Plan Review Details - Permit 21021363
Plan Review Stops For Permit 21021363
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-03-05 Cont ID  
Sent By cpuell Date 2021-03-05 Time 14:49 Rev Time 0.00
Received By cpuell Date 2021-03-05 Time 14:49 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-03-01 Cont ID  
Sent By cpuell Date 2021-03-01 Time 10:18 Rev Time 0.00
Received By cpuell Date 2021-03-01 Time 10:18 Sent To  
Notes
2021-03-01 10:18:21NEED A SITE PLAN OR THE WHOLE PROJECT, ALL THE
 PROPERTIES NEED TO BE ADDRESSES. PLEASE CONTACT
 [email protected] TO ESTABLISH ADDRESSES FOR THIS PROJECT

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-05-11 Cont ID  
Sent By cthroop Date 2021-05-11 Time 13:07 Rev Time 0.00
Received By cthroop Date 2021-05-11 Time 13:06 Sent To  
Notes
2021-05-11 13:07:26PROVISO ON PLAN PAGE A-2LD: PROVIDE A SURVEY, SITE PLAN
 W/FF ELEVATION, SITE DRAINAGE P.
 GEOTECHNICAL REPORT ON-FILE. SEE MASTER PERMIT
 21021363. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-05-08 Cont ID  
Sent By cthroop Date 2021-05-08 Time 09:43 Rev Time 0.00
Received By cthroop Date 2021-05-08 Time 09:39 Sent To  
Notes
2021-05-08 09:45:30PROVISO ON PLAN PAGE A-2LD: PROVIDE A SURVEY, SITE PLAN
 W/FF ELEVATION, SITE DRAINAGE PLAN AND A SOILS REPORT
 OF PAD CERTIFICATION FOR EACH NEW SFR PERMIT. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-28 Cont ID  
Sent By cthroop Date 2021-04-28 Time 09:09 Rev Time 0.00
Received By cthroop Date 2021-04-27 Time 06:22 Sent To  
Notes
2021-04-28 09:25:49PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. PROVIDE A SURVEY, A SITE PLAN AND SITE DRAINAGE
 PLAN.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN) CITY AMENDMENTS
  
 PROVIDE A SITE PLAN. DRAINAGE/SURVEY
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
  
 FBC R401.3 SITE DRAINAGE
  
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 ADDITIONAL COMMENTS FOR # 1 ABOVE:
 1(A) A SITE DRAINAGE PLAN IS REQUIRED FOR EACH LOT PER
 107.2.5 AND R401.3.
  
  
 2. PROVIDE A SOILS REPORT.
  
 ADDITIONAL COMMENTS FOR # 2 ABOVE:
 2(A) THE GEOTECHNICAL ENGINEERING REPORT FOR THE ENTIRE
 SITE WAS PROVIDED FOR REVIEW.
 2(B) PROVIDE A COPY OF THE BUILDING PAD CERTIFICATION
 FOR EACH LOT PER FBC 1803.5.8.
 1803.5.8 COMPACTED FILL MATERIAL.
 WHERE SHALLOW FOUNDATIONS WILL BEAR ON COMPACTED FILL
 MATERIAL MORE THAN 12 INCHES (305 MM) IN DEPTH, A
 GEOTECHNICAL INVESTIGATION SHALL BE CONDUCTED AND SHALL
 INCLUDE ALL OF THE FOLLOWING:
 1. 1.SPECIFICATIONS FOR THE PREPARATION OF THE SITE
 PRIOR TO PLACEMENT OF COMPACTED FILL MATERIAL.
 2. 2.SPECIFICATIONS FOR MATERIAL TO BE USED AS
 COMPACTED FILL.
 3. 3.TEST METHODS TO BE USED TO DETERMINE THE MAXIMUM
 DRY DENSITY AND OPTIMUM MOISTURE CONTENT OF THE
 MATERIAL TO BE USED AS COMPACTED FILL.
 4. 4.MAXIMUM ALLOWABLE THICKNESS OF EACH LIFT OF
 COMPACTED FILL MATERIAL.
 5. 5.FIELD TEST METHOD FOR DETERMINING THE IN-PLACE DRY
 DENSITY OF THE COMPACTED FILL.
 6. 6.MINIMUM ACCEPTABLE IN-PLACE DRY DENSITY EXPRESSED
 AS A PERCENTAGE OF THE MAXIMUM DRY DENSITY DETERMINED
 IN ACCORDANCE WITH ITEM 3.
 7. 7.NUMBER AND FREQUENCY OF FIELD TESTS REQUIRED TO
 DETERMINE COMPLIANCE WITH ITEM 6.
  
  
 3. PROVIDE FINISHED FLOOR ELEVATION.
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 ADDITIONAL COMMENTS FOR # 3 ABOVE:
 3(A) THE OVERALL DRAINAGE PLAN, SHEET 2A, STATES A
 MINIMUM FINISHED FLOOR ELEVATION OF 21.60 FOR THE SITE.
 PROVIDE A SITE PLAN AND AN ACCURATE AND INCLUDED
 BOUNDARY LINE SURVEY STATING THE PROPOSED FINISHED
 FLOOR ELEVATION FOR EACH LOT PER 107.2.5. AND
 R403.1.7.3.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By cthroop Date 2021-03-18 Time 15:53 Rev Time 0.00
Received By cthroop Date 2021-03-16 Time 13:05 Sent To  
Notes
2021-03-18 16:10:13PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A SURVEY, A SITE PLAN AND SITE DRAINAGE
 PLAN.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN) CITY AMENDMENTS
  
 PROVIDE A SITE PLAN. DRAINAGE/SURVEY
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
  
 FBC R401.3 SITE DRAINAGE
  
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 2. PROVIDE A SOILS REPORT OR A COPY OF THE BUILDING PAD
 CERTIFICATION FROM THE PROJECT GEO-TECHNICAL ENGINEER.
  
 FBC 1803.1 GENERAL. GEOTECHNICAL INVESTIGATIONS SHALL
 BE CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6.
  
 1803.2 INVESTIGATIONS REQUIRED.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN
 ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5.
 EXCEPTION: THE BUILDING OFFICIAL SHALL BE PERMITTED TO
 WAIVE THE REQUIREMENT FOR A GEOTECHNICAL INVESTIGATION
 WHERE SATISFACTORY DATA FROM ADJACENT AREAS IS
 AVAILABLE THAT DEMONSTRATES AN INVESTIGATION IS NOT
 NECESSARY FOR ANY OF THE CONDITIONS IN SECTIONS
 1803.5.1 THROUGH 1803.5.6 AND SECTIONS 1803.5.10 AND
 1803.5.11.
  
 3. PROVIDE FINISHED FLOOR ELEVATION.
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-19 Cont ID  
Sent By equinone Date 2021-04-19 Time 15:10 Rev Time 0.00
Received By equinone Date 2021-04-19 Time 15:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-04 Cont ID  
Sent By equinone Date 2021-03-04 Time 16:45 Rev Time 0.00
Received By equinone Date 2021-03-04 Time 16:45 Sent To  
Notes
2021-03-04 16:45:59CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEET C1 -ELECTRICAL NOTE 20: NEW FBC EC R404
 REQUIRES:
  
 "NOT LESS THAN 90 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LUMINAIRES SHALL HAVE AN EFFICACY OF AT LEAST
 45 LUMENS-PER-WATT OR SHALL UTILIZE LAMPS WITH AN
 EFFICACY OF NOT LESS THAN 65 LUMENS-PER-WATT?.
  
 PLEASE CHANGE NOTE AS INDICATED. FBC EC R404.1
  
 2) GFCI/WP RECEPTACLE IS REQUIRED AT BACK OF DWELLING
 UNIT 210.52(E)(1)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-03-18 Cont ID  
Sent By cthroop Date 2021-03-18 Time 15:32 Rev Time 0.00
Received By cthroop Date 2021-03-16 Time 13:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-05-11 Cont ID  
Sent By lcrespo Date 2021-05-11 Time 10:39 Rev Time 0.00
Received By lcrespo Date 2021-05-11 Time 10:39 Sent To  
Notes
2021-05-11 10:39:4705/11/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-04-22 Cont ID  
Sent By lcrespo Date 2021-04-22 Time 08:13 Rev Time 0.00
Received By lcrespo Date 2021-04-22 Time 08:13 Sent To  
Notes
2021-04-22 08:14:1204/22/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT CALCULATIONS FOR COMBUSTION AIR PER
 THE 2020 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES
 DRYERS). IF LOUVER WILL BE USED. PLEASE SHOW THE
 LOCATION AND SIZE OF THE LOUVER(S) ON THE PLANS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 3. PLEASE SHOW THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 5. PLEASE LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC
 RES. SEC. G2413.
  
 6. PLEASE SHOW THE DISTANCE FROM THE POINT OF DELIVERY
 (GAS METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 8. THE GAS GRILL AND IT SEEMS TO BE IN A COVERED PATIO,
 IF SO PLEASE PROVIDE THE MANUFACTURE'S RECOMMENDATION
 FOR A VENTILATION HOOD PER THE 2020 FBC RES. SEC.
 G2408.1.
  
 9. NEED A HARD CAP FOR FUTURE RANGE SHOW ON GAS
 ISOMERIC PER THE 2020 FBC RES. SEC. G2401.1.3.
  
 10. IF THIS UNIT REQUIRES A CONDENSATE, IT WILL NEED TO
 BE 1' AWAY FROM STRUCTURE PER THE 2020 FBC SEC R318.5.
  
 11. PLEASE SHOW THE LOCATION OF THE TANK-LESS WATER
 HEATER AND THE LOCATION AND DISTANCE OF ANY OPERABLE
 DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 12. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.2.
  
 13. PLEASE LABEL THE SHUT-OFF VALVE ON GAS ISOMERIC AND
 THEY SHALL HAVE ACCESS TO THEM PER THE 2020 FBC RES.
 SEC. G2420.5.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-04-13 Cont ID  
Sent By lcrespo Date 2021-04-13 Time 11:14 Rev Time 0.00
Received By lcrespo Date 2021-04-13 Time 11:13 Sent To  
Notes
2021-04-13 11:14:38GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-03-19 Cont ID  
Sent By lcrespo Date 2021-03-19 Time 06:34 Rev Time 0.00
Received By lcrespo Date 2021-03-19 Time 06:34 Sent To  
Notes
2021-03-19 06:34:46GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-11 Cont ID  
Sent By cthroop Date 2021-05-11 Time 13:45 Rev Time 0.00
Received By cthroop Date 2021-05-10 Time 14:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-28 Cont ID  
Sent By cthroop Date 2021-04-28 Time 09:25 Rev Time 0.00
Received By cthroop Date 2021-04-09 Time 11:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-23 Cont ID  
Sent By pvalenti Date 2021-03-23 Time 08:12 Rev Time 0.00
Received By pvalenti Date 2021-02-26 Time 09:58 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2021-05-10 Cont ID  
Sent By shill Date 2021-05-10 Time 09:22 Rev Time 0.00
Received By shill Date 2021-05-10 Time 09:22 Sent To  
Notes
2021-05-10 09:30:47IMPACT FEES TO BE PAID UNDER BUILDING PERMITS
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-03-23 Cont ID  
Sent By pvalenti Date 2021-03-23 Time 08:10 Rev Time 0.00
Received By pvalenti Date 2021-03-23 Time 08:09 Sent To  
Notes
2021-03-23 08:11:33****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-03-09 Cont ID  
Sent By medwards Date 2021-03-09 Time 13:39 Rev Time 0.00
Received By medwards Date 2021-03-09 Time 12:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-05-11 Cont ID  
Sent By lcrespo Date 2021-05-11 Time 10:39 Rev Time 0.00
Received By lcrespo Date 2021-05-11 Time 10:39 Sent To  
Notes
2021-05-11 10:40:3205/11/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-04-22 Cont ID  
Sent By lcrespo Date 2021-04-22 Time 08:33 Rev Time 0.00
Received By lcrespo Date 2021-04-22 Time 08:33 Sent To  
Notes
2021-04-22 08:41:4104/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-04-13 Cont ID  
Sent By lcrespo Date 2021-04-13 Time 11:13 Rev Time 0.00
Received By lcrespo Date 2021-04-13 Time 11:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By lcrespo Date 2021-03-19 Time 06:39 Rev Time 0.00
Received By lcrespo Date 2021-03-19 Time 06:30 Sent To  
Notes
2021-03-19 06:40:0303/19/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. ON PAGE A-1L;
 A. IT SHOWS A GAS TANK-LESS. PLEASE PROVIDE A NOTE ON
 PLANS THAT A SEPARATE PERMIT SHALL BE SUBMITTED FOR GAS
 PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 B. THE TANKLESS HOT WATER LINES ON THE OUTSIDE SHALL
 HAVE INSULATED MINIMUM R-3 PER THE 2017 FBC SEC. RE
 403.5.3. PLEASE PLACE A NOTE.
  
 C. IF THIS HAS A CONDENSATE, IT WILL NEED TO BE 1' AWAY
 FROM THE STRUCTURE PER THE 2017 FBC SEC. R318.5.
  
 D. PLEASE SHOW THE TANK-LESS WATER HEATER'S LOCATION
 AND THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 3. ON SHEET S1L AND S1R;
 A. THE LAUNDRY TRAY IS NOT SHOW NEXT TO WASHING
 MACHINE.
  
 B. IN BATH THREE THE SINK IS NOT SIZED.
  
 PLEASE CORRECT THESE ITEMS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2021-03-18 Cont ID  
Sent By cthroop Date 2021-03-18 Time 15:21 Rev Time 0.00
Received By cthroop Date 2021-03-16 Time 13:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-11 Cont ID  
Sent By cthroop Date 2021-05-11 Time 13:44 Rev Time 0.00
Received By cthroop Date 2021-05-11 Time 13:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-28 Cont ID  
Sent By cthroop Date 2021-04-28 Time 09:09 Rev Time 0.00
Received By cthroop Date 2021-04-27 Time 06:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By cthroop Date 2021-03-18 Time 15:21 Rev Time 0.00
Received By cthroop Date 2021-03-16 Time 13:05 Sent To  
Notes
2021-03-18 15:24:22PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: MECHANICAL PLANS
  
  
 1. THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD
 SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN
 SHEETS UNDER THEIR AUTHORITY.
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
  
 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL
 WITH SIGNATURE OF DESIGNER AS APPLICABLE; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT OR DROP
 OFF (OR MAIL) ONE PAPER ORIGINAL WITH CONTRACTORS/O/B
 SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-04-26 Cont ID  
Sent By ajones Date 2021-04-22 Time 10:57 Rev Time 0.00
Received By ajones Date 2021-04-22 Time 10:57 Sent To  
Notes
2021-04-22 10:58:274/21/21-4/21/21-PASS. AT TIME THE INDIVIDUAL LOTS ARE
 SUBMITED FOR BUILDING PERMIT ZONING WILL THE SURVEY
 AND/OR SITE PLAN SHOWING THE LOCATION/SETBACKS OF THE
 HOME FROM THE PROPERTY LINE.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-22 Cont ID  
Sent By aaponte Date 2021-03-22 Time 10:26 Rev Time 0.00
Received By ajones Date 2021-03-22 Time 10:26 Sent To  
Notes
2021-03-22 10:35:133/22/21-FAILED- SURVEY/SITE PLAN SHOWING SETBACKS FROM
 THE PROPERTY LINES FOR THE HOUSE/ADDITION.
  
 ANGELLA VANN, AICP
 [email protected]
 561-822-1441