Plan Review Details - Permit 21030143
Plan Review Stops For Permit 21030143
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-03-10 Cont ID  
Sent By cpuell Date 2021-03-10 Time 12:49 Rev Time 0.00
Received By cpuell Date 2021-03-10 Time 12:49 Sent To  
Notes
2021-08-10 16:22:03PRIMARY ADDRESS OK FOR PROJECT

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-06-17 Cont ID  
Sent By pvalenti Date 2021-06-17 Time 09:19 Rev Time 0.00
Received By pvalenti Date 2021-06-17 Time 06:19 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By rmcphers Date 2021-04-07 Time 16:14 Rev Time 0.00
Received By rmcphers Date 2021-04-07 Time 16:14 Sent To  
Notes
2021-04-07 16:15:01PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-12-07 Cont ID  
Sent By rmcphers Date 2021-12-07 Time 07:48 Rev Time 0.00
Received By rmcphers Date 2021-12-07 Time 07:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-10-05 Cont ID  
Sent By rmcphers Date 2021-10-05 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2021-10-05 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-08-12 Cont ID  
Sent By pvalenti Date 2021-08-12 Time 15:56 Rev Time 0.00
Received By pvalenti Date 2021-08-12 Time 14:50 Sent To  
Notes
2021-08-12 16:10:22****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD BUILDING REVIEW DENIED; THE FOLLOWING ITEMS FROM
 THE LAST REVIEW LIST STILL NEED TO BE ADDRESSED:
  
  
 12) FBC B 1015.6, PLEASE PROVIDE ROOF TOP GUARD RAIL
 REQUIREMENTS AT INDICATORS SHOWN ON SHEET A2.0.1.
 PROVIDE THE SIGNED/SEALED RAILING TO ROOF CONNECTION
 DETAILS THAT MEET THE LOAD REQUIREMENTS OF FBC B
 SECTION 1607.8.1, 1607.8.1.1, & 1607.8.1.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-17 Cont ID  
Sent By pvalenti Date 2021-06-17 Time 08:54 Rev Time 0.00
Received By pvalenti Date 2021-06-17 Time 06:19 Sent To  
Notes
2021-06-17 09:07:00****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW DENIED; THE FOLLOWING ITEMS FROM
 THE LAST REVIEW LIST STILL NEED TO BE ADDRESSED:
  
 3) FBC B 107.2, PLEASE SUBMIT ALL PRODUCT APPROVALS.
 EACH PRODUCT APPROVAL NEEDS TO BE REVIEW STAMPED.
  
 11) FBC B 107.2, PLEASE PROVIDE THE ATTACHMENT DETAILS
 FOR THE ROOF TOP EQUIPMENT TO THE EXISTING ROOF OR
 PRODUCT APPROVALS SHOWING COMPLIANCE WITH WINDLOADS PER
 FBC B 1609.
  
 12) FBC B 1015.6, PLEASE PROVIDE ROOF TOP GUARD RAIL
 REQUIREMENTS AT INDICATORS SHOWN ON SHEET A2.0.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By rmcphers Date 2021-04-07 Time 16:14 Rev Time 0.00
Received By rmcphers Date 2021-04-07 Time 14:17 Sent To  
Notes
2021-04-07 16:14:20COMMERCIAL ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THAT THE PARKING LOT RESTRIPING WILL BE
 ON A SEPARATE PERMIT.
 2) PLEASE SHOW THAT THE SITEWALL WILL BE ON A SEPARATE
 PERMIT.
 3) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVAL FOR THE EXTERIOR DOORS, WINDOWS
 AND ROOFING SYSTEM. ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD.
 4) DRAWING LS.1.1 SHOWS THE EGRESS GATE WIDTH AT 4' -
 DRAWING A 7.0.1 SHOWS ON THE DOOR SCHEDULE THE EGRESS
 GATE TO BE 4'4" - PLEASE CLARIFY - THE MAXIMUM WIDTH
 SHOULD BE 4' PER FBC 1010.1.1
 5) THE AWNING AREA SHOULD HAVE EMERGENCY LIGHTING PER
 FBC 1008.3.2 (4).
 6) PLEASE SHOW THE KNEE AND TOE CLEARANCES AT THE
 ACCESSIBLE BAR AREA AND THE RESTROOM ACCESSIBLE SINKS
 PER FBC A306
 7) PLEASE SHOW THE ACCESSIBLE BAR AREA AT EACH BAR PER
 FBC A226.1
 8) PLEASE SHOW THE BUILDING SQUARE FOOTAGE.
 9) PLEASE SHOW THE AREA SQUARE FOOTAGE UNDER THE CANOPY
 - FBC 3105.3.2 AREA.NO FABRIC AWNING OR FABRIC-COVERED
 FRAME SHALL EXCEED THE AREA OF THE BUILDING TO WHICH IT
 IS ATTACHED.
 10) PLEASE SHOW ROOF TOP MECHANICAL EQUIPMENT CURB
 HEIGHT OR STAND CLEARANCE FROM THE ROOFING TO COMPLY
 WITH FBC 1510.10.
 11) PLEASE PROVIDE ATTACHMENT DETAILS FOR THE ROOF TOP
 MECHANICAL EQUIPMENT TO THE EXISTING ROOF OR PRODUCT
 APPROVALS TO COMPLY WITH THE WIND LOADS FBC 1609
 12) PLEASE SHOW THE REQUIRED GUARD RAILS ON THE ROOF
 PER FBC 1015.6 MECHANICAL EQUIPMENT, SYSTEMS AND
 DEVICES.
 GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND
 EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-01 Cont ID  
Sent By jleahy Date 2021-06-01 Time 14:44 Rev Time 0.00
Received By jleahy Date 2021-06-01 Time 14:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-05 Cont ID  
Sent By jleahy Date 2021-04-05 Time 15:27 Rev Time 0.00
Received By jleahy Date 2021-04-05 Time 15:17 Sent To  
Notes
2021-04-05 15:30:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FAULT CURRENT CALCULATION AND LABELS FOR SERVICE
 MISSING FROM PLANS 110.9, 110.10, 110.24
  
 2) GFI PROTECTION MISSING FROM KITCHEN, AND WITHIN 6'
 OF SINKS 210.8(B)

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-07-29 Cont ID  
Sent By cwalker Date 2021-07-29 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-05-18 Cont ID  
Sent By cwalker Date 2021-05-18 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-03-26 Cont ID  
Sent By pleduc Date 2021-03-26 Time   Rev Time 0.00
Received By pleduc Date 2021-03-26 Time 14:33 Sent To  
Notes
2021-03-26 14:34:56PROVIDE EXIT SIGNS PER PREVIOSU COMMENTS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-15 Cont ID  
Sent By cwalker Date 2021-03-15 Time   Rev Time 0.00
Received By cwalker Date 2021-03-15 Time 10:49 Sent To  
Notes
2021-03-15 10:53:37FIRE PROVISO, EXIT SIGN LOCATIONS, PROVIDE EXIT SIGN IN
 FOYER AT DOOR
  
 C. R. WALKER,
 SENIOR FIRE INSPECTOR
 804-4762,
 [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-10-13 Cont ID  
Sent By ccole Date 2021-10-13 Time 13:14 Rev Time 0.00
Received By ccole Date 2021-10-13 Time 12:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-08-12 Cont ID  
Sent By ccole Date 2021-08-12 Time 17:39 Rev Time 0.00
Received By ccole Date 2021-08-12 Time 17:38 Sent To  
Notes
2021-08-12 17:41:033RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 21030143
 8/12/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST AND
 2ND REVIEWS ARE LISTED BELOW AS PASSED OR FAILED. NOTES
 FOR FURTHER CLARIFICATION HAVE BEEN ADDED TO FAILED
 COMMENTS. PLEASE CONTACT ME IF I CAN BE OF ANY
 ASSISTANCE IN GETTING THE FUEL GAS PLANS APPROVED.
  
 1) FAILED. SHEET P5.1: BASED ON THE SIZING TABLE
 402.4(2) LISTED ON THE PLAN, THE 3/4 IN. PIPE AT METER
 IS UNDERSIZED FOR THE 363.000 GAS LOAD AT 32 FT. TDL.
 THE TOTAL CONNECTED LOAD WITH THE WATER HEATER IS
 562,000 BTUS. BASED ON THE LISTED PIPE SIZING TABLE ON
 THE PLAN (402.4(2)) THE 1-INCH MAIN GAS PIPE IS
 UNDERSIZED. PLEASE CLARIFY IF THIS IS A LOW PRESSURE
 SYSTEM PER THE SELECTED PIPE SIZING TABLE OR POSSIBLY A
 2 PSI SYSTEM WHICH WOULD ONLY REQUIRE A MINIMUM ?-INCH
 MAIN PIPE FOR THE TOTAL LOAD AT 32-FT. TDL- SEE TABLE
 402.4(5).
  
 2) PASSED. P5.1: SHOW THE LOCATION OF AUTO GAS VALVE-
 SECTION 10.4.1 NFPA 96.
  
 3) FAILED P5.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE COOKING APPLIANCES - SECTION 304.1 FBC FG. THE NEW
 CALCULATIONS ARE USING THE EQUATION FOUND IN SECTION
 304.5.2 FBC FG WHICH CAN ONLY BE USED WHEN THERE IS A
 KNOWN AIR INFILTRATION RATE LESS THAN .40 AIR CHANGES
 PER HOUR (ACH). THE CALCULATIONS PROVIDED ARE USING AN
 ACH OF 17.6. THE CALCULATION IS ALSO USING 2535 CFMS OF
 O/A AS THE BASIS OF THE ACH, HOWEVER THE AIR IS BEING
 SUPPLIED MECHANICALLY AS OPPOSED TO INFILTRATION. IF
 USING MECHANICAL AIR PLEASE REFER TO SECTION 304.9 AND
 PROVIDE THE CALCULATION. PLEASE REVIEW SECTION 304.5.1
 BELOW:
 THE REQUIRED VOLUME OF INDOOR AIR SHALL BE DETERMINED
 IN ACCORDANCE WITH SECTION 304.5.1 OR 304.5.2, EXCEPT
 THAT WHERE THE AIR INFILTRATION RATE IS KNOWN TO BE
 LESS THAN 0.40 AIR CHANGES PER HOUR (ACH), SECTION
 304.5.2 SHALL BE USED. THE TOTAL REQUIRED VOLUME SHALL
 BE THE SUM OF THE REQUIRED VOLUME CALCULATED FOR ALL
 APPLIANCES LOCATED WITHIN THE SPACE. ROOMS
 COMMUNICATING DIRECTLY WITH THE SPACE IN WHICH THE
 APPLIANCES ARE INSTALLED THROUGH OPENINGS NOT FURNISHED
 WITH DOORS, AND THROUGH COMBUSTION AIR OPENINGS SIZED
 AND LOCATED IN ACCORDANCE WITH SECTION 304.5.3, ARE
 CONSIDERED TO BE PART OF THE REQUIRED VOLUME.
  
 4) PASSED- DEFERRED SUBMITTAL. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE COOKING APPLIANCES AND THE WATER
 HEATER- SECTIONS 623.1 & 624.1 FBC FG.
  
 5) PASSED- DEFERRED SUBMITTAL. P0.1: PROVIDE THE
 MANUFACTURER OF THE GAS WATER HEATER IN THE FIXTURE
 SCHEDULE- SECTION 624.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-06-03 Cont ID  
Sent By ccole Date 2021-06-03 Time 09:18 Rev Time 0.00
Received By ccole Date 2021-06-03 Time 09:18 Sent To  
Notes
2021-06-03 09:20:342ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21030143
 6/3/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW LISTED BELOW STILL EXIST. NO CORRECTED PLANS OR
 NARRATIVE RESPONSES WERE SUBMITTED.
  
 1) SHEET P5.1: BASED ON THE SIZING TABLE 402.4(2)
 LISTED ON THE PLAN, THE 3/4 IN. PIPE AT METER IS
 UNDERSIZED FOR THE 363.000 GAS LOAD AT 32 FT. TDL.
  
 2) P5.1: SHOW THE LOCATION OF AUTO GAS VALVE- SECTION
 10.4.1 NFPA 96.
  
 3) P5.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 COOKING APPLIANCES - SECTION 304.1 FBC FG.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCES AND THE WATER HEATER- SECTIONS 623.1 & 624.1
 FBC FG.
  
 5) P0.1: PROVIDE THE MANUFACTURER OF THE GAS WATER
 HEATER IN THE FIXTURE SCHEDULE- SECTION 624.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-12 Cont ID  
Sent By ccole Date 2021-04-12 Time 19:03 Rev Time 0.00
Received By ccole Date 2021-04-12 Time 19:03 Sent To  
Notes
2021-04-12 19:04:051ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21030143
 4/12/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P5.1: BASED ON THE SIZING TABLE 402.4(2)
 LISTED ON THE PLAN, THE 3/4 IN. PIPE AT METER IS
 UNDERSIZED FOR THE 363.000 GAS LOAD AT 32 FT. TDL.
 INDICATE THE DELIVERY PRESSURE AT THE METER- 2 PSI OR
 8-11 INCHES WC?
  
 2) P5.1: SHOW THE LOCATION OF AUTO GAS VALVE- SECTION
 10.4.1 NFPA 96.
  
 3) P5.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 COOKING APPLIANCES - SECTION 304.1 FBC FG.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCES AND THE WATER HEATER- SECTIONS 623.1 & 624.1
 FBC FG.
  
 5) P0.1: PROVIDE THE MANUFACTURER OF THE WATER HEATER
 IN THE FIXTURE SCHEDULE- SECTION 624.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-12-07 Cont ID  
Sent By rmcphers Date 2021-12-07 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2021-11-15 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-10-13 Time   Rev Time 0.00
Received By aoliver Date 2021-09-17 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-08-25 Time   Rev Time 0.00
Received By aoliver Date 2021-07-28 Time 07:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-22 Cont ID  
Sent By pvalenti Date 2021-06-22 Time 06:59 Rev Time 0.00
Received By pvalenti Date 2021-05-14 Time 14:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-22 Cont ID  
Sent By ccarvaja Date 2021-04-22 Time 08:11 Rev Time 0.00
Received By rmcphers Date 2021-03-10 Time 15:50 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-04-07 Cont ID  
Sent By rmcphers Date 2021-04-07 Time 16:15 Rev Time 0.00
Received By rmcphers Date 2021-04-07 Time 16:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-04 Cont ID  
Sent By medwards Date 2021-06-04 Time 11:19 Rev Time 0.00
Received By medwards Date 2021-06-03 Time 10:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 07:49 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 06:29 Sent To  
Notes
2021-04-08 07:49:111ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21030143
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ATTACH NOTE ON THE DRAWINGS STATING THAT THE
 KITCHEN HOOD, GREASE DUCT AND MAKEUP AIR WILL BE
 SUBMITTED AS A SEPARATE PERMIT AND PLAN REVIEW.
  
 2) PLEASE ATTACH A NOTE ON THE DRAWINGS STATING THAT
 THE REFRIGERATION EQUIPMENT WILL BE SUBMITTED AS A
 SEPARATE PERMIT AND PLAN REVIEW.
  
 3) THE OUTDOOR AIR CALCULATION FOR THE INDOOR DINING
 APPEARS TO BE LOW ACTUAL CFM SHOULD BE 384. FBC M
 403.3.1.1 AND TABLE 403.3.1.1
  
 4) THE OUTDOOR AIR CALCULATIONS SHOULD ALSO SHOW THE
 OUTDOOR AIR REQUIRED FOR THE KITCHEN. FBC M 403.3.1.1
 AND TABLE 403.3.1.1
  
 5) SHEET M6.1 (ROOF TOP A/C EQUIPMENT SCHEDULE) OUTDOOR
 AIR CFM IS UNDERSIZED.
  
 6) PLEASE SHOW THAT GUARDS ARE INSTALLED FOR THE
 MAINTENANCE OF THE UNITS THAT ARE WITHIN 10 FT. OF ROOF
 EDGE. FBC M 304.11
  
 7) PLEASE SHOULD THE ROOF ACCESS FOR SERVICE OF THE
 UNITS ON THE ROOF. FBC M 306.5
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-10-13 Cont ID  
Sent By ccole Date 2021-10-13 Time 13:14 Rev Time 0.00
Received By ccole Date 2021-10-13 Time 12:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-08-12 Cont ID  
Sent By ccole Date 2021-08-12 Time 17:56 Rev Time 0.00
Received By ccole Date 2021-08-12 Time 17:41 Sent To  
Notes
2021-08-12 17:57:483RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21030143
 8/12/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS 2, 6, & 8
 FROM THE 1ST REVIEW AND 2ND REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES FOR CLARIFICATION. PLEASE CONTACT
 ME IF I CAN BE OF ANY ASSISTANCE IN GETTING THE
 PLUMBING PLANS APPROVED.
  
 2) FAILED. P0.1: PLEASE INCLUDE THE MOP SINK,
 3-COMPARTMENT SINK, PREP SINKS, AND HAND SINKS TO THE
 FIXTURE SCHEDULE- SECTION 107.2.1 WPB. PROVIDE TYPE OF
 WALL FINISH MATERIAL TO BE INSTALLED AROUND THE MOP
 SINK- SECTION 1210.2.2 FBC B. PLEASE IDENTIFY THE
 LOCATION OF THE MOP SINK ON THE PLANS, ADD IT TO THE
 SCHEDULE, AND PROVIDE THE WALL FINISH MATERIAL AS
 PREVIOUSLY REQUESTED.
  
 6) FAILED. P5.1: THE KEY NOTES REFERENCE CIVIL DRAWINGS
 FOR POINTS OF CONNECTIONS AND WATER METER AND BACKFLOW
 PREVENTER LOCATIONS- PLEASE PROVIDE THE PLANS. PLEASE
 NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR SHALL
 OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. PROVIDE
 THE CIVIL DRAWINGS OR REQUEST DEFERRED SUBMITTAL TO BE
 PROVIDED WITH THE GREASE INTERCEPTOR PERMIT.
  
 8) FAILED. P0.1: PROVIDE AN INDIRECT WASTE DETAIL FOR
 THE 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P. SHEETS
 P2.1 & P5.1: THE ISOMETRIC DRAWING ON P5.1 SHOWS A
 DIRECT WASTE CONNECTION FOR THE 3-COMPARTMENT SINK.
 TYPICALLY, A FLOOR SINK IS PROVIDED HOWEVER THE PIPING
 PLAN ON P2.1 SHOWS A FD. PLEASE CORRECT THE DETAIL ON
 P0.1 TO SHOW EACH WELL OF THE SINK DISCHARGING
 INDEPENDENTLY TO THE WASTE RECEPTOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-06-03 Cont ID  
Sent By ccole Date 2021-06-03 Time 09:07 Rev Time 0.00
Received By ccole Date 2021-06-03 Time 08:43 Sent To  
Notes
2021-06-03 09:07:292ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21030143
 6/3/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW LISTED BELOW STILL EXIST. NO CORRECTED OR
 NARRATIVE RESPONSES WERE SUBMITTED.
  
 1) SHEETS P0.1, P2.1, P5.1 PROVIDE THE FOLLOWING GREASE
 INTERCEPTOR INFO AND DETAILS: SIZING CALCULATIONS,
 EQUIPMENT SCHEDULE, ENLARGED PIPING DETAIL THAT SHOWS
 THE LOCATION AND TYPE OF SAMPLING PORT, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR ALL COMPONENTS-
 SECTIONS 1003.3.5 & 1003.3.7 FBC P.
  
 2) P0.1: PLEASE INCLUDE THE MOP SINK, 3-COMPARTMENT
 SINK, PREP SINKS, AND HAND SINKS TO THE FIXTURE
 SCHEDULE- SECTION 107.2.1 WPB. PROVIDE TYPE OF WALL
 FINSH MATERIAL TO BE INSTALLED AROUND THE MOP SINK-
 SECTION 1210.2.2 FBC B.
  
 3) P2.1 & P5.1: PLEASE RELOCATE THE DRAINAGE FROM THE
 HAND SINKS FROM THE GREASE WASTE TO THE SANITARY
 SYSTEM- SECTION 1003.3.1 FBC P. PLEASE NOTE THE CHIEF
 PLUMBING INSPECTOR FOR THE CITY OF WPB HAS RESTRICTED
 HAND SINKS FROM DRAINING INTO THE GREASE WASTE SYSTEM
 BASED ON HIS INTERPRETATION OF THE CODE. PLEASE NOTE
 THAT THE FIXTURES AT THE OUTDOOR BAR MAY ALSO BE
 PROHIBITED- SEE COMMENT #5 NOTES.
  
 4) LS.1.1 & P SHEETS: SHOW THE LOCATION OF THE REQUIRED
 DRINKING FOUNTAINS AND PROVIDE THE PLUMBING PIPING
 DETAILS. IF THE INTENTION IS TO PROVIDE DRINKING WATER
 FREE OF CHARGE, PLEASE PLACE A NOTE ON THE PLAN- TABLE
 403.1 AND SECTION 410.4 FBC P.
  
 5) P2.1, P3.1 & P5.1: PROVIDE THE FIXTURE, APPLIANCE,
 AND EQUIPMENT SCHEDULE THAT CORRELATES WITH THE
 NUMBERED OUTLETS IN THE DRAWINGS- SECTION 107.2.1 WPB.
 A COMPLETE PLUMBING REVIEW CANNOT BE ACCOMPLISHED WITH
 THE SCHEDULE.
  
 6) P5.1: THE KEY NOTES REFERENCE CIVIL DRAWINGS FOR
 POINTS OF CONNECTIONS AND WATER METER AND BACKFLOW
 PREVENTER LOCATIONS- PLEASE PROVIDE THE PLANS. PLEASE
 NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR SHALL
 OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 8) P0.1: PROVIDE AN INDIRECT WASTE DETAIL FOR THE
 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-12 Cont ID  
Sent By ccole Date 2021-04-12 Time 18:35 Rev Time 0.00
Received By ccole Date 2021-04-12 Time 15:52 Sent To  
Notes
2021-04-12 18:36:041ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21030143
 4/12/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P0.1, P2.1, P5.1 PROVIDE THE FOLLOWING GREASE
 INTERCEPTOR INFO AND DETAILS: SIZING CALCULATIONS,
 EQUIPMENT SCHEDULE, ENLARGED PIPING DETAIL THAT SHOWS
 THE LOCATION AND TYPE OF SAMPLING PORT, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR ALL COMPONENTS-
 SECTIONS 1003.3.5 & 1003.3.7 FBC P.
  
 2) P0.1: PLEASE INCLUDE THE MOP SINK, 3-COMPARTMENT
 SINK, PREP SINKS, AND HAND SINKS TO THE FIXTURE
 SCHEDULE- SECTION 107.2.1 WPB. PROVIDE TYPE OF WALL
 FINSH MATERIAL TO BE INSTALLED AROUND THE MOP SINK-
 SECTION 1210.2.2 FBC B.
  
 3) P2.1 & P5.1: PLEASE RELOCATE THE DRAINAGE FROM THE
 HAND SINKS FROM THE GREASE WASTE TO THE SANITARY
 SYSTEM- SECTION 1003.3.1 FBC P. PLEASE NOTE THE CHIEF
 PLUMBING INSPECTOR FOR THE CITY OF WPB HAS RESTRICTED
 HAND SINKS FROM DRAINING INTO THE GREASE WASTE SYSTEM
 BASED ON HIS INTERPRETATION OF THE CODE. PLEASE NOTE
 THAT THE FIXTURES AT THE OUTDOOR BAR MAY ALSO BE
 PROHIBITED- SEE COMMENT #5 NOTES.
  
 4) LS.1.1 & P SHEETS: SHOW THE LOCATION OF THE REQUIRED
 DRINKING FOUNTAINS AND PROVIDE THE PLUMBING PIPING
 DETAILS. IF THE INTENTION IS TO PROVIDE DRINKING WATER
 FREE OF CHARGE, PLEASE PLACE A NOTE ON THE PLAN- TABLE
 403.1 AND SECTION 410.4 FBC P.
  
 5) P2.1, P3.1 & P5.1: PROVIDE THE FIXTURE, APPLIANCE,
 AND EQUIPMENT SCHEDULE THAT CORRELATES WITH THE
 NUMBERED OUTLETS IN THE DRAWINGS- SECTION 107.2.1 WPB.
 A COMPLETE PLUMBING REVIEW CANNOT BE ACCOMPLISHED WITH
 THE SCHEDULE.
  
 6) P5.1: THE KEY NOTES REFERENCE CIVIL DRAWINGS FOR
 POINTS OF CONNECTIONS AND WATER METER AND BACKFLOW
 PREVENTER LOCATIONS- PLEASE PROVIDE THE PLANS. PLEASE
 NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR SHALL
 OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 7) A9.01: PROVIDE AN ACCESSIBLE LAVATORY DETAIL SHOWING
 REQUIRED KNEE AND TOE CLEARANCES- SECTION 606.2 FBC
 ACC.
  
 8) P0.1: PROVIDE AN INDIRECT WASTE DETAIL FOR THE
 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-12-07 Cont ID  
Sent By rmcphers Date 2021-12-07 Time 07:48 Rev Time 0.00
Received By rmcphers Date 2021-12-07 Time 07:48 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-10-05 Cont ID  
Sent By rmcphers Date 2021-10-05 Time 10:34 Rev Time 0.00
Received By rmcphers Date 2021-10-05 Time 10:34 Sent To  
Notes
2021-10-05 10:41:03ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONE 3 WHICH REQUIRE A HIGHER PRESSURE THAN
 THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-97.5) - SEE
 GENERAL LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-12-14 Cont ID  
Sent By rmcphers Date 2021-12-14 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2021-12-14 Time 13:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-12-07 Cont ID  
Sent By rmcphers Date 2021-12-07 Time 07:49 Rev Time 0.00
Received By rmcphers Date 2021-12-07 Time 07:49 Sent To  
Notes
2021-12-07 07:52:59SIGNATURE REVIEW
  
 DOCUMENT LABELED " ROOF ATTACHMENT DETAILS SIGNED.PDF "
 DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-10-05 Cont ID  
Sent By rmcphers Date 2021-10-05 Time 11:00 Rev Time 0.00
Received By rmcphers Date 2021-10-05 Time 11:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-12 Cont ID  
Sent By pvalenti Date 2021-08-12 Time 16:13 Rev Time 0.00
Received By pvalenti Date 2021-08-12 Time 14:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-17 Cont ID  
Sent By pvalenti Date 2021-06-17 Time 09:21 Rev Time 0.00
Received By pvalenti Date 2021-06-17 Time 09:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-07 Cont ID  
Sent By rmcphers Date 2021-04-07 Time 16:17 Rev Time 0.00
Received By rmcphers Date 2021-04-07 Time 16:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2021-09-24 Cont ID  
Sent By ajones Date 2021-09-24 Time 10:26 Rev Time 0.00
Received By ajones Date 2021-09-24 Time 10:26 Sent To  
Notes
2021-09-24 10:27:599/24/21- PASSED WITH THGE PROVISO THAT SEPERATE PERMITS
 ARE REQUIRED FOR LANDSCAPING AND ANY PARKING LOT WORK.
  
 ANGELLA VANN, AICP
 [email protected]
 561-822-1441

Review Stop Z ZONING
Rev No 3 Status F Date 2021-08-24 Cont ID  
Sent By ajones Date 2021-08-24 Time 11:50 Rev Time 0.00
Received By ajones Date 2021-08-24 Time 11:50 Sent To  
Notes
2021-08-24 11:51:188/24/21- FAILED. ALL POSTS MUST BE SETBACK A MINIMUM OF
 5 FEET FROM THE PROPERTY LINE.
  
 ANGELLA VANN
 [email protected]
 561-822-1441

Review Stop Z ZONING
Rev No 2 Status F Date 2021-06-21 Cont ID  
Sent By ajones Date 2021-06-21 Time 11:46 Rev Time 0.00
Received By ajones Date 2021-06-21 Time 11:46 Sent To  
Notes
2021-06-21 11:49:086/20/21- FAILED PLEASE PROVIDE THE SETBACK FOR ALL
 AWNING POSTS.
  
 ANGELLA VANN, AICP
 [email protected]
 5618221441

Review Stop Z ZONING
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By avann Date 2021-04-21 Time 15:55 Rev Time 0.00
Received By ajones Date 2021-04-21 Time 15:55 Sent To  
Notes
2021-04-21 16:59:324-21-21- FAILED
 1. WHAT IS THE SETBACKS AND HEIGHT OF THE PROPOSED WALL
 ALONG S. DIXIE HIGHWAY.
 2. WILL THE AWNING ALONG S. DIXIE BE ATTACHED TO
 ANYTHING BY POSTS?
 3. SEPERATE PERMIT REQUIRED FOR LANDSCAPING.
 4. STAFF WOULD SUGGEST THAT YOU PROVIDE SOME SORT OF
 LANDSCAPING ALONG S DIXIE HWY TO SOFTEN THE APPEARNACE
 OF THE ENTRANCE FROM THE STREET.
  
  
 ANGELLA VANN, AICP
 [email protected]
 561-822-1441