| 2021-09-23 17:07:45 | 4TH ELECTRONIC SIGNATURE REVIEW |
| | PERMIT- 21020874 |
| | 9/23/21 |
| | |
| | FAILED- COMMENT # 1 FROM THE 3RD REVIEW LISTED BELOW |
| | STILL EXISTS- PLEASE COMPLY. |
| | |
| | 1) DRAWINGS LABELED "COMMENT 4 _ ENGINEERING - INTERIOR |
| | STAIRCASE.PDF" DOES NOT SHOW AS ELECTRONICALLY SIGNED |
| | IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN |
| | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED |
| | BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC |
| | PLAN REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES |
| | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN |
| | DROP OFF THE ORIGINAL SIGNED AND SEALED |
| | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING |
| | DIVISION AT THE CITY HALL. |
| | |
| | 2) NEW COMMENT: CALCULATIONS TITLED STAIR #7, THE |
| | CRYSTAL CONDO ARE NOT DIGITALLY SIGNED AND SEALED BY |
| | THE T ENGINEER OF RECORD XUAN CHEN. CALCULATIONS |
| | PREPARED BY A FL. LICENSED ENGINEER THAT ARE |
| | TRANSMITTED ELECTRONICALLY SHALL BEAR THE DIGITAL SEAL |
| | SIGNATURE OF THE ENGINEER- FL. STATUTE 471.025, AND |
| | SECTION 61G15-23.005 FAC. |
| | |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR |
| | ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND |
| | DOCUMENTS. |
| | A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL |
| | ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY |
| | CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION. |
| | THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE |
| | A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES |
| | NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.) |
| | YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE |
| | ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT |
| | USE A THIRD PARTY. |
| | YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT |
| | IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE |
| | AND DOCUMENT. |
| | |
| | AS AN ALTERNATIVE TO PROVIDING DIGITALLY SIGNED AND |
| | SEALED CALCULATIONS, SIGNED AND SEALED ENGINEERING IN |
| | PAPER FORM CAN BE BROUGHT INTO THE WPB BUILDING |
| | DEPARTMENT WITH A COMPLETED PLAN REVIEW REQUEST FORM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |