| 2021-03-15 16:57:44 | PLAN REVIEW / ROOFING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: THIS APPLICATION IS FOR A ROOF OVER. |
| | |
| | 1. SUBMIT ANALYSIS REPORT OF EXISTING ROOF BY A DESIGN |
| | PROFESSIONAL. |
| | R908.3 RECOVERING VERSUS REPLACEMENT. |
| | NEW ROOF COVERINGS SHALL NOT BE INSTALLED WITHOUT FIRST |
| | REMOVING ALL EXISTING LAYERS OF ROOF COVERINGS WHERE |
| | ANY OF THE FOLLOWING CONDITIONS OCCUR: |
| | 1.WHERE THE EXISTING ROOF OR ROOF COVERING IS WATER |
| | SOAKED OR HAS DETERIORATED TO THE POINT THAT THE |
| | EXISTING ROOF OR ROOF COVERING IS NOT ADEQUATE AS A |
| | BASE FOR ADDITIONAL ROOFING. |
| | 2.WHERE THE EXISTING ROOF COVERING IS WOOD SHINGLE OR |
| | SHAKE, SLATE, CLAY, CEMENT OR ASBESTOS-CEMENT TILE. |
| | 3.WHERE THE EXISTING ROOF HAS TWO OR MORE APPLICATIONS |
| | OF ANY TYPE OF ROOF COVERING. |
| | 4.WHEN BLISTERS EXIST IN ANY ROOFING, UNLESS BLISTERS |
| | ARE CUT OR SCRAPED OPEN AND REMAINING MATERIALS SECURED |
| | DOWN BEFORE APPLYING ADDITIONAL ROOFING. |
| | 5.WHERE THE EXISTING ROOF IS TO BE USED FOR ATTACHMENT |
| | FOR A NEW ROOF SYSTEM AND COMPLIANCE WITH THE |
| | SECUREMENT PROVISIONS OF SECTION R905 CANNOT BE MET. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |