Plan Review Details - Permit 21021309
Plan Review Stops For Permit 21021309
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 13:41 Rev Time 0.00
Received By jleahy Date 2021-05-13 Time 13:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-10 Cont ID  
Sent By jleahy Date 2021-03-10 Time 16:21 Rev Time 0.00
Received By jleahy Date 2021-03-10 Time 16:14 Sent To  
Notes
2021-03-10 16:27:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SEPARATE PERMIT REQUIRED FOR THE GENERATOR.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-05-14 Cont ID  
Sent By lcrespo Date 2021-05-14 Time 15:14 Rev Time 0.00
Received By lcrespo Date 2021-05-14 Time 15:14 Sent To  
Notes
2021-05-14 15:15:3405/14/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-14 Cont ID  
Sent By lcrespo Date 2021-05-14 Time 15:15 Rev Time 0.00
Received By lcrespo Date 2021-05-12 Time 09:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-10 Cont ID  
Sent By jleahy Date 2021-03-10 Time 16:28 Rev Time 0.00
Received By jleahy Date 2021-03-01 Time 08:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-05-14 Cont ID  
Sent By lcrespo Date 2021-05-14 Time 15:14 Rev Time 0.00
Received By lcrespo Date 2021-05-14 Time 15:14 Sent To  
Notes
2021-05-14 15:15:1705/14/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-09 Cont ID  
Sent By lcrespo Date 2021-03-09 Time 11:48 Rev Time 0.00
Received By lcrespo Date 2021-03-09 Time 10:30 Sent To  
Notes
2021-03-09 11:49:3603/09/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 THESE COMMENTS BELOW ARE NOT FOR THE ENGINEER AND CAN
 BE ADDRESSED BY THE GENERAL CONTRACTOR. SOME REDLINE
 WILL BE DONE ON PLANS BY YOURS TRULY FOR THE GAS
 PORTION.
  
 1. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS(GENERATOR AND
 TANKLESS) EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC
 RES. SEC. G 305.1.
  
 2. PLEASE SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE FBC RES. SEC. G 410.1.
  
 3. REDLINE, PIPES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. CE
 404.4.
  
 4. REDLINE, IF THE TANKLESS HAS A CONDENSATE, IT WILL
 NEED TO BE 1' AWAY FROM THE STRUCTURE PER THE 2017 FBC
 SEC. R318.5.
  
 5. REDLINE, SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC FG SEC 410.2.
  
 6. REDLINE, LABEL THE SHUTOFF VALVE UNION ON GAS
 ISOMERIC PER THE 2017 FBC FG SEC. 409.4.
  
 7. A LICENSED CONTRACTOR HAS APPLIED FOR A GAS PERMIT
 FOR THE SCOPE OF WORK. IT HAS COMMENTS THAT HAVE NOT
 BEEN ADDRESSED BUT ARE IN THIS REVISION. PLEASE MAKE
 THE GAS A SUB PERMIT AND REFER IT TO THIS AS A MASTER
 AND LAPEL; PER PLANS, PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  
 8. AN ELECTRICAL PERMIT IS REQUIRED FOR THE GENERATOR
 BY A LICENSED CONTRACTOR PER THE WPB AMENDMENTS TO THE
 FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 13:41 Rev Time 0.00
Received By jleahy Date 2021-05-13 Time 13:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-10 Cont ID  
Sent By jleahy Date 2021-03-10 Time 16:28 Rev Time 0.00
Received By jleahy Date 2021-03-10 Time 16:27 Sent To  
Notes
***NONE***