Plan Review Details - Permit 21021109
| Plan Review Stops For Permit 21021109 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-03-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-03-15 |
Time |
16:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-03-02 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-03-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-03-02 |
Time |
12:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-03-15 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-03-12 |
Time |
12:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-03-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-03-03 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-02-24 |
Time |
23:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-03-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-03-12 |
Time |
19:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-03-12 |
Time |
19:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-03-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-03-10 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-03-10 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2021-03-10 09:39:47 | SECOND REVIEW: | | | 1-DRAWING AND CALCULATIONS SUBMITTED STILL HAVE WHAT | | | LOOKS LIKE A RUBBER STAMP SIGNATURE OF THE ENGINEER. NO | | | WET SIGNATURE. | | | 2- ENGINEER'S CALCULATIONS ARE STILL MISSING THE | | | REQUIRED INDEX SHEET. | | | | | | ORIGINAL COMMENTS: | | | 1- DRAWING FP-1 OF 1 AND CALCULATIONS SUBMITTED HAVE A | | | PRINTED IMAGE OF THE ENGINEER'S SIGNATURE. NEED TO HAVE | | | THE ORIGINAL PHYSICALLY SIGNATURE OF THE ENGINEER AS | | | REQUIRED BY 61G15-23.003 FAC. | | | | | | 2- CALCULATIONS SUBMITTED DON'T HAVE AN INDEX SHEET AND | | | IS MISSING THE ENGINEER'S INFORMATION AS REQUIRED BY | | | 61G15-23.001 (4) FAC. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-03-04 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-03-04 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-03-04 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2021-03-04 15:52:59 | 1- DRAWING FP-1 OF 1 AND CALCULATIONS SUBMITTED HAVE A | | | PRINTED IMAGE OF THE ENGINEER'S SIGNATURE. NEED TO HAVE | | | THE ORIGINAL PHYSICALLY SIGNATURE OF THE ENGINEER AS | | | REQUIRED BY 61G15-23.003 FAC. | | | | | | 2- CALCULATIONS SUBMITTED DON'T HAVE AN INDEX SHEET AND | | | IS MISSING THE ENGINEER'S INFORMATION AS REQUIRED BY | | | 61G15-23.001 (4) FAC. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-03-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-03-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-03-03 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2021-03-03 07:05:11 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | SHEET FP1 AND HYDRAULIC CALCS PREPARED BY WAYNE MARKHAM | | | BENNETT, PE57216 ARE NOT DIGITALLY SIGNED. | | | | | | FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS. | | | | | | EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL | | | SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE | | | TO: | | | | | | | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | | 561-805-6724. | | | |
|
|
|