| 2021-04-06 11:46:03 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW |
| | |
| | MEDICAL GAS COMMENTS: DENIED |
| | |
| | 1.PER WPB FBC 107.2.1, INDICATE ON THE PLAN VIEW, THE |
| | EXTENT OF REMOVAL OF MEDICAL GAS AND REROUTING TO THE |
| | NEW CEILING OUTLETS. PROVIDE RISER DIAGRAM OF PIPING |
| | SYSTEMS SHOWING THE SAME. ADD NOTE PROVIDING FOR |
| | REROUTING OF PIPING TO NEW CEILING OUTLETS. |
| | |
| | 2.P1.1 MEDICAL GAS NOTES: ADD NOTE "BRAZING TECHNICIANS |
| | TO BE QUALIFIED AND CERTIFIED IN ACCORDANCE WITH NFPA |
| | 99-15 SECTION 5.1.10.11.11" |
| | |
| | 3.P1.1 MEDICAL GAS NOTES: ADD NOTE "PROVIDE VALVE |
| | ID/SYSTEM IDENTIFICATION/COLOR CODING SPECIFICATION PER |
| | NFPA 99-15 SECTION 5.1.11 THROUGH 5.1.11.5 AND TABLE |
| | 5.1.11" |
| | |
| | 4.P1.1 MEDICAL GAS NOTES: ADD TO NOTE 10; ITEM D |
| | "SEGREGATED TOOL SETS SHALL BE INCORPORATED, IDENTIFIED |
| | AND MAINTAINED; ONE SET SHALL BE FOR OXYGEN AND ONE SET |
| | FOR VACUUM/WAGD". |
| | ADDITIONALLY, ADD TO INSTALLER TESTING NOTES: NOTE B, |
| | "SEGREGATED TOOL SETS WERE INCORPORATED, IDENTIFIED AND |
| | MAINTAINED; ONE SET FOR OXYGEN AND ONE SET FOR |
| | VACUUM/WAGD" |
| | IN LIEU OF REQUIREMENT FOR SEGREGATED TOOL SETS, |
| | SPECIFY THAT VACUUM/WAGD PIPING FULLY COMPLY WITH NOTE |
| | 9 AS REQUIRED FOR PRESSURIZED MEDICAL GAS SYSTEMS. |
| | |
| | 5.P1.1 INSTALLER TESTING NOTES: AMEND NOTE B (1) TO |
| | STATE "THAT ALL BRAZING WAS CONDUCTED BY BRAZERS |
| | QUALIFIED TO ASSE 6000, NFPA 99-15 SECTION 5.1.10.11.11 |
| | AND HOLDING CURRENT MEDICAL GAS ENDORSEMENTS" |
| | |
| | 6.P1.1 INSTALLER TESTING NOTES: ADD TO NOTE B, "ALL |
| | PIPE, VALVES AND FITTINGS WERE CLEANED, CAPPED AND/OR |
| | SEALED IN ACCORDANCE WITH NFPA 99-15 SECTIONS |
| | 5.1.10.1.2 AND 5.1.10.1.3." |
| | |
| | PROVISO: PROVIDE MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR MEDICAL GAS EQUIPMENT |
| | AND COMPONENTS. SEE WPB FBC 107.3.4.1 DEFERRED |
| | SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THEY SHALL |
| | BE SUBMITTED TO, APPROVED BY THE BUILDING OFFICIAL AND |
| | ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN |
| | RISK. |
| | THIS MAY BE DONE BY NOTING SUCH IN THE RESPONSE LETTER |
| | TO THIS REVIEW. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21030140 901 45TH ST |