| 2021-03-16 07:52:16 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21020873 |
| | 3/16/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE INCREASE IN VALUE TO INSTALL THE |
| | FILE ROOM SINK, WATER HEATER, PLUMBING PIPING, AND |
| | CABINETRY- SECTION 109.3 WPB. PLEASE NOTE THAT PERMIT |
| | VALUE IS BASED ON THE COSTS OF LABOR, MATERIALS, |
| | FIXTURES, APPLIANCES, EQUIPMENT, DESIGN FEES AND |
| | OVERHEAD AND PROFIT. |
| | |
| | 2) SHEET A1.11: PROVIDE THE CLEAR FLOOR SPACE DIAGRAM |
| | AND DIMENSION SHOWING EITHER A FORWARD OR PARALLEL |
| | APPROACH TO THE SINK- SECTIONS 606.2 & 305 FBC ACC. |
| | |
| | 3) A1.11: PROVIDE AN ELEVATION VIEW OF THE SINK SHOWING |
| | THE SINK HEIGHT, AND KNEE AND TOE CLEARANCES- SECTIONS |
| | 606.2, 606.3 & 306 FBC ACC. |
| | |
| | 4) P0.1: A DEDICATED FULL-OPEN TYPE SHUT OFF VALVE IS |
| | REQUIRED FOR THE NEW WATER HEATER- SECTIONS 503.1 & |
| | 606.1 FBC P. |
| | |
| | 5) A1.11 & P0.1: INSTALLATION OF THE NEW SINK DRAIN MAY |
| | REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 6) A1.11 & P0.1: THE NEW DRAIN PENETRATION OF THE |
| | EXISTING SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE |
| | ANNULAR SPACE AROUND THE PIPING. PROVIDE A UL TESTED |
| | AND APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| | SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |