Plan Review Details - Permit 21021094
Plan Review Stops For Permit 21021094
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By rmcdouga Date 2021-03-09 Time 08:17 Rev Time 0.00
Received By rmcdouga Date 2021-03-09 Time 08:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-01 Cont ID  
Sent By rmcdouga Date 2021-03-01 Time 08:04 Rev Time 0.00
Received By rmcdouga Date 2021-03-01 Time 08:04 Sent To  
Notes
2021-03-01 08:26:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY ON THE GENERATOR LOCATION THAT THE GENERATOR
 EXHAUST IS REQUIRED TO BE 10 FEET FROM ANY OPENINGS TO
 A STRUCTURE. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL
 AND GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE
 LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2) THE ELEVATED GENERATOR SLAB, FOUNDATION AND WALLS
 REQUIRE STEEL REINFORCEMENT. SPECIFY THE REBAR SIZE AND
 SPACING ON THE DRAWINGS. FBC 107.2.1
 I AM NOT SURE WHY THE GENERATOR IS BEING ELEVATED. THE
 PROPERTY IS NOT LOCATED IN A SPECIAL FLOOD HAZARD AREA
 AND IS NOT REQUIRED TO BE ELEVATED BY THE BUILDING CODE
 OR CITY'S FLOOD ORDINANCE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By jleahy Date 2021-03-09 Time 15:02 Rev Time 0.00
Received By jleahy Date 2021-03-09 Time 14:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-02 Cont ID  
Sent By jleahy Date 2021-03-02 Time 09:19 Rev Time 0.00
Received By jleahy Date 2021-02-26 Time 13:15 Sent To  
Notes
2021-03-02 09:21:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE HAS TO INCLUDE ALL MATERIALS AND
 EQUIPMENT.(1500)
  
 2) ATS CAN NOT BE PROTECTED BY A 200A BREAKER.
  
 3) ATS DOES NOT HAVE TO BE SERVICE ENTRANCE RATED, IT
 IS AFTER THE FIRST MEANS OF DISCONNECT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-09 Cont ID  
Sent By jleahy Date 2021-03-09 Time 15:02 Rev Time 0.00
Received By jleahy Date 2021-03-08 Time 16:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-05 Cont ID  
Sent By lmarchan Date 2021-03-05 Time 14:25 Rev Time 0.00
Received By lmarchan Date 2021-02-22 Time 15:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-02-22 Cont ID  
Sent By medwards Date 2021-02-22 Time 17:17 Rev Time 0.00
Received By medwards Date 2021-02-22 Time 17:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-03-05 Cont ID  
Sent By kalexand Date 2021-03-05 Time 14:20 Rev Time 0.00
Received By kalexand Date 2021-03-05 Time 14:20 Sent To I
Notes
***NONE***