Plan Review Details - Permit 21030139
Plan Review Stops For Permit 21030139
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-05-17 Cont ID  
Sent By jwitmer Date 2021-05-17 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2021-05-17 Time 10:17 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-03-23 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2021-03-22 Time 14:13 Sent To  
Notes
2021-03-22 15:05:42COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-07-15 Cont ID  
Sent By jwitmer Date 2021-07-15 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2021-07-15 Time 17:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-17 Cont ID  
Sent By jwitmer Date 2021-05-17 Time 11:16 Rev Time 0.00
Received By jwitmer Date 2021-05-17 Time 10:15 Sent To  
Notes
2021-05-17 11:17:10WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21030139
 ADD: 901 45TH ST. ST. MARY?S / REPLACEMENT OF MRI
 EQUIPMENT.
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: MONDAY, MAY 17TH/ 2021
 ACTION: DENIED
  
 1) 2ND REQUEST/ SEMI-COMPLIED. A NEW GENERIC CUT
 SECTION OF A ROOF TOP CURB IS SHOWN. THE DETAIL DOES
 NOT INDICATE THE TYPE OF ROOF DECK. IF CONCRETE OR IF
 THIS ROOF DECK IS COMPOSED OF A BAR JOIST SYSTEM AND
 METAL B DECKING, SPACING OF BAR JOIST, POINT LOADING OF
 THE BAR JOIST, IF NEW METAL ANGLE IRON IS NEEDED TO
 FORM THE SUPPORT FRAMING FOR THE NEW ROOF TOP RTU. THE
 DETAIL ALSO FAILS TO PROVIDE THE PROPOSED ANCHORING
 SYSTEM OF THE RTU UNIT TO THE CURB, NO CALCULATIONS
 WERE SUBMITTED. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED, SEE 1ST ROUND OF COMMENTS.
  
 1ST ROUND OF COMMENTS. SHEET A2.1 NOTE # 7STATES NEW
 ROOF CURB & MECHANICAL VENT (OUTSIDE AIR INTAKE FAN).
 SEE MECHANICAL PLANS. SHEET M1.0 DETAIL FOR NEW ROOF
 CURB AND LOW PROFILE OUTSIDE AIR INTAKE FAN. THERE ARE
 NO DETAILS IN EITHER THE ARCHITECTURAL OR MECHANICAL
 PLANS FOR THE ROOF FRAMING AROUND THE NEW ROOF TOP
 OPENING. HOW THE ROOF TOP CURB AND FAN ARE GOING TO BE
 ANCHORED TO THE MWFRS (MAIN WIND FORCE RESISTING
 SYSTEM).
  
 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 1A)(1) 2ND REQUEST. THE NEW DETAIL ON SHEET A8.1 DETAIL
 16 DOES NOT STATE THE TYPE OF ROOF DECK.
 1ST ROUND OF COMMENTS. THE STEEL ROOF FRAMING MEMBERS
 AND ROOF DECK PANELS WILL NEED TO BE EITHER BOLTED OR
 WELDED ON HE JOBSITE FOR INSTALLATION. WELDED OR BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 1A)(2) NEW COMMENT. SHEET A8.1 DIRECTLY BELOW THE NEW
 DETAIL 16 THERE IS A DETAIL # 15 AND WITHIN THE NOTE IT
 STATES THE CONTRACTOR TO VERIFY THAT HARDWARE USED IN
 THE MRI PROCEDURE ROOM DOES NOT CONTAIN FERROUS METALS,
 DOES THIS ALSO INCLUDE THE AREA DIRECTLY ABOVE THE
 ENCLOSED ROOM, FOR EXAMPLE IF THERE IS BAR JOIST OR IF
 A CONCRETE DECK RE-BAR IN THE DECK ITSELF AND OR THE
 ROOF TOP CURB AND RTU? 107.2.1.2 ADDITIONAL INFORMATION
 NEEDED.
  
 1B) SEMI-COMPLIED. NO PRODUCT INFORMATION WAS SUPPLIED
 FOR THE ROOF TOP CURB. 2020 FBC-B 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(D) ROOFING PRODUCTS AND ASSEMBLIES,
 ROOF TOP CURBS & ROOF TOP VENTILATORS,
  
 1C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 2) SEMI-COMPLIED. THIS REVIEW CYCLE THERE IS NO WIND
 DESIGN CRITERIA PROVIDED. 2020 FBC-B 1603.1.4 WIND
 DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO WIND
 LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS
 GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM
 OF THE STRUCTURE:
  
 2.1.COMPLIED. ULTIMATE DESIGN WIND SPEED, VULT,
 (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. 2ND REQUEST. THE EXPOSURE GIVEN IS AN B EXPOSURE.
 ST. MARY?S IS LOCATED ON THE TOP OF A HILL AND THE ONLY
 LARGE STRUCTURE AROUND, WE BELIEVE THIS IS AN C
 EXPOSURE, OR SURFACE ROUGHNESS C. OPEN TERRAIN WITH
 SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS
 THAN 30 FEET IN HEIGHT.
 RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 2.4. COMPLIED. APPLICABLE INTERNAL PRESSURE
 COEFFICIENT.
 2.5. 2ND REQUEST. NO PRESSURES WERE GIVEN FOR THE ROOF
 TOP OR THE EQUIPMENT TO BE LOCATED ON THE ROOF TOP.
 DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
 2.6. 2ND REQUEST. TABLE 1609.7(2) ADJUSTMENT FACTORS
 FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR
 THE BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND
 SPEED CONVERSION VULT TO VASD.
  
 3) 2ND REQUEST. ANY INFORMATION BEING SENT TO THE
 BUILDING DEPARTMENT NEEDS TO FOLLOW STATE STATUTES IN
 REGARDS TO ARCHITECTURAL REVIEW. A SHOP DRAWING STAMP
 OF REVIEW AND APPROVAL. THE 24-PAGE SIGNA ARTIST IPM
 FINAL STUDY IS NOT SIGNED NOR SEALED BY AN ENGINEER OR
 SHOP DRAWING STAMP OF APPROVAL BY THE DESIGNER OF
 RECORD. FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE
 FOR SUPERVISING AND REVIEWING ALL PROJECT DATA,
 REPORTS, SHOP DRAWINGS ETC.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-03-22 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2021-03-22 Time 14:13 Sent To  
Notes
2021-03-22 15:07:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21030139
 ADD: 901 45TH ST. ST. MARY?S / REPLACEMENT OF MRI
 EQUIPMENT.
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MONDAY, MARCH 22ND/ 2021
 ACTION: DENIED
  
 1) SHEET A2.1 NOTE # 7STATES NEW ROOF CURB & MECHANICAL
 VENT (OUTSIDE AIR INTAKE FAN). SEE MECHANICAL PLANS.
 SHEET M1.0 DETAIL FOR NEW ROOF CURB AND LOW PROFILE
 OUTSIDE AIR INTAKE FAN. THERE ARE NO DETAILS IN EITHER
 THE ARCHITECTURAL OR MECHANICAL PLANS FOR THE ROOF
 FRAMING AROUND THE NEW ROOF TOP OPENING. HOW THE ROOF
 TOP CURB AND FAN ARE GOING TO BE ANCHORED TO THE MWFRS
 (MAIN WIND FORCE RESISTING SYSTEM).
  
 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
 1A) THE STEEL ROOF FRAMING MEMBERS AND ROOF DECK PANELS
 WILL NEED TO BE EITHER BOLTED OR WELDED ON HE JOBSITE
 FOR INSTALLATION. WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
 1B) 2020 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS: (31)(D) ROOFING
 PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS & ROOF TOP
 VENTILATORS
 1C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
 2) THIS REVIEW CYCLE THERE IS NO WIND DESIGN CRITERIA
 PROVIDED. 2020 FBC-B 1603.1.4 WIND DESIGN DATA. THE
 FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL BE
 SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2.2. RISK CATEGORY.
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
 3) THE 24-PAGE SIGNA ARTIST IPM FINAL STUDY IS NOT
 SIGNED NOR SEALED BY AN ENGINEER OR SHOP DRAWING STAMP
 OF APPROVAL BY THE DESIGNER OF RECORD. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-01 Cont ID  
Sent By jleahy Date 2021-06-01 Time 07:44 Rev Time 0.00
Received By jleahy Date 2021-06-01 Time 07:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-31 Cont ID  
Sent By jleahy Date 2021-03-31 Time 12:44 Rev Time 0.00
Received By jleahy Date 2021-03-31 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-02-09 Cont ID  
Sent By jleahy Date 2022-02-09 Time 15:49 Rev Time 0.00
Received By jleahy Date 2022-02-09 Time 15:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-07-15 Cont ID  
Sent By pleduc Date 2021-07-15 Time   Rev Time 0.00
Received By pleduc Date 2021-07-15 Time 09:16 Sent To  
Notes
2021-07-15 09:17:13FIRE PROVISO:
  
 ANY FIRE SPRINKLER AND/OR FIRE ALARM WORK, INCLUDING
 DEMO SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
 THE FS & FA SYSTEM SHALL BE MAINTAINED THROUGHOUT DEMO
 AND CONSTRUCTION.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-05-11 Cont ID  
Sent By pleduc Date 2021-05-11 Time   Rev Time 0.00
Received By pleduc Date 2021-05-11 Time 13:07 Sent To  
Notes
2021-05-11 13:07:30FIRE PROVISO:
  
 ANY FIRE SPRINKLER AND/OR FIRE ALARM WORK, INCLUDING
 DEMO SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
 THE FS & FA SYSTEM SHALL BE MAINTAINED THROUGHOUT DEMO
 AND CONSTRUCTION.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-09 Cont ID  
Sent By pleduc Date 2021-03-09 Time   Rev Time 0.00
Received By pleduc Date 2021-03-09 Time 13:23 Sent To  
Notes
2021-03-09 13:30:51FIRE PROVISO:
  
 ANY FIRE SPRINKLER AND/OR FIRE ALARM WORK, INCLUDING
 DEMO SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
 THE FS & FA SYSTEM SHALL BE MAINTAINED THROUGHOUT DEMO
 AND CONSTRUCTION.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-27 Cont ID  
Sent By medwards Date 2021-07-27 Time 11:00 Rev Time 0.00
Received By medwards Date 2021-07-14 Time 10:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-01 Cont ID  
Sent By medwards Date 2021-06-01 Time 11:16 Rev Time 0.00
Received By medwards Date 2021-05-10 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-06 Cont ID  
Sent By jesmith Date 2021-04-06 Time 13:53 Rev Time 0.00
Received By jesmith Date 2021-04-06 Time 13:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-07-27 Cont ID  
Sent By medwards Date 2021-07-27 Time 11:00 Rev Time 0.00
Received By medwards Date 2021-07-27 Time 11:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-01 Cont ID  
Sent By medwards Date 2021-06-01 Time 11:08 Rev Time 0.00
Received By medwards Date 2021-06-01 Time 11:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-01 Cont ID  
Sent By medwards Date 2021-04-01 Time 08:12 Rev Time 0.00
Received By medwards Date 2021-04-01 Time 08:12 Sent To  
Notes
2021-04-01 08:13:101ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21030139
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.2: NOTE (2) IS REFERENCING THE NEW CRAC-3
 BUT NOTE (2) IS SHOWN AS DUCT WORK IN THE BLOWER BOX
 CLOSET INSIDE THE MRI ROOM. PLEASE SHOW NOTE
 REFERENCING THE DUCTWORK. FBC 107.2.1
  
 2) SEE BUILDING REVIEWER COMMENTS FOR MECHANICAL
 EQUIPMENT ON THE ROOF.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status P Date 2021-07-27 Cont ID  
Sent By jesmith Date 2021-07-27 Time 10:17 Rev Time 0.00
Received By jesmith Date 2021-07-27 Time 10:16 Sent To  
Notes
2021-07-27 10:17:35MEDICAL GAS COMMENTS: APPROVED
  
 PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE AS A
 DEFERRED SUBMITTAL, THE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE MEDICAL GAS
 WALL OUTLETS. THE DOCUMENTS SHALL BE SUBMITTED AS A
 SUPPORTING DOCUMENT WITH REQUIRED ARCHITECT'S STAMP AND
 SIGNATURE, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION. PROCEED AT YOUR OWN RISK.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030139 901 45TH ST
  

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status F Date 2021-05-13 Cont ID  
Sent By jesmith Date 2021-05-13 Time 12:48 Rev Time 0.00
Received By jesmith Date 2021-05-11 Time 16:51 Sent To  
Notes
2021-05-13 12:45:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
  
 MEDICAL GAS COMMENTS: DENIED
  
 NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR
 THE SUPPORT OF HORIZONTAL PIPING. INCLUDE STRUCTURAL
 ATTACHMENTS, ROD SIZE, HANGER TYPE AND HORIZONTAL
 SPACING REQUIREMENTS.
  
 PROVISO: PROVIDE MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR MEDICAL GAS EQUIPMENT
 AND COMPONENTS. SEE IN ACCORDANCE WITH WPB FBC
 107.3.4.1 DEFERRED SUBMITTALS AND AS ACKNOWLEDGED IN
 THE RESPONSE LETTER DATED 4/20/2021; PROVIDE
 MANUFACTURER'S SPECIFICATION SHEETS/INSTALLATION MANUAL
 FOR MEDICAL GAS EQUIPMENT AND COMPONENTS. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THEY SHALL BE SUBMITTED TO, APPROVED BY THE BUILDING
 OFFICIAL AND ON SITE PRIOR TO FINAL INSPECTION.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030139 901 45TH ST
  

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2021-04-06 Cont ID  
Sent By jesmith Date 2021-04-06 Time 13:53 Rev Time 0.00
Received By jesmith Date 2021-04-06 Time 12:04 Sent To  
Notes
2021-04-06 13:52:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
  
 MEDICAL GAS COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, PROVIDE RISER DIAGRAM OF NEW
 MEDICAL GAS PIPING SYSTEMS TO REFLECT THE PLAN VIEW.
  
 2. P1.1 MEDICAL GAS NOTES, NOTE 2: PER WPB FBC 107.2.1,
 DELETE ITEMS B) AND C).
  
 3. P1.1 MEDICAL GAS NOTES: ADD NOTE "BRAZING
 TECHNICIANS TO BE QUALIFIED AND CERTIFIED IN ACCORDANCE
 WITH NFPA 99-15 SECTION 5.1.10.11.11"
  
 4. P1.1 MEDICAL GAS NOTES: ADD NOTE "PROVIDE VALVE
 ID/SYSTEM IDENTIFICATION/COLOR CODING SPECIFICATION PER
 NFPA 99-15 SECTION 5.1.11 THROUGH 5.1.11.5 AND TABLE
 5.1.11 "
  
 5. P1.1 MEDICAL GAS NOTES: ADD TO NOTE 10; ITEM D)
 "SEGREGATED TOOL SETS SHALL BE INCORPORATED, IDENTIFIED
 AND MAINTAINED; ONE SET SHALL BE FOR OXYGEN AND ONE SET
 FOR VACUUM/WAGD".
 IN LIEU OF REQUIREMENT FOR SEGREGATED TOOL SETS,
 SPECIFY THAT VACUUM/WAGD PIPING FULLY COMPLY WITH NOTE
 9 AS REQUIRED FOR PRESSURIZED MEDICAL GAS SYSTEMS.
  
 PROVISO: PROVIDE MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR MEDICAL GAS EQUIPMENT
 AND COMPONENTS. SEE WPB FBC 107.3.4.1 DEFERRED
 SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THEY SHALL
 BE SUBMITTED TO, APPROVED BY THE BUILDING OFFICIAL AND
 ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN
 RISK.
 THIS MAY BE DONE BY NOTING SUCH IN THE RESPONSE LETTER
 TO THIS REVIEW.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030139 901 45TH ST
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-07-27 Cont ID  
Sent By jesmith Date 2021-07-27 Time 08:59 Rev Time 0.00
Received By jesmith Date 2021-07-27 Time 08:54 Sent To  
Notes
2021-07-27 08:59:41PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030139 901 45TH ST

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-05-13 Cont ID  
Sent By jesmith Date 2021-05-13 Time 13:34 Rev Time 0.00
Received By jesmith Date 2021-05-11 Time 16:51 Sent To  
Notes
2021-05-13 13:34:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 NEW COMMENTS: REGARDING CONDENSATE DISCHARGE TO THE
 EXISTING FLOOR DRAIN AND ELIMINATION OF TRIPPING
 HAZARD.
  
 1.IT IS BROUGHT TO MY ATTENTION THAT PER WPB CODE OF
 ORDINANCE CHAPTER 90, ARTICLE 3, SECTION 90-12B5, A/C
 CONDENSATE SHALL NOT DISCHARGE TO THE CITY UTILITIES
 SANITARY SEWAGE INFRASTRUCTURE WITHOUT PERMISSION FROM
 THE UTILITIES DEPARTMENT. YOU MAY CONTACT MR. MANNY
 GONZALES IN ENGINEERING AT 561-494-1128 FOR ADDITIONAL
 INFORMATION. MOVING FORWARD, DISCHARGE THE CONDENSATE
 TO AN EXTERIOR DRYWELL; PER WPB FBC 107.2.1, PROVIDE
 ROUTING AND DRYWELL DETAIL.
  
 2. DUE TO THE RAISED FLOOR, PLEASE NOTE THAT PER FBC PL
 413.2, READY ACCESS SHALL BE PROVIDED TO FLOOR DRAINS.
 READY ACCESS IS DEFINED IN FBC PL CHAPTER 2,
 DEFINITIONS AS THAT WHICH ENABLES A FIXTURE, APPLIANCE
 OR EQUIPMENT TO BE DIRECTLY REACHED WITHOUT REQUIRING
 THE REMOVAL OR MOVEMENT OF ANY PANEL, DOOR OR SIMILAR
 OBSTRUCTION AND WITHOUT THE USE OF A PORTABLE LADDER,
 STEP STOOL OR SIMILAR DEVICE.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND
 FS.END OF COMMENTS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030139 901 45TH ST

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-06 Cont ID  
Sent By jesmith Date 2021-04-06 Time 13:48 Rev Time 0.00
Received By jesmith Date 2021-04-06 Time 12:04 Sent To  
Notes
2021-04-06 13:48:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. RE: A8.1/DETAIL 1AND 3; COUNTERTOP IS NOTED TO BE
 MAXIMUM 2 FEET 10 INCHES (34 INCHES) VERTICAL DISTANCE
 FROM FINISH FLOOR TO TOP. PER WPB FBC 107.2.1, PROVIDE
 NOTE AT DETAILS STATING ?LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND PER FBC ACC 606.3.?
  
 2. RE: A1.1; PER WPB FBC 107.2.1, PROVIDE ON PLAN,
 CLEAR FLOOR SPACE AND APPROACH FOR NEW ACCESSIBLE SINK
 AS REQUIRED BY FBC ACC 305.3 AND 804.3.1.
  
 3. RE: P1.1, NOTE 2; PER WPB FBC 107.2.1, PROVIDE
 PIPING SPECIFICATIONS FOR DOMESTIC WATER (PIPE VALVES,
 FITTINGS). NOTE ALL COMPONENTS SHALL BE LEAD FREE TO
 COMPLY WITH FBC PL 605.2.
 PROVIDE SPECIFICATION FOR HOT WATER INSULATION AS MAY
 BE REQUIRED PER FBC PL E607.5.
  
 4. RE: P1.1, NOTE 3; PER WPB FBC 107.2.1, PROVIDE A
 SLAB REPAIR DETAIL. SHOW THE WIDTH OF THE REPAIR, THE
 MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED, AND
 THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF
 THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE
 EXISTING SLAB, THE ANCHORING MATERIAL FOR THE DOWELS
 AND THE SPACING OF THE DOWELS ON CENTER. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND
 THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED SOIL. A
 COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR A
 FINAL INSPECTION.
  
 5. RE: P1.1, NOTE 3 AND 4; PER WPB FBC 107.2.1, PROVIDE
 PIPING SPECIFICATIONS FOR SANITARY WASTE AND VENT
 PIPING.
  
 6. RE: P1.1, NOTE 5 AND 6; PER WPB FBC 107.2.1, SPECIFY
 TYPE AND THICKNESS OF INSULATION REQUIRED FOR
 CONDENSATE DRAINS.
  
 7. RE: P1.1, NOTE 5; PER WPB FBC 107.2.1, PROVIDE A
 DETAIL FOR THE CONDENSATE DISCHARGE TO THE EXISTING
 DRYWELL.
  
 8. RE: P1.1, NOTE 6; PER WPB FBC 107.2.1, PROVIDE A
 DETAIL FOR THE CONDENSATE DISCHARGE TO THE EXISTING
 FLOOR DRAIN. PROVIDE PROTECTION TO ELIMINATE ANY
 TRIPPING HAZARD THAT MIGHT OCCUR DUE TO THIS
 INSTALLATION.
  
 9. PER WPB FBC 107.2.1, PROVIDE HANGER DETAIL FOR
 HORIZONTAL PIPING INCLUDING BUT NOT LIMITED TO HANGER
 TYPE, ROD TYPE, SHIELDS AND STRUCTURAL ATTACHMENTS.
 PROVIDE SCHEDULE FOR ROD SIZE. REFERENCE FBC PL 308.5
 FOR SPACING.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030139 901 45TH ST
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-27 Cont ID  
Sent By jesmith Date 2021-07-27 Time 10:26 Rev Time 0.00
Received By jesmith Date 2021-07-27 Time 10:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-01 Cont ID  
Sent By medwards Date 2021-06-01 Time 11:16 Rev Time 0.00
Received By medwards Date 2021-06-01 Time 11:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-01 Cont ID  
Sent By medwards Date 2021-04-01 Time 08:23 Rev Time 0.00
Received By medwards Date 2021-04-01 Time 08:23 Sent To  
Notes
2021-04-01 08:25:38THE MEP SHEETS ARE INVALID AS THE ENGINEERS HAVE SELF
 CERTIFIED THEIR SIGNATURES.PLEASE HAVE THE DIGITAL
 SIGNATURES THIRD PARTY CERTIFIED.
  
 61G15?23.004 F.A.C.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS: (A) UNIQUE TO THE PERSON USING IT; (B) CAPABLE OF
 VERIFICATION; AS OF NOVEMBER 16, 2020 63 (C) UNDER THE
 SOLE CONTROL OF THE PERSON USING IT; AND, (D) LINKED TO
 A DOCUMENT IN SUCH A MANNER THAT THE DIGITAL SIGNATURE
 AND CORRESPONDINGLY THE DOCUMENT IS INVALIDATED IF ANY
 DATA IN THE DOCUMENT IS CHANGED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  