Plan Review Details - Permit 21030161
Plan Review Stops For Permit 21030161
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-05-25 Cont ID  
Sent By rmcdouga Date 2021-05-25 Time 10:22 Rev Time 0.00
Received By rmcdouga Date 2021-05-25 Time 10:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-26 Cont ID  
Sent By rmcdouga Date 2021-04-26 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2021-04-26 Time 13:57 Sent To  
Notes
2021-04-26 14:09:51PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT COMPLIED. [THE GENERATOR PAD ENGINEERING THAT
 WAS SUBMITTED, REFERENCES TO 2017 FBC SIXTH EDITION AND
 THSI PERMIT IS UNDER THE 2020 FBC SEVENTH EDITION. THE
 PLANS HAVE SEVERAL REFERENCES TO THE FBC SIXTH EDITION
 (2017). THE FBC SEVENTH EDITION (2020) WENT INTO EFFECT
 ON DECEMBER 31, 2020. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE 2020 FBC SEVENTH EDITION. FS CHAPTER 553]
 SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD
 ANCHORING DETAILS. IF A PREFABRICATED SLAB IS USED,
 SUBMIT PRODUCT APPROVALS OR SITE SPECIFIC ENGINEERING.
 THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DOCUMENTS. FBC AMENDMENTS
 107.2.1 & FBC-R301
  
 2) NOT COMPLIED. [THIS NEEDS TO BE SPECIFIED ON THE
 GENERATOR LOCATION SURVEY.] SPECIFY THAT THE GENERATOR
 EXHAUST IS TO BE LOCATED AT LEAST 10 FEET FROM OPENINGS
 INTO A BUILDING. FBC-R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By rmcdouga Date 2021-03-24 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2021-03-24 Time 07:36 Sent To  
Notes
2021-03-24 08:01:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD
 ANCHORING DETAILS. IF A PREFABRICATED SLAB IS USED,
 SUBMIT PRODUCT APPROVALS OR SITE SPECIFIC ENGINEERING.
 THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DOCUMENTS. FBC AMENDMENTS
 107.2.1 & FBC-R301
  
 2) SPECIFY THAT THE GENERATOR EXHAUST IS TO BE LOCATED
 AT LEAST 10 FEET FROM OPENINGS INTO A BUILDING.
 FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-30 Cont ID  
Sent By jleahy Date 2021-04-30 Time 17:12 Rev Time 0.00
Received By jleahy Date 2021-04-30 Time 17:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By cthroop Date 2021-03-24 Time 09:24 Rev Time 0.00
Received By cthroop Date 2021-03-24 Time 08:17 Sent To  
Notes
2021-03-24 09:26:46PLAN REVIEW ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE CABLE SIZING BETWEEN GEN. AND ATS AND ATS
 AND MAIN DISCONNECT. INCLUDE CONTROL WIRING SIZES.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-26 Cont ID  
Sent By rmcdouga Date 2021-05-26 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2021-05-26 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-25 Cont ID  
Sent By rmcdouga Date 2021-05-25 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2021-05-17 Time 07:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 14:02 Rev Time 0.00
Received By jleahy Date 2021-04-21 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-14 Cont ID  
Sent By cthroop Date 2021-04-14 Time 09:09 Rev Time 0.00
Received By cthroop Date 2021-03-16 Time 08:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-05-26 Cont ID  
Sent By rmcdouga Date 2021-05-26 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2021-05-26 Time 09:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-05-25 Cont ID  
Sent By rmcdouga Date 2021-05-25 Time 10:23 Rev Time 0.00
Received By rmcdouga Date 2021-05-25 Time 10:23 Sent To  
Notes
2021-05-25 10:25:54A COPY OF AN ENGINEER'S DIGITALLY SIGNED GENERATOR PAD
 DRAWING WAS SUBMITTED. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & 61G1 OR FS 471 & 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-04-26 Cont ID  
Sent By rmcdouga Date 2021-04-26 Time 14:10 Rev Time 0.00
Received By rmcdouga Date 2021-04-26 Time 14:09 Sent To  
Notes
2021-04-26 14:11:30THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 ENGINEER'S DIGITAL SIGNATURE. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT'S OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT'S OR ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS.
 NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 471 & 61G15, FS 481 & 61G1
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By rmcdouga Date 2021-03-24 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2021-03-24 Time 08:01 Sent To  
Notes
2021-03-24 09:24:03ELECTRICAL CONTRACTOR SHALL PRINT NAME AND SIGN NEW
 LOAD CALC'S. SIGNAURE ON ELECTRICAL RISER IS APPROVED.
 CT
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
2021-03-24 08:02:53ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15

Review Stop Z ZONING
Rev No 3 Status P Date 2021-05-17 Cont ID  
Sent By awooten Date 2021-05-17 Time   Rev Time 0.00
Received By awooten Date 2021-05-17 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2021-05-12 Time   Rev Time 0.00
Received By   Date 2021-05-12 Time   Sent To  
Notes
2021-05-12 16:01:02***************************ZONING REVIEW
 FAILED******************(REPEAT COMMENT)
  
 PROVIDE THE SETBACKS FOR THE GENERATOR. GENERATORS ARE
 CONSIDERED MECHANICAL EQUIPMENT. BELOW IS THE CODE THAT
 GOVERNS MECHANICAL EQUIPMENT.
  
 MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK. WINDOW
 AIR-CONDITIONING UNITS MAY NOT PROJECT MORE THAN 18
 INCHES INTO A REQUIRED SIDE SETBACK.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISON
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2021-04-13 Cont ID  
Sent By awooten Date 2021-04-13 Time   Rev Time  
Received By awooten Date 2021-04-13 Time   Sent To  
Notes
2021-04-13 10:44:39***************************ZONING REVIEW
 FAILED******************
  
 PROVIDE THE SETBACKS FOR THE GENERATOR. GENERATORS ARE
 CONSIDERED MECHANICAL EQUIPMENT. BELOW IS THE CODE THAT
 GOVERNS MECHANICAL EQUIPMENT.
  
 MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK. WINDOW
 AIR-CONDITIONING UNITS MAY NOT PROJECT MORE THAN 18
 INCHES INTO A REQUIRED SIDE SETBACK.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISON
 561-822-1449
 [email protected]