Plan Review Details - Permit 21021417
Plan Review Stops For Permit 21021417
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-04-08 Cont ID  
Sent By jwitmer Date 2021-04-08 Time 08:21 Rev Time 0.00
Received By jwitmer Date 2021-04-08 Time 08:15 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-03-17 Cont ID  
Sent By jwitmer Date 2021-03-17 Time 10:13 Rev Time 0.00
Received By jwitmer Date 2021-03-17 Time 09:06 Sent To  
Notes
2021-03-17 10:11:11TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-05-10 Cont ID  
Sent By jwitmer Date 2021-05-10 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2021-05-10 Time 07:28 Sent To  
Notes
2021-05-10 07:55:54W. P. B. BUILDING DEPARTMENT HAS
 ALL (3) REQUIRED TEST ON FILE AT CITY HALL
 ON (F) DRIVE FLOOR UNDERLAYMENTS FOR:
  
 PROFLEX SUPER SIM 90 /TILE OR MARBLE
 IIC = 50 DB / 6 INCH SLAB P. T. / NO DROPPED CEILING /
 ASTM E-492
 STC = 52 DB / 6 INCH SLAB P. T./ NO DROPPED / CEILING
 ASTM E-90
 FLAME= 0 ASTM-E84
 SMOKE= 0 ASTM E-84
 J. WITMER BUILD PLAN REVIEW 05/10/2021
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-05-03 Cont ID  
Sent By jwitmer Date 2021-05-03 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2021-05-03 Time 10:00 Sent To  
Notes
2021-05-03 10:08:20WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21021417
 ADD: 529 S. FLAGLER DR.
 CONT: ALBRIGHT CONSTRUCTION
 TEL: 561-547-7433
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDI2) NG CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. MAY03RD/ 2021
 ACTION: DENIED
  
 1) THE 3RD REVIEW WAS COMPLETED ON 4/19/2021 WITH
 REVISION # 3. THERE HAS BEEN NO CHANGES MADE TO THE
 PLAN SINCE THE LAST CONVERSATION WITH TODD KENNY. THE
 SHEET PROPOSED CONDITIONS IN THE DETAIL TYPICAL
 NON-BEARING WALL SECTION AT THE BOTTOM OF THE DETAIL
 LIST THE PROPOSED UNDERLAYMENT AS PROFLEX 90. PLEASE BE
 AWARE THERE IS A PROFLEX PRODUCT NAMED PROFLEX SUPER
 SIM 90. THE OTHER ISSUE IS THAT THE DESIGNER OF RECORD
 HAS NOT LISTED THE FINISH FLOOR MATERIAL, IT IS STATED
 AS TBD (TO BE DETERMINED). THE INFORMATION ON THE PLANS
 HAS TO BE SPECIFIC FOR CODE COMPLIANCE. THEN AT THE END
 OF THE NOTE IT STATES OR AN EQUAL SOUND ATTENUATION
 MATERIAL. THERE CAN BE NO ALTERNATIVES. ONCE THE FLOOR
 FINISHES ARE PICKED AND UNDERLAYMENT IS KNOWN THAT IS
 WHEN YOU RESUBMIT. AFTER PERMIT ISSUANCE IF THERE IS A
 CHANGE IN EITHER THE FINISH FLOOR MATERIAL OR
 UNDERLAYMENT THEN THAT IS CONSIDERED A REVISION.
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2020 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
 2ND ROUND OF COMMENTS. THE SPEC SHEET FOR PROFLEX MSC
 MEGA SOUND CONTROL UNDERLAYMENT SOUND PROOFING IS
 NOTHING MORE THAN A SALES BROCHURE. TO DATE WE DO NOT
 HAVE PROFLEX MSC IN OUR FOLDER OF APPROVED FLOOR
 UNDERLAYMENT SYSTEMS. THE CITY IS IN RECEIPT OF PROFLEX
 SUPER SIM 90 W/ PORCELAIN TILE. THIS REPORT AND BE USED
 WITH TILE AND OR MARBLE. COMPLIED.
 THE CITY OF WEST PALM BEACH REQUIRES THE ACTUAL TEST
 REPORTS LISTED BELOW.
  
 FLOOR INSULATION (FBC-B 2020). FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2-3) COMPLIED.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-04-26 Cont ID  
Sent By jwitmer Date 2021-04-26 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2021-04-26 Time 09:31 Sent To  
Notes
2021-04-26 10:00:02WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21021417
 ADD: 529 S. FLAGLER DR.
 CONT: ALBRIGHT CONSTRUCTION
 TEL: 561-547-7433
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDI2) NG CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. APRIL 26TH/ 2021
 ACTION: DENIED
  
 1) SEMI-COMPLIED. THE SHEET PROPOSED CONDITIONS IN THE
 DETAIL TYPICAL NON-BEARING WALL SECTION AT THE BOTTOM
 OF THE DETAIL LIST THE PROPOSED UNDERLAYMENT AS PROFLEX
 90. PLEASE BE AWARE THERE IS A PROFLEX PRODUCT NAMED
 PROFLEX SUPER SIM 90. THE OTHER ISSUE IS THAT THE
 DESIGNER OF RECORD HAS NOT LISTED THE FINISH FLOOR
 MATERIAL, IT IS STATED AS TBD (TO BE DETERMINED). THE
 INFORMATION ON THE PLANS HAS TO BE SPECIFIC FOR CODE
 COMPLIANCE. THEN AT THE END OF THE NOTE IT STATES OR AN
 EQUAL SOUND ATTENUATION MATERIAL. THERE CAN BE NO
 ALTERNATIVES. ONCE THE FLOOR FINISHES ARE PICKED AND
 UNDERLAYMENT IS KNOWN THAT IS WHEN YOU RESUBMIT. AFTER
 PERMIT ISSUANCE IF THERE IS A CHANGE IN EITHER THE
 FINISH FLOOR MATERIAL OR UNDERLAYMENT THEN THAT IS
 CONSIDERED A REVISION.
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2020 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
 2ND ROUND OF COMMENTS. THE SPEC SHEET FOR PROFLEX MSC
 MEGA SOUND CONTROL UNDERLAYMENT SOUND PROOFING IS
 NOTHING MORE THAN A SALES BROCHURE. TO DATE WE DO NOT
 HAVE PROFLEX MSC IN OUR FOLDER OF APPROVED FLOOR
 UNDERLAYMENT SYSTEMS. THE CITY IS IN RECEIPT OF PROFLEX
 SUPER SIM 90 W/ PORCELAIN TILE. THIS REPORT AND BE USED
 WITH TILE AND OR MARBLE. COMPLIED.
 THE CITY OF WEST PALM BEACH REQUIRES THE ACTUAL TEST
 REPORTS LISTED BELOW.
  
 FLOOR INSULATION (FBC-B 2020). FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2-3) COMPLIED.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-08 Cont ID  
Sent By jwitmer Date 2021-04-08 Time 08:32 Rev Time 0.00
Received By jwitmer Date 2021-04-08 Time 08:15 Sent To  
Notes
2021-04-08 08:31:56WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21021417
 ADD: 529 S. FLAGLER DR.
 CONT: ALBRIGHT CONSTRUCTION
 TEL: 561-547-7433
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDI2) NG CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. APRIL 08TH/ 2021
 ACTION: DENIED
  
 1) THE SPEC SHEET FOR PROFLEX MSC MEGA SOUND CONTROL
 UNDERLAYMENT SOUND PROOFING IS NOTHING MORE THAN A
 SALES BROCHURE. TO DATE WE DO NOT HAVE PROFLEX MSC IN
 OUR FOLDER OF APPROVED FLOOR UNDERLAYMENT SYSTEMS. THE
 CITY IS IN RECEIPT OF PROFLEX SUPER SIM 90 W/ PORCELAIN
 TILE. THIS REPORT AND BE USED WITH TILE AND OR MARBLE.
 COMPLIED.
 THE CITY OF WEST PALM BEACH REQUIRES THE ACTUAL TEST
 REPORTS LISTED BELOW.
  
 FLOOR INSULATION (FBC-B 2020). FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2-3) COMPLIED.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-17 Cont ID  
Sent By jwitmer Date 2021-03-17 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2021-03-17 Time 09:06 Sent To  
Notes
2021-03-17 09:07:57WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21021417
 ADD: 529 S. FLAGLER DR.
 CONT: ALBRIGHT CONSTRUCTION
 TEL: 561-547-7433
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDI2) NG CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MARCH 17TH/ 2021
 ACTION: DENIED
  
 1) THE SPEC SHEET FOR SUPER SAM 125 UNDERLAYMENT SOUND
 PROOFING IS NOTHING MORE THAN A SALES BROCHURE. TO DATE
 WE DO NOT HAVE SUPER SAM 125 IN OUR FOLDER OF APPROVED
 FLOOR UNDERLAYMENT SYSTEMS.
 THE CITY OF WEST PALM BEACH REQUIRES THE ACTUAL TEST
 REPORTS LISTED BELOW.
  
 FLOOR INSULATION (FBC-B 2020). FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2)FLOOR PLAN-PROPOSED CONDITIONS.
 2A) THE MASTER BATHROOM THE TUB LOCATION CHANGES, WHICH
 WILL MEAN A NEW PENETRATION THROUGH THE POST TENSION
 FLOOR SYSTEM. THE FLOOR WILL NEED TO BE X-RAYED TO
 LOCATE THE LOCATION OF THE EXISTING POST TENSIONED
 CHORDS. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2B) THE PROPOSED NEW TUB LOCATION AND CORED HOLE
 THROUGH THE FIRE RATED FLOOR SYSTEM WILL NEED TO
 PROVIDE COMPLIANCE WITH 2020 FBC-B SECTION 714.4.1.2
 THROUGH-PENETRATIONS FIRE STOP SYSTEMS FOR HORIZONTAL
 (FLOOR) SYSTEMS. THE SYSTEM SHALL HAVE AN F RATING/ T
 RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE
 REQUIRED RATING OF THE FLOOR PENETRATED. SEE TABLE 601
 FLOOR RATINGS FOR TYPE I-A & I-B BUILDINGS REQUIRE A 2
 HOUR FLOOR RATING.
  
 2C) THE FLOOR PLAN IS SILENT AS TO THE TYPE OF BACKER
 BOARD FOR THE SHOWER AND TUB FOR ALL BATHROOMS.
 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 3) FOR FUTURE REFERENCE. THE DETAIL DRYWALL TO CEILING
 IS DRAWN BACKWARDS. THE TWO FLANGES SHOULD BE DRAWN
 NEXT TO THE CONCRETE CEILING SO THEY CAN BE SHOT INTO
 THE CONCRETE AND THE RAISED WIDE CENTER SECTION GIVE
 THE DRYWALL HANGER SOMETHING TO SECURE THE DRYWALL TOO.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-05-05 Cont ID  
Sent By equinone Date 2021-05-05 Time 14:23 Rev Time 0.00
Received By equinone Date 2021-05-05 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-04-23 Cont ID  
Sent By equinone Date 2021-04-23 Time 10:36 Rev Time 0.00
Received By equinone Date 2021-04-23 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-04-14 Cont ID  
Sent By equinone Date 2021-04-14 Time 16:41 Rev Time 0.00
Received By equinone Date 2021-04-14 Time 09:11 Sent To  
Notes
2021-04-14 16:56:24CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) WORKING CLEARANCES FOR ELECTRICAL PANEL DOES NOT
 SEEM TO COMPLY WITH NEC 210.26
 2) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN
 EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL
 UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65
 LUMENS-PER-WATT?. A NOTE WILL SUFFICE. FBC EC R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-04 Cont ID  
Sent By equinone Date 2021-03-04 Time 16:07 Rev Time 0.00
Received By equinone Date 2021-03-04 Time 15:59 Sent To  
Notes
2021-03-04 16:08:11CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SCOPE OF WORK NOT CLEAR. SHEET 002 (PROPOSED
 CONDITIONS) SHOWS THAT NO ELECTRICAL WORK IS BEING IN
 MASTER ROOM, GUEST ROOM AND LIVING ROOM. HOWEVER, SHEET
 004 (ELECTRICAL LAYOUT) SEEMS TO INDICATE THAT NEW
 ELECTRICAL WORK IS BEING DONE. PLEASE CLARIFY WHAT IS
 THE ACTUAL SCOPE OF ELECTRICAL WORK.
 2) PLEASE SHOW LOCATION OF METER, MAIN SERVICE
 DISCONNECT, AND ELECTRICAL PANELBOARD.
 3) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN
 EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL
 UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65
 LUMENS-PER-WATT?. A NOTE WILL SUFFICE. FBC EC R404.1
 4) PLEASE SPECIFY RATINGS FOR MAIN SERVICE DISCONNECT
 AND ELECTRICAL PANEL. PLEASE ALSO SPECIFY AIC RATING OF
 EXISTING DISCONNECT AND ELECTRICAL PANEL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-04-08 Cont ID  
Sent By pleduc Date 2021-04-08 Time   Rev Time 0.00
Received By pleduc Date 2021-04-08 Time 12:46 Sent To  
Notes
2021-04-08 12:47:43THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 2) DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 3) THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 4) WITH ANY REMOVAL OF WALLS/CEILINGS, ENSURE CODE
 COMPLIANT SPRINKLER HEAD COVERAGE IS MAINTAINED.
  
 ANY REQUIRED FIRE SPRINKLER WORK SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-03 Cont ID  
Sent By pleduc Date 2021-03-03 Time   Rev Time 0.00
Received By pleduc Date 2021-03-03 Time 13:32 Sent To  
Notes
2021-03-03 13:37:58THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 2) DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 3) THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 4) WITH ANY REMOVAL OF WALLS/CEILINGS, ENSURE CODE
 COMPLIANT SPRINKLER HEAD COVERAGE IS MAINTAINED.
  
 ANY REQUIRED FIRE SPRINKLER WORK SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2021-05-10 Time 07:58 Rev Time 0.00
Received By aoliver Date 2021-05-07 Time 14:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-06 Cont ID  
Sent By rmcdouga Date 2021-05-06 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2021-04-27 Time 10:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-04-26 Time   Rev Time 0.00
Received By aoliver Date 2021-04-20 Time 08:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-04-16 Time   Rev Time 0.00
Received By aoliver Date 2021-04-06 Time 12:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-03-19 Time   Rev Time 0.00
Received By aoliver Date 2021-02-26 Time 13:31 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-03-17 Time 10:13 Rev Time 0.00
Received By jwitmer Date 2021-03-17 Time 10:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-03-08 Cont ID  
Sent By medwards Date 2021-03-08 Time 15:03 Rev Time 0.00
Received By medwards Date 2021-03-08 Time 15:03 Sent To  
Notes
2021-03-08 15:04:24NO MECHANICAL WORK SHOWN FOR THIS PROJECT.ME

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-05-04 Cont ID  
Sent By ccole Date 2021-05-04 Time 14:26 Rev Time 0.00
Received By ccole Date 2021-05-04 Time 13:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-04-26 Cont ID  
Sent By ccole Date 2021-04-26 Time 16:29 Rev Time 0.00
Received By ccole Date 2021-04-26 Time 16:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-04-16 Cont ID  
Sent By ccole Date 2021-04-16 Time 11:16 Rev Time 0.00
Received By ccole Date 2021-04-16 Time 10:21 Sent To  
Notes
2021-04-16 11:17:102ND REVIEW FBC-2020 PLUMBING
 PERMIT-21021417
 4/16/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET EP1: THE NEW RISER DRAWING SHOWS RELOCATED TUB
 AND SHOWER DRAINS DRAINING INTO A VENT PIPE. THE
 RELOCATED DRAINS SHALL CONNECT TO A SANITARY BRANCH
 DRAIN OR A HORIZONTAL OR VERTICAL WET VENT LINE- SEE
 SECTIONS 912.1, 912.1.1, 912.2, 912.2.1, AND 912.2.2
 FBC P. IF THE INTENTION IS TO SHOW A COMMON VENT FOR
 THE TWO FIXTURES, THEN THE VENT CONNECTION SHALL BE AT
 THE INTERCONNECTION OF THE FIXTURE DRAINS OR DOWNSTREAM
 OF THE INTERCONNECTION- SECTIONS 911.1 & 911.2 FBC P.
  
 2) 2ND REQUEST FOR A SHOWER PAN DETAIL- SECTION 421.5.2
 FBC P.
  
 3) BASED ON THE ISOMETRIC AND COMMENT RESPONSE
 INDICATING RELOCATED DRAINS, I AM MAKING A 2ND REQUEST
 FOR A FIRESTOPPING DETAIL. NEW DRAIN PIPE PENETRATIONS
 OF THE EXISTING SLAB WILL REQUIRE FIRESTOPPING TO SEAL
 THE ANNULAR SPACE AROUND THE PIPING. PROVIDE A UL
 TESTED AND APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE
 PLAN- SECTIONS 315.1 FBC P & 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By ccole Date 2021-03-19 Time 12:12 Rev Time 0.00
Received By ccole Date 2021-03-19 Time 11:39 Sent To  
Notes
2021-03-19 12:14:021ST REVIEW FBC-2020 PLUMBING
 PERMIT-21021417
 3/19/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 02: PROVIDE A SANITARY RISER DRAWING FOR THE
 NEW SHOWER AND TUB IN THE MASTER BATH- SECTION
 107.3.5.3.1 WPB. PLEASE NOTE IF THE EXISTING TRAPS ARE
 TO BE REUSED, REFER TO SECTION 1002.1: THE HORIZONTAL
 DISTANCE FROM THE CENTERLINE OF THE NEW SHOWER DRAIN
 OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING
 TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A NOTE ON THE
 PLAN INDICATING COMPLIANCE.
  
 2) 02: PROVIDE A SHOWER PAN DETAIL- SECTION 421.5.2 FBC
 P.
  
 3) 02: SHOW THE SHOWER DOOR LOCATIONS AND DIMENSIONS-
 SECTION 421.4.2 FBC P.
  
 3) 02: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW SHOWER
 AND BATHTUB VALVES SHOWING MAKES, MODELS, AND LISTING
 AND COMPLIANCE STANDARDS- SECTIONS 412.3 & 412.5 FBC P.
  
 4) 02: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTIONS
 315.1 FBC P & 714.4.1.2 FBC B.
  
 5) 02: SHOW THE SCOPE OF WORK FOR THE WASHING MACHINE-
 SECTION 107.2.21 WPB. IS IT BEING REPLACED OR
 RELOCATED?
  
 6) ) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-05-07 Cont ID  
Sent By medwards Date 2021-05-07 Time 16:33 Rev Time 0.00
Received By medwards Date 2021-05-07 Time 16:31 Sent To  
Notes
2021-05-07 16:33:51ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-04-27 Cont ID  
Sent By medwards Date 2021-04-27 Time 11:18 Rev Time 0.00
Received By medwards Date 2021-04-27 Time 11:17 Sent To  
Notes
2021-04-27 11:19:56ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-21 Cont ID  
Sent By medwards Date 2021-04-21 Time 09:12 Rev Time 0.00
Received By medwards Date 2021-04-21 Time 09:09 Sent To  
Notes
2021-04-21 09:13:24ORIGINAL SIGNED AND SEALED PAPER DRAWING IS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-06 Cont ID  
Sent By medwards Date 2021-04-06 Time 16:48 Rev Time 0.00
Received By medwards Date 2021-04-06 Time 16:47 Sent To  
Notes
2021-04-06 16:49:44ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 06:35 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 06:35 Sent To  
Notes
2021-03-01 06:38:00ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop Z ZONING
Rev No 1 Status N Date 2021-03-04 Cont ID  
Sent By elevesqu Date 2021-03-04 Time 16:47 Rev Time 0.00
Received By elevesqu Date 2021-03-04 Time 16:47 Sent To  
Notes
***NONE***