| Plan Review Stops For Permit 21021282 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-15 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-15 |
Time |
17:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-15 |
Time |
06:26 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-15 |
Time |
06:26 |
Sent To |
|
|
| Notes |
| 2021-03-15 06:26:42 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21021282 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THIS IS A LESS THAN 2 PSI SYSTEM WITH A TOTAL | | | DEVELOPED LENGTH OF 90 FEET. WITHOUT ANY OTHER | | | INFORMATION ABOUT THE TYPE OF SYSTEM I MUST ASSUME THAT | | | THE DESIGNER IS USING THE LONGEST LENGTH METHOD FOR | | | SIZING THIS SYSTEM. BASED ON THE REFERENCED TABLE AT 90 | | | FEET FOR THE NEW RANGE THE ?? PIPE IS UNDERSIZED. BASED | | | ON THE SAME TABLE THE NEW TOTAL LOAD HAS INCREASED SO | | | THE 1? PIPE FROM THE METER TO THE FIRST T FITTING IS | | | ALSO UNDERSIZED. AS THE BTU?S FOR THE EXISTING WATER | | | HEATER AND DRYER ARE NOT GIVEN AND THE PIPE SIZING FOR | | | THIS BRANCH IS NOT GIVEN I CANNOT SIZE THIS EXISTING | | | BRANCH WITH THE NEW TOTAL DEVELOPED LENGTH. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2021-03-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-05 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-05 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2021-03-05 15:29:54 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21021282 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P0.1: ON THE GAS ISOMETRIC I SEE THAT THE | | | REGULATOR HAS BEEN REMOVED FROM THE AREA AT THE GAS | | | METER. THIS MAKES THIS APPEARS TO MAKE THE ENTIRE | | | SYSTEM A 2 PSI SYSTEM. WAS THE EXISTING SYSTEM A 2 PSI | | | SYSTEM? I DO NOT SEE ANY REGULATORS TO DROP THE | | | PRESSURE BEFORE THE EXISTING APPLIANCES. THE GAS TABLE | | | USED FOR SIZING THIS SYSTEM IS STILL SHOWN TO BE T. | | | 402.4(2) WHICH IS A LESS THAN 2 PSI TABLE. PLEASE | | | RECHECK THE ENTIRE SYSTEM AND PROVIDE A COMPLETE CODE | | | COMPLIANT GAS RISER DIAGRAM. FBC 107.2.1, FBC FG | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-03-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-02 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-02 |
Time |
07:05 |
Sent To |
|
|
| Notes |
| 2021-03-02 07:05:38 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21021252 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P3.1 INDICATES THE TOTAL LENGTH TO THE GRILL | | | IS 90?, SHEET P0.1 INDICATES THE TOTAL LENGTH TO SIZE | | | PIPING SYSTEM TO BE 50?. PLEASE PROVIDE THE TOTAL | | | DEVELOPED LENGTH FROM THE METER TO THE MOST REMOTE | | | APPLIANCE. FBC FG 402.4.1 | | | | | | 2) SHEET P0.1: PLEASE CORRECT THE HEADING FOR THE | | | 8?-11? GAS SYSTEM. FBC 107.2.1 | | | | | | 3) SHEET P0.1: GAS ISOMETRIC INDICATES THIS IS A LOW | | | PRESSURE SYSTEM AND HAS AN MP REGULATOR SHORTLY AFTER | | | THE METER. PLEASE REMOVE NOTE 5 OF THE GAS NOTES. FBC | | | 107.2.1 | | | | | | 4) PLEASE PROVIDE PIPE SIZING FROM REGULATOR TO THE | | | FIRST ?T? FITTING AS THIS PIECE OF PIPE IS CARRYING THE | | | ENTIRE SYSTEM?S BTU LOAD. FBC FG 402.3 | | | | | | 5) PLEASE PROVIDE THE COMBUSTION AIR CALCULATION FOR | | | THE NEW GAS RANGE. FBC FG 304.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-15 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-15 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-15 |
Time |
06:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-11 |
Time |
08:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-03-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-05 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-04 |
Time |
15:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-03-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-02 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-25 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-03-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-05 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-05 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-03-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-02 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-02 |
Time |
07:06 |
Sent To |
|
|
| Notes |
| 2021-03-02 07:09:07 | PLEASE OBTAIN A MECHANICAL PERMIT FOR THE HOOD OVER | | | THIS RANGE. FBC 107.2.1 | | | PLEASE LABEL THE FAN USED IN THIS NEW HOOD. IF THE | | | CFM'S ARE OVER 800 THEN PLEASE SHOW THE MAKE UP AIR FOR | | | THIS RANGE HOOD. FBC RES M1503.4 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-15 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-15 |
Time |
06:27 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-15 |
Time |
06:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2021-03-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-05 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-05 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2021-03-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-02 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-02 |
Time |
07:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-15 |
Time |
06:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-15 |
Time |
06:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-03-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-05 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-05 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-03-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-02 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-02 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2021-03-02 07:12:18 | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|