Plan Review Details - Permit 21021206
Plan Review Stops For Permit 21021206
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-03-25 Cont ID  
Sent By cpuell Date 2021-03-25 Time 09:15 Rev Time 0.00
Received By cpuell Date 2021-03-25 Time 09:15 Sent To  
Notes
2021-03-25 09:15:42APPLICANT IDENTIFIED UNIT A - PERMIT UPDATED.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By cpuell Date 2021-03-19 Time 12:36 Rev Time 0.00
Received By cpuell Date 2021-03-19 Time 12:36 Sent To  
Notes
2021-03-19 12:37:25IS THIS WORK FOR UNITS A B C D OR FOR ALL UNITS. PLEASE
 EMAIL [email protected] WITH RESPONCE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-27 Cont ID  
Sent By jleahy Date 2021-03-27 Time 10:46 Rev Time 0.00
Received By jleahy Date 2021-03-27 Time 10:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-22 Cont ID  
Sent By pleduc Date 2021-03-22 Time   Rev Time 0.00
Received By pleduc Date 2021-03-22 Time 13:47 Sent To  
Notes
2021-03-22 13:55:47THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
  
 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED
 EGRESS
 DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE
 PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL
 LOCKING SYSTEMS
 RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED
 THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF
 THE ELECTRICAL
 LOCK IS AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY
 OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING
 CONDITIONS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE
 DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE
 POWER SUPPLY TO
 THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION
 OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY ELECTRICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-05 Cont ID  
Sent By lcrespo Date 2021-04-05 Time 13:12 Rev Time 0.00
Received By lcrespo Date 2021-04-02 Time 07:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-27 Cont ID  
Sent By jleahy Date 2021-03-27 Time 10:46 Rev Time 0.00
Received By jleahy Date 2021-03-17 Time 12:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-05 Cont ID  
Sent By lcrespo Date 2021-04-05 Time 13:12 Rev Time 0.00
Received By lcrespo Date 2021-04-05 Time 13:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-27 Cont ID  
Sent By jleahy Date 2021-03-27 Time 10:45 Rev Time 0.00
Received By jleahy Date 2021-03-27 Time 10:45 Sent To  
Notes
2021-03-27 10:46:30PLANS NOT SIGNED BY QUALIFIER JLEAHY