Plan Review Details - Permit 21030177
Plan Review Stops For Permit 21030177
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-05-01 Cont ID  
Sent By ccole Date 2021-05-01 Time 08:13 Rev Time 0.00
Received By ccole Date 2021-05-01 Time 08:13 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-16 Cont ID  
Sent By ccole Date 2021-04-16 Time 15:19 Rev Time 0.00
Received By ccole Date 2021-04-16 Time 12:42 Sent To  
Notes
2021-04-16 15:19:321ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT-21030177
 4/16/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS G-1 & G-2: TWO TANKLESS WATER HEATERS WERE
 SHOWN ON THE APPROVED MASTER PLANS UNDER
 PERMIT-20080095, HOWEVER THE SUBMITTED GAS RISER
 INDICATES ONLY ONE. PLEASE REVISE THE RISER DRAWING
 (G-2) AND SHOW THE LOCATIONS OF BOTH GAS WATER HEATERS
 ON G-1. THE CURRENT G-1 PLAN DOES NOT SHOW A WATER
 HEATER IN ANY LOCATION. THE APPROVED MASTER PLANS SHOW
 A WATER HEATER IN THE MAIN HOUSE GARAGE AND ONE AT THE
 REAR OF THE STUDIO BUILDING.
  
 2) G-1: AS NOTED ABOVE THE LOCATIONS OF THE GAS WATER
 HEATERS NEED TO BE CLEARLY SHOWN ON THE PLANS WITH
 REQUIRED INSTALLATION CLEARANCE MEASUREMENTS AS
 RECOMMENDED BY THE MANUFACTURER- SECTION G2448.1, AND
 IN ACCORDANCE WITH SECTION G2427.8 FBC RES. BASED ON
 THE APPROVED MASTER PLANS, COMBUSTION AIR AND VENTING
 ARE REQUIRED FOR THE WATER HEATER IN THE GARAGE. PLEASE
 REVIEW THE MANUFACTURER'S SPECIFICATIONS FOR A DIRECT
 VENT SYSTEM AND PROVIDE DETAILS ON THE PLAN- TYPES AND
 SIZES OF INLET AND OUTLET PIPES, PIPE RUNS, AND
 TERMINATION LOCATIONS. INDICATE HOW CONDENSATION AT ALL
 WATER HEATER LOCATIONS WILL BE DRAINED TO AN APPROVED
 PLACE OF DISPOSAL- SECTION 307.2 FBC FG.
  
 3) G-1 & G-2: PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR INSTALLATION OF THE GENERATOR, HOWEVER BE
 ADVISED THAT THE GENERATOR EXHAUST SHALL BE LOCATED A
 MINIMUM OF 10 FT. FROM MECHANICAL AND GRAVITY AIR
 INTAKES INTO THE BUILDING INCLUDING OPERABLE WINDOWS
 AND DOORS- SECTION R303.5.1 FBC RES.
  
 4) G-1: THE PLAN SHOWS THE BBQ GRILL ADJACENT TO THE
 WALL AND IN CLOSE PROXIMITY OF A WINDOW. PLEASE CLARIFY
 IF THE WALL IS OF COMBUSTIBLE CONSTRUCTION, OR IF THERE
 IS OVERHEAD COMBUSTIBLE CONSTRUCTION. PLEASE REVIEW THE
 SUBMITTED MANUFACTURER'S CLEARANCE TO COMBUSTIBLES
 SPECIFICATIONS AND PROVIDE CLEARANCE DISTANCE
 MEASUREMENTS ON THE PLAN- SECTION G2447.1 FBC RES.
  
 5) G-1: INDICATE HOW COMBUSTION AIR IS TO BE PROVIDED
 TO THE COOKTOP IN THE KITCHEN AND PROVIDE CALCULATIONS-
 SECTION G2407.1 FBC RES.
  
 6) G-1: INDICATE HOW MAKEUP AIR IS TO BE PROVIDED TO
 THE DRYER IN THE CLOSET- SECTIONS G2407.1 & G2439.5 FBC
 RES.
  
 7) G-2: PLEASE SHOW THE REQUIRED LOCATIONS OF PIPE
 UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATORS-
 SECTION G2421.2(7) FBC RES.
  
 8) G-2: INDICATE THE MAKE AND MODEL OF REGULATORS TO BE
 INSTALLED AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 MARKED UP OR HIGHLIGHTED TO SHOW THE SELECTED MODEL,
 INLET AND OUTLET PIPE SIZES AND PRESSURES- SECTION
 G2421.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2021-05-01 Time   Rev Time 0.00
Received By aoliver Date 2021-04-27 Time 13:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-04-16 Time   Rev Time 0.00
Received By shill Date 2021-03-29 Time 17:49 Sent To  
Notes
2021-03-29 17:49:51ROUTED FOR BUILDING DIVISION AUDIT
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-29 Cont ID  
Sent By shill Date 2021-03-29 Time 17:49 Rev Time 0.00
Received By shill Date 2021-03-26 Time 12:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-25 Cont ID  
Sent By shill Date 2021-03-25 Time 08:07 Rev Time 0.00
Received By shill Date 2021-03-24 Time 11:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-04 Cont ID  
Sent By shill Date 2021-03-04 Time 19:13 Rev Time 0.00
Received By shill Date 2021-03-04 Time 16:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-05-01 Cont ID  
Sent By ccole Date 2021-05-01 Time 08:13 Rev Time 0.00
Received By ccole Date 2021-05-01 Time 08:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-16 Cont ID  
Sent By ccole Date 2021-04-16 Time 15:24 Rev Time 0.00
Received By ccole Date 2021-04-16 Time 12:42 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status P Date 2021-04-28 Cont ID  
Sent By shill Date 2021-04-28 Time 16:10 Rev Time 0.00
Received By shill Date 2021-04-28 Time 16:10 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status P Date 2021-03-29 Cont ID  
Sent By shill Date 2021-03-29 Time 17:49 Rev Time 0.00
Received By shill Date 2021-03-29 Time 17:48 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2021-03-25 Cont ID  
Sent By shill Date 2021-03-25 Time 07:52 Rev Time 0.00
Received By shill Date 2021-03-25 Time 07:52 Sent To  
Notes
2021-03-25 08:05:14SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PROJECT IS PRIVATE PROVIDER PLAN REVIEW, PROVIDE
 AFFIDAVIT. FS553.791(6):
  
 (6)?A PRIVATE PROVIDER PERFORMING PLANS REVIEW UNDER
 THIS SECTION SHALL REVIEW THE PLANS TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES. UPON DETERMINING
 THAT THE PLANS REVIEWED COMPLY WITH THE APPLICABLE
 CODES, THE PRIVATE PROVIDER SHALL PREPARE AN AFFIDAVIT
 OR AFFIDAVITS ON A FORM REASONABLY ACCEPTABLE TO THE
 COMMISSION CERTIFYING, UNDER OATH, THAT THE FOLLOWING
 IS TRUE AND CORRECT TO THE BEST OF THE PRIVATE
 PROVIDER?S KNOWLEDGE AND BELIEF:
 (A)?THE PLANS WERE REVIEWED BY THE AFFIANT, WHO IS DULY
 AUTHORIZED TO PERFORM PLANS REVIEW PURSUANT TO THIS
 SECTION AND HOLDS THE APPROPRIATE LICENSE OR
 CERTIFICATE.
 (B)?THE PLANS COMPLY WITH THE APPLICABLE CODES.
  
 PLANS ARE STAMPED AS REVIEWED BY THE PRIVATE PROVIDER,
 BUT NO AFFIDAVIT WAS SUBMITTED.
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2021-03-04 Cont ID  
Sent By shill Date 2021-03-04 Time 19:12 Rev Time 0.00
Received By shill Date 2021-03-04 Time 19:12 Sent To  
Notes
2021-03-04 19:13:08SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PROJECT IS PRIVATE PROVIDER PLAN REVIEW, PROVIDE
 AFFIDAVIT.
 FS553

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-04-27 Cont ID  
Sent By medwards Date 2021-04-27 Time 15:02 Rev Time 0.00
Received By medwards Date 2021-04-27 Time 15:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-03-25 Cont ID  
Sent By medwards Date 2021-03-25 Time 05:55 Rev Time 0.00
Received By medwards Date 2021-03-25 Time 05:55 Sent To  
Notes
***NONE***