| | |
| | 5) G-1: INDICATE HOW COMBUSTION AIR IS TO BE PROVIDED |
| | TO THE COOKTOP IN THE KITCHEN AND PROVIDE CALCULATIONS- |
| | SECTION G2407.1 FBC RES. |
| | |
| | 6) G-1: INDICATE HOW MAKEUP AIR IS TO BE PROVIDED TO |
| | THE DRYER IN THE CLOSET- SECTIONS G2407.1 & G2439.5 FBC |
| | RES. |
| | |
| | 7) G-2: PLEASE SHOW THE REQUIRED LOCATIONS OF PIPE |
| | UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATORS- |
| | SECTION G2421.2(7) FBC RES. |
| | |
| | 8) G-2: INDICATE THE MAKE AND MODEL OF REGULATORS TO BE |
| | INSTALLED AND SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | MARKED UP OR HIGHLIGHTED TO SHOW THE SELECTED MODEL, |
| | INLET AND OUTLET PIPE SIZES AND PRESSURES- SECTION |
| | G2421.2 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |