Plan Review Details - Permit 21021109
Plan Review Stops For Permit 21021109
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-03-15 Cont ID  
Sent By pleduc Date 2021-03-15 Time   Rev Time 0.00
Received By pleduc Date 2021-03-15 Time 16:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-02 Cont ID  
Sent By pleduc Date 2021-03-02 Time   Rev Time 0.00
Received By pleduc Date 2021-03-02 Time 12:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-15 Cont ID  
Sent By lmarchan Date 2021-03-15 Time 16:07 Rev Time 0.00
Received By lmarchan Date 2021-03-12 Time 12:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-03 Cont ID  
Sent By shill Date 2021-03-03 Time 07:06 Rev Time 0.00
Received By shill Date 2021-02-24 Time 23:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-03-12 Cont ID  
Sent By jgomez Date 2021-03-12 Time 19:39 Rev Time 0.00
Received By shill Date 2021-03-12 Time 19:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-03-10 Cont ID  
Sent By jgomez Date 2021-03-10 Time 09:34 Rev Time 0.00
Received By jgomez Date 2021-03-10 Time 09:34 Sent To  
Notes
2021-03-10 09:39:47SECOND REVIEW:
 1-DRAWING AND CALCULATIONS SUBMITTED STILL HAVE WHAT
 LOOKS LIKE A RUBBER STAMP SIGNATURE OF THE ENGINEER. NO
 WET SIGNATURE.
 2- ENGINEER'S CALCULATIONS ARE STILL MISSING THE
 REQUIRED INDEX SHEET.
  
 ORIGINAL COMMENTS:
 1- DRAWING FP-1 OF 1 AND CALCULATIONS SUBMITTED HAVE A
 PRINTED IMAGE OF THE ENGINEER'S SIGNATURE. NEED TO HAVE
 THE ORIGINAL PHYSICALLY SIGNATURE OF THE ENGINEER AS
 REQUIRED BY 61G15-23.003 FAC.
  
 2- CALCULATIONS SUBMITTED DON'T HAVE AN INDEX SHEET AND
 IS MISSING THE ENGINEER'S INFORMATION AS REQUIRED BY
 61G15-23.001 (4) FAC.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-04 Cont ID  
Sent By jgomez Date 2021-03-04 Time 15:44 Rev Time 0.00
Received By jgomez Date 2021-03-04 Time 15:14 Sent To  
Notes
2021-03-04 15:52:591- DRAWING FP-1 OF 1 AND CALCULATIONS SUBMITTED HAVE A
 PRINTED IMAGE OF THE ENGINEER'S SIGNATURE. NEED TO HAVE
 THE ORIGINAL PHYSICALLY SIGNATURE OF THE ENGINEER AS
 REQUIRED BY 61G15-23.003 FAC.
  
 2- CALCULATIONS SUBMITTED DON'T HAVE AN INDEX SHEET AND
 IS MISSING THE ENGINEER'S INFORMATION AS REQUIRED BY
 61G15-23.001 (4) FAC.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-03 Cont ID  
Sent By pleduc Date 2021-03-02 Time   Rev Time 0.00
Received By shill Date 2021-03-03 Time 07:03 Sent To  
Notes
2021-03-03 07:05:11SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SHEET FP1 AND HYDRAULIC CALCS PREPARED BY WAYNE MARKHAM
 BENNETT, PE57216 ARE NOT DIGITALLY SIGNED.
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
  
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.
  