Plan Review Details - Permit 21021166
Plan Review Stops For Permit 21021166
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-06-02 Cont ID  
Sent By cpuell Date 2021-06-02 Time 12:18 Rev Time 0.00
Received By cpuell Date 2021-06-02 Time 12:18 Sent To  
Notes
2021-06-02 12:18:59UNITS READDRESSED, THIS UNIT HAS BEEN GIVEN THE ADDRESS
 OF 5307 S DIXIE HWY, UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-05-03 Cont ID  
Sent By cpuell Date 2021-05-03 Time 15:42 Rev Time 0.00
Received By cpuell Date 2021-05-03 Time 15:42 Sent To  
Notes
2021-05-03 15:42:16UNIT 4 IS NOT A LEGAL ADDRESS, PLEASE PROVIDE A FLOOR
 PLAN SHOWING ALL THE UNITS IN THE BUILDING, PLEASE
 EMAIL DOCUMENTS TO [email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By cpuell Date 2021-03-19 Time 16:53 Rev Time 0.00
Received By cpuell Date 2021-03-19 Time 16:53 Sent To  
Notes
2021-03-19 16:54:17UNIT 4 IS NOT A LEGAL ADDRESS, PLEASE PROVIDE A FLOOR
 PLAN SHOWING ALL THE UNITS IN THE BUILDING, PLEASE
 EMAIL DOCUMENTS TO [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-08 Cont ID  
Sent By equinone Date 2021-06-08 Time 08:09 Rev Time 0.00
Received By equinone Date 2021-06-08 Time 08:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-05-05 Cont ID  
Sent By equinone Date 2021-05-05 Time 11:42 Rev Time 0.00
Received By equinone Date 2021-05-05 Time 11:38 Sent To  
Notes
2021-05-05 11:48:32CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 PERMIT 21021166
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SCOPE OF WORK NOT CLEAR. APPLICATION ONLY MENTIONS A
 NEW ELECTRICAL SERVICE, BUT DRAWINGS SEEM TO INDICATE
 ADDITIONAL ELECTRICAL WORK BEING DONE (NEW LIGHTS,
 RECEPTACLES, EQUIPMENT, ETC)
  
 PLEASE INDICATE CLEARLY THE SCOPE OF WORK. THE
 APPLICATION ONLY MENTIONS A NEW ELECTRICAL SERVICE BUT
 THERE IS A LOT OF OTHER ELECTRICAL WORK ON DRAWINGS.
 INDICATE WHAT IS EXISTING OR WHAT IS NOT COVERED UNDER
 THIS PERMIT.
  
 2) SHEET E-03 (ELECTRICAL RISER DIAGRAMS) : GROUNDING
 ELECTRODE CONDUCTOR TO EXISTING WATER PIPE MUST BE AT
 LEAST #4 CU OR #2 AL FOR SERVICE CONDUCTORS #3/0 AND
 ABOVE. NEC 250.66
  
 NOT CORRECTED.
  
 3) PLEASE CHANGE CODE REFERENCES TO NEC 2017 AND FBC
 2020, 7TH EDITION FBC 107
  
 NOT CORRECTED'
  
 4) PLEASE SEE SIGNATURE COMMENTS.
  
 CORRECTED FOR ELECTRICAL DRAWINGS
  
 5) IT SEEMS THAT DUPLICATE DRAWINGS HAVE BEEN UPLOADED
 (THERE ARE THREE E-01S, TWO E-02S, AND TWO E-03S).
 PLEASE CLARIFY WHICH VERSIONS ARE THE ONES THAT NEED TO
 BE REVIEWED AND REMOVE THE ONES THAT SHOULD NOT BE
 USED. FBC
  
 PARTIALLY CORRECTED. DUPLICATE DRAWINGS STILL PRESENT.
  
 6) SHEET E-2 MENTIONS THAT NEW ELECTRIC SERVICE IS
 UNDERGROUND BY FPL BUT SHEET E-3 (ELECTRICAL RISER
 DIAGRAM #3) SAYS THAT SERVICE IS OVERHEAD. PLEASE
 CLARIFY AND CORRECT. FBC 107
  
  
 7) SHEET E-2: THERE IS A NOTE THAT READS ELECTRICAL
 PANEL. WHICH PANEL IS THIS? IS IT ELECTRICAL PANEL A?
  
 PLEASE SHOW LOCATION OF ALL PANELS AND CLEARLY LABELED
 THEM
  
 8) NEW COMMENT
  
 ELECTRICAL DRAWINGS CAN NOT BE APPROVED UNTIL ADDRESS
 COMMENTS ARE RESOLVED.
  
 END OF COMMENTS.
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 PHONE 561-805-6746.
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By equinone Date 2021-03-19 Time 12:19 Rev Time 0.00
Received By equinone Date 2021-03-19 Time 12:19 Sent To  
Notes
2021-03-19 15:34:58CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 PERMIT 21021166
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SCOPE OF WORK NOT CLEAR. APPLICATION MENTIONS A NEW
 ELECTRICAL SERVICE, BUT DRAWINGS SEEM TO INDICATE
 ADDITIONAL ELECTRICAL WORK BEING DONE (NEW LIGHTS,
 RECEPTACLES, EQUIPMENT, ETC)
 2) SHEET E-03 (NEW ELECTRICAL RISER DIAGRAM #3):
 GROUNDING ELECTRODE CONDUCTOR TO EXISTING WATER PIPE
 MUST BE AT LEAST #4 CU OR #2 AL. NEC 250.66
 3) PLEASE CHANGE CODE REFERENCES TO NEC 2017 AND FBC
 2020, 7TH EDITION FBC 107
 4) PLEASE SEE SIGNATURE COMMENTS.
 5) IT SEEMS THAT DUPLICATE DRAWINGS HAVE BEEN UPLOADED
 (THERE ARE THREE E-01S, TWO E-02S, AND TWO E-03S).
 PLEASE CLARIFY WHICH VERSIONS ARE THE ONES THAT NEED TO
 BE REVIEWED AND REMOVE THE ONES THAT SHOULD NOT BE
 USED. FBC
 6) SHEET E-2 MENTIONS THAT NEW ELECTRIC SERVICE IS
 UNDERGROUND BY FPL BUT SHEET E-3 (ELECTRICAL RISER
 DIAGRAM #3) SAYS THAT SERVICE IS OVERHEAD. PLEASE
 CLARIFY AND CORRECT. FBC 107
 7) SHEET E-2: THERE IS A NOTE THAT READS ?ELECTRICAL
 PANEL?. WHICH PANEL IS THIS? IS IT ELECTRICAL PANEL A?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 PHONE 561-805-6746.
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-08 Cont ID  
Sent By equinone Date 2021-06-08 Time 08:12 Rev Time 0.00
Received By equinone Date 2021-06-01 Time 08:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-06 Cont ID  
Sent By rmcdouga Date 2021-05-06 Time 09:02 Rev Time 0.00
Received By rmcdouga Date 2021-04-26 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-19 Cont ID  
Sent By equinone Date 2021-03-19 Time 15:35 Rev Time 0.00
Received By equinone Date 2021-03-08 Time 11:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-08 Cont ID  
Sent By equinone Date 2021-06-08 Time 08:12 Rev Time 0.00
Received By equinone Date 2021-06-08 Time 08:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-06 Cont ID  
Sent By rmcdouga Date 2021-05-06 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2021-05-06 Time 08:59 Sent To  
Notes
2021-05-06 09:01:57THE ARCHITECT'S DIGITAL SIGNATURE WILL NEED TO BE
 RE-EVALUATED IF NEW PLANS ARE SUBMITTED. THE DIGITAL
 SIGNATURE ON VERSION 2 OF DRAWINGS E1, E2 AND E3 ARE
 OKAY.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By equinone Date 2021-03-19 Time 11:58 Rev Time 0.00
Received By equinone Date 2021-03-19 Time 11:58 Sent To  
Notes
2021-03-19 12:01:28CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
 FS471, FS481,
  
  
 DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A DIGITALLY SIGNED PLAN IS
 NOT CONSIDERED AN ORIGINAL, PDF MUST HAVE THE
 INTEGRATED DIGITAL SIGNATURE.
  
 EITHER SUBMIT A DIGITALLY OR ELECTRONICALLY SIGNED
 PLAN, OR YOU CAN DROP OFF SIGNED AND SEALED PAPER
 ORIGINALS WITH A WET SEAL AND SIGNATURE.
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  