Plan Review Details - Permit 21020875
Plan Review Stops For Permit 21020875
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-11-23 Cont ID  
Sent By cpuell Date 2021-11-23 Time 16:44 Rev Time 0.00
Received By cpuell Date 2021-11-23 Time 16:44 Sent To  
Notes
2021-11-23 16:45:10ADDED ADDRESS ON APPLICATION FORM THAT WAS LEFT OFF BY
 CONTRACTOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2021-06-17 Cont ID  
Sent By rmcdouga Date 2021-06-17 Time 12:47 Rev Time 0.00
Received By rmcdouga Date 2021-06-17 Time 12:47 Sent To  
Notes
2021-06-17 12:49:30THE POLE IS LOCATED IN A RIGHT OF WAY. A BUILDING
 REVIEW IS NOT REQUIRED PER SAMANTHA HILL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-29 Cont ID  
Sent By rmcdouga Date 2021-04-29 Time 15:11 Rev Time 0.00
Received By rmcdouga Date 2021-04-29 Time 15:11 Sent To  
Notes
2021-04-29 15:22:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) UPDATE THE CODE REFERENCES ON SHEET T-1 TO THE 2020
 FBC SEVENTH EDITION. THE PLANS HAVE SEVERAL REFERENCES
 TO THE FBC SIXTH EDITION (2017). THE FBC SEVENTH
 EDITION (2020) WENT INTO EFFECT ON DECEMBER 31, 2020.
 ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE
 REQUIRED TO COMPLY WITH AND REFERENCE THE 2020 FBC
 SEVENTH EDITION. FS CHAPTER 553
  
 2) SUBMIT SIGNED AND SEALED STRUCTURAL DRAWINGS AND
 CALCULATIONS THAT ADDRESS THE WIND LOADS ON THE METAL
 POLE AND THE EQUIPMENT THAT WILL BE MOUNTED ON IT. FBC
 1609

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 15:07 Rev Time 0.00
Received By jleahy Date 2022-09-29 Time 15:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-02-16 Cont ID  
Sent By mpeterso Date 2022-02-16 Time 09:21 Rev Time 0.00
Received By mpeterso Date 2022-02-16 Time 09:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-11-23 Cont ID  
Sent By jleahy Date 2021-11-23 Time 15:35 Rev Time 0.00
Received By jleahy Date 2021-11-23 Time 15:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-05-10 Cont ID  
Sent By jleahy Date 2021-05-10 Time 10:40 Rev Time 0.00
Received By jleahy Date 2021-04-19 Time 15:41 Sent To  
Notes
2021-05-10 10:42:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 HOW IS THIS 105 DAURA, INSPECTORS WILLNEVER FIND JOB.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-05 Cont ID  
Sent By jleahy Date 2021-03-05 Time 12:04 Rev Time 0.00
Received By jleahy Date 2021-03-05 Time 07:41 Sent To  
Notes
2021-03-05 12:07:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLEASE CHANGE EDITIONS OF CODES USED ON COVER SHEET
 2020 7TH ED.
  
 2) VALUE OF WORK IS LOW. (1800)
  
 3) SHOW LOCATION OF METER AND DISCONNECT AT POLE. 215.5

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2021-12-06 Cont ID  
Sent By eschneid Date 2021-12-06 Time 14:57 Rev Time 0.00
Received By eschneid Date 2021-12-06 Time 14:57 Sent To  
Notes
2021-12-06 14:58:45NO ENGINEERING STOP ON THIS ELECTRICAL PERMIT - SEE
 19020390 FOR ENGINEERING COMMENTS FOR THE WCF ROW
 PERMIT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-06-11 Cont ID  
Sent By gpatrie Date 2021-06-11 Time 08:04 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2021-06-11 08:04:371. THERE IS ANOTHER VRISON PERMIT #21041701 WHICH MOVES
 THE POLE TO THE SOUTH SIDE OF 3RD ST.
 2. LAT - LONG LOCATION REQUIRED FOR HAND HOLD.
  
 CONTACT: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aoliver Date 2022-10-25 Time 06:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 15:07 Rev Time 0.00
Received By jleahy Date 2022-09-06 Time 07:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-22 Cont ID  
Sent By jgomez Date 2022-02-22 Time 14:05 Rev Time 0.00
Received By jgomez Date 2022-01-31 Time 16:37 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-07 Cont ID  
Sent By rmcphers Date 2021-12-07 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2021-10-29 Time 12:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-14 Cont ID  
Sent By rmcdouga Date 2021-06-14 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2021-04-08 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-24 Cont ID  
Sent By lmarchan Date 2021-03-24 Time 13:34 Rev Time 0.00
Received By lmarchan Date 2021-02-25 Time 08:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status N Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 15:11 Rev Time 0.00
Received By jleahy Date 2022-09-29 Time 15:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2022-02-22 Cont ID  
Sent By jgomez Date 2022-02-22 Time 14:02 Rev Time 0.00
Received By jgomez Date 2022-02-22 Time 13:58 Sent To  
Notes
2022-02-22 14:05:01SIGNATURE REVIEW.
  
 1- S1 SURVEY AND S2 SURVEY UPLOADED TO PROJECTDOX ON
 01/31/22 :
 SURVEYS SUBMITTED NEED SURVEYOR'S ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. WHEN
 SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: SUBMIT SURVEY ELECTRONICALLY WITH SURVEYOR'S
 DIGITAL SIGNATURE OR PROVIDE HARD COPY WITH SURVEYOR'S'
 ORIGINAL SEAL AND SIGNATURE.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-12-07 Cont ID  
Sent By rmcphers Date 2021-12-07 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2021-12-07 Time 08:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-10 Cont ID  
Sent By jleahy Date 2021-05-10 Time 10:42 Rev Time 0.00
Received By jleahy Date 2021-05-10 Time 10:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-05 Cont ID  
Sent By jleahy Date 2021-03-05 Time 12:05 Rev Time 0.00
Received By jleahy Date 2021-03-05 Time 12:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2022-09-29 Cont ID  
Sent By ckimmerl Date 2022-09-29 Time 13:32 Rev Time 0.00
Received By ckimmerl Date 2022-09-29 Time 13:32 Sent To  
Notes
2022-09-29 13:32:56THE SUBMITTED COMMUNICATION FACILITY PLACEMENT PERMIT -
 CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO THIS
 PERMIT BEING APPROVED. THE PLANS INCLUDED WITH THIS
 ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED WITH
 THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS BELOW
 ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS WELL AS
 WITH THIS PERMIT.
  
  
 9.29.22 ZONING REVIEW - 19020390 105 @ DATURA WPB NODE
 2
  
 1. PLEASE PROVIDE SURVEY FOR ENTIRE SCOPE OF PROJECT,
 INCLUDING THE POWER ROUTE. APPEARS POWER IS BEING
 PULLED FROM A TRANSFORMER WITHIN PRIVATE/CITY PROPERTY,
 PLEASE PROVIDE PROOF OF UTILITY/ACCESS EASEMENT ON THE
 SURVEY OR PROVIDE OWNER???S CONSENT. OTHERWISE POLE
 WILL HAVE TO DRAW POWER FROM AN ALTERNATIVE LOCATION.
  
 2. THE POLE STEALTH DESIGN AND COLOR MEETS CITY
 STANDARDS.
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 (561)822-1426 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status F Date 2022-02-17 Cont ID  
Sent By ckimmerl Date 2022-02-17 Time 16:06 Rev Time 0.00
Received By ckimmerl Date 2022-02-17 Time 16:04 Sent To  
Notes
2022-02-17 16:05:221. PRIOR TO ZONING APPROVAL OF THIS PERMIT, A
 COMMUNICATIONS FACILITIES PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY MUST BE SECURED/APPROVED FROM THE CITY'S
 PLANNING DIVISION. (PERMIT 19020390)
  
 2. PLEASE PROVIDE ADDITIONAL DETAIL TO THE FINAL
 UNDERGROUND ELECTRIC CONNECTION. THE PROPOSED POLE AS
 PART OF THIS PERMIT IS TAKING POWER FROM A SEPARATE
 POLE (WPB NODE 11)? PLEASE SPECIFY WHERE THE FINAL
 POWER DRAW IS COMING FROM.
  
 3. THE POLE DESIGN AND THE UNDERGROUND PATH/DEPTH
 COMPLY WITH CITY REQUIREMENTS.
  
 4. THE POLE COLOR SHALL BE ADJUSTED TO THE RAYCON (RAL#
 7022 RNS3-20001 UMBRA GREY) ALONG DATURA STREET, PER
 OUR ADJUSTMENTS FROM OUR RECENT EMAIL CORRESPONDENCES.
  
 CHRIS KIMMERLY @ 822-1426
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2021-12-06 Cont ID  
Sent By   Date 2021-12-06 Time 14:43 Rev Time 0.50
Received By eschneid Date   Time   Sent To  
Notes
2021-12-06 14:56:34FAILED
  
 PRIOR TO ZONING APPROVAL OF THIS PERMIT, A
 COMMUNICATIONS FACILITIES PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY MUST BE SECURED FROM THE CITY'S PLANNING
 DIVISION. THE COMMENTS BELOW ARE THE ZONING COMMENTS
 FROM THE WCF ROW APPLICATION 19020390 FOR WPB NODE 2:
  
 1) THE SURVEY PROVIDED WITH THE APPLICATION DOES NOT
 COVER THE ENTIRE SCOPE OF WORK, SPECIFICALLY THE SOUTH
 WEST CORNER OF THE INTERSECTION OF EVERNIA STREET AND
 FLAGLER DRIVE. THIS SECTION OF THE INTERSECTION CALLS
 OUT A PROPOSED BORE PIT AND HANDHOLE FOR THE
 UNDERGROUND POWER. THE SURVEY NEEDS TO BE PROVIDED SO
 THAT STAFF CAN VERIFY THAT THE INSTALLATIONS ARE FULLY
 WITHIN THE RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) THE POLE NEEDS TO BE IN LINE WITH PALM TREES ALONG
 DATURA STREET. PLEASE NOTE THE OUTSIDE EDGE OF THE POLE
 MUST BE SETBACK A MINIMUM OF 18 INCHES FROM THE CURB.
  
 3) PROVIDE THE DIMENSIONS FROM THE EDGE OF THE
 EXCAVATION PIT FOR THE PROPOSED HANDHOLE WITHIN THE
 FLAGLER DRIVE RIGHT-OF-WAY, GENERALLY MIDWAY BETWEEN
 DATURA AND EVERNIA STREETS, TO THE TRUNK OF THE
 ADJACENT PALM TREES. THIS DIMENSION SHALL BE NO LESS
 THAN 5 FEET.
  
 4) THE PLANS MUST CLEARLY CALL OUT THAT THE BORE, AND
 THUS THE BORE EQUIPMENT STAGING, IS DONE FROM THE BORE
 PITS ALONG FLAGLER DRIVE. THE BORE EQUIPMENT MAY NOT BE
 STAGED ADJACENT TO A PALM TREE (AT THE POLE OR AT THE
 HANDHOLE) SO AS NOT TO DAMAGE THE TREES.
  
 5) THE POLE DESIGN AND THE UNDERGROUND FIBER PATH/DEPTH
 COMPLY WITH CITY REQUIREMENTS.
  
 6) THE POLE COLOR SHALL BE GREY TO MATCH THE DECORATIVE
 LIGHT POLES ALONG DATURA STREET.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-05-11 Cont ID  
Sent By   Date 2021-05-11 Time 16:30 Rev Time 0.25
Received By eschneid Date 2021-05-11 Time 16:30 Sent To  
Notes
2021-05-11 16:33:55FAILED
  
 1) PROVIDE VERIFICATION THAT THE SITE HAS BEEN ISSUED A
 COMMUNICATION FACILITY PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY AND A RIGHT-OF-WAY USE PERMIT FOR THE
 PLACEMENT OF THE POLE, THE UNDERGROUND FIBER/POWER, THE
 HANDHOLES, ETC. WITHIN THE DATURA STREET AND FLAGLER
 DRIVE RIGHTS-OF-WAY. THE PLANS INCLUDED WITH THIS
 ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED WITH
 THE AFOREMENTIONED PERMITS.
  
 2) THE RESUBMITTED PLANS ARE NOT THE PLANS FOR WEST
 PALM BEACH 02. THE PLANS THAT WERE UPLOADED ARE FOR
 DOWNTOWN WPB 2, WHICH IS ACTUALLY PERMIT 20101235.
 PLEASE UPLOAD THE CORRECT PLANS ONCE YOU HAVE ADDRESSED
 COMMENT NUMBER 1.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By ckimmerl Date 2021-03-24 Time 11:06 Rev Time 0.25
Received By eschneid Date 2021-03-24 Time 11:06 Sent To  
Notes
2021-03-24 11:36:17FAILED
  
 PROVIDE VERIFICATION THAT THE SITE HAS BEEN ISSUED A
 COMMUNICATION FACILITY PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY AND A RIGHT-OF-WAY USE PERMIT FOR THE
 PLACEMENT OF THE POLE, THE UNDERGROUND FIBER/POWER, THE
 HANDHOLES, ETC. WITHIN THE DATURA STREET AND FLAGLER
 DRIVE RIGHTS-OF-WAY. THE PLANS INCLUDED WITH THIS
 ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED WITH
 THE AFOREMENTIONED PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  