Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-09 Cont ID  
Sent By equinone Date 2021-04-09 Time 08:14 Rev Time 0.00
Received By equinone Date 2021-04-09 Time 08:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By equinone Date 2021-03-24 Time 16:24 Rev Time 0.00
Received By equinone Date 2021-03-24 Time 16:11 Sent To  
Notes
2021-03-24 16:27:24CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) PLEASE CHANGE CODE REFERENCES TO FBC 2020 7TH
 EDITION AND NEC 2017
 2) GROUNDING ELECTRODE CONDUCTOR FOR 7.5 KVA
 TRANSFORMER MUST BE AT LEAST #8 CU (NEC 250.66)
 3) SEE SIGNATURE COMMENTS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-12 Cont ID  
Sent By medwards Date 2021-04-12 Time 08:08 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 11:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-26 Cont ID  
Sent By medwards Date 2021-03-26 Time 17:26 Rev Time 0.00
Received By medwards Date 2021-03-17 Time 12:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-04-12 Cont ID  
Sent By medwards Date 2021-04-12 Time 08:07 Rev Time 0.00
Received By medwards Date 2021-04-12 Time 08:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-03-26 Cont ID  
Sent By medwards Date 2021-03-26 Time 17:22 Rev Time 0.00
Received By medwards Date 2021-03-26 Time 17:22 Sent To  
Notes
2021-03-26 17:25:58PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
 PLEASE INCLUDE ON THE DRAWING THE LOCATION OF THE
 ELEVATOR MACHINE ROOM AND A ROOF DRAWING SHOWING THE
 LOCATION OF THE CONDENSER. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-09 Cont ID  
Sent By equinone Date 2021-04-09 Time 08:15 Rev Time 0.00
Received By equinone Date 2021-04-09 Time 08:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By equinone Date 2021-03-24 Time 16:28 Rev Time 0.00
Received By equinone Date 2021-03-24 Time 16:28 Sent To  
Notes
2021-03-24 16:30:19CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 PLANS ARE MISSING THE ELECTRONIC/DIGITAL SIGNATURE.
  
 DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A DIGITALLY SIGNED PLAN IS
 NOT CONSIDERED AN ORIGINAL, PDF MUST HAVE THE
 INTEGRATED DIGITAL SIGNATURE.
  
 EITHER SUBMIT A DIGITALLY OR ELECTRONICALLY SIGNED
 PLAN, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL SIGNED
 AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE.
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  