Plan Review Details - Permit 21020873
Plan Review Stops For Permit 21020873
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-12 Cont ID  
Sent By rmcphers Date 2021-04-12 Time 13:03 Rev Time 0.00
Received By rmcphers Date 2021-04-12 Time 12:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-17 Cont ID  
Sent By rmcphers Date 2021-03-17 Time 09:34 Rev Time 0.00
Received By rmcphers Date 2021-03-17 Time 09:26 Sent To  
Notes
2021-03-17 09:34:51REVISION TO ADD SINK
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE DRAWING A4.21
 2) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT - FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT, INTERIOR DESIGNER, LANDSCAPE ARCHITECT , OR
 ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THIS STATE REGULATING THE
 PRACTICE OF ARCHITECTURE OR INTERIOR DESIGN AS
 PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART I,
 OR LANDSCAPE ARCHITECTURE AS PROVIDED FOR
 IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471,
 FLORIDA STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA, AS REQUIRED BY
 FLORIDA STATUTE.
 3) PLEASE SHOW THE ADDITIONAL JOB VALUE ON THE PLAN
 REVIEW REQUEST FORM IN THE SPACE PROVIDED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-04-20 Time   Rev Time 0.00
Received By aoliver Date 2021-04-19 Time 13:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-04-15 Time   Rev Time 0.00
Received By aoliver Date 2021-03-31 Time 13:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-17 Cont ID  
Sent By rmcphers Date 2021-03-17 Time 09:35 Rev Time 0.00
Received By rmcphers Date 2021-02-24 Time 13:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-04-20 Cont ID  
Sent By ccole Date 2021-04-20 Time 12:18 Rev Time 0.00
Received By ccole Date 2021-04-20 Time 12:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-04-15 Cont ID  
Sent By ccole Date 2021-04-15 Time 13:08 Rev Time 0.00
Received By ccole Date 2021-04-15 Time 12:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-16 Cont ID  
Sent By ccole Date 2021-03-16 Time 07:52 Rev Time 0.00
Received By ccole Date 2021-03-15 Time 15:56 Sent To  
Notes
2021-03-16 07:52:161ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21020873
 3/16/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE INCREASE IN VALUE TO INSTALL THE
 FILE ROOM SINK, WATER HEATER, PLUMBING PIPING, AND
 CABINETRY- SECTION 109.3 WPB. PLEASE NOTE THAT PERMIT
 VALUE IS BASED ON THE COSTS OF LABOR, MATERIALS,
 FIXTURES, APPLIANCES, EQUIPMENT, DESIGN FEES AND
 OVERHEAD AND PROFIT.
  
 2) SHEET A1.11: PROVIDE THE CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSION SHOWING EITHER A FORWARD OR PARALLEL
 APPROACH TO THE SINK- SECTIONS 606.2 & 305 FBC ACC.
  
 3) A1.11: PROVIDE AN ELEVATION VIEW OF THE SINK SHOWING
 THE SINK HEIGHT, AND KNEE AND TOE CLEARANCES- SECTIONS
 606.2, 606.3 & 306 FBC ACC.
  
 4) P0.1: A DEDICATED FULL-OPEN TYPE SHUT OFF VALVE IS
 REQUIRED FOR THE NEW WATER HEATER- SECTIONS 503.1 &
 606.1 FBC P.
  
 5) A1.11 & P0.1: INSTALLATION OF THE NEW SINK DRAIN MAY
 REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
  
 6) A1.11 & P0.1: THE NEW DRAIN PENETRATION OF THE
 EXISTING SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE
 ANNULAR SPACE AROUND THE PIPING. PROVIDE A UL TESTED
 AND APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN-
 SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-20 Cont ID  
Sent By ccole Date 2021-04-20 Time 12:18 Rev Time 0.00
Received By ccole Date 2021-04-20 Time 12:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-04-12 Cont ID  
Sent By rmcphers Date 2021-04-12 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2021-04-12 Time 13:01 Sent To  
Notes
2021-04-12 13:02:54DRAWING LABELED ( SHEET_P-2.1_PLUMBING PLAN_REV
 1_2-12-21.PDF ) IN PROJECTDOX = SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-16 Cont ID  
Sent By ccole Date 2021-03-16 Time 08:01 Rev Time 0.00
Received By ccole Date 2021-03-16 Time 07:54 Sent To  
Notes
2021-03-16 08:07:59DIGITAL SIGNATURE REVIEW
 3/16/2021
  
 1) THE PLANS SHALL BEAR THE DIGITAL SIGNATURES AND
 SEALS OF THE ARCHITECT AND ENGINEER OF RECORD- FL.
 STATUTES 481.221 & 471.025 AND SECTIONS 61G1-16.005 &
 61G15-23.005 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  