Plan Review Details - Permit 21020848
Plan Review Stops For Permit 21020848
Review Stop E ELECTRICAL
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-03 Cont ID  
Sent By fgiaquin Date 2021-04-03 Time 21:12 Rev Time 0.00
Received By gpatrie Date 2021-04-03 Time 20:07 Sent To  
Notes
2021-07-02 08:17:29NOT IN CITY RIGHT-OF-WAY. FDOT ROADWAY.
2021-06-15 14:08:431512 S DIXIE HWY IS FDOT RIGHT-OF-WAY NOT IN CITY
 RIGHT-OF-WAY. FDOT PERMIT REQUIRED.
  
 CONTACT: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By fgiaquin Date 2021-02-25 Time 22:17 Rev Time 0.00
Received By fgiaquin Date 2021-02-25 Time 21:18 Sent To  
Notes
2021-02-25 22:17:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO MAIN SHOWN IN PANEL, AND PANEL IS A 10 CIRCUIT
 PANEL. EITHER CHANGE TO A 6 CIRCUIT PANEL OR PROVIDE A
 MAIN BREAKER SO IS NO CAPABILITY OF HAVING MORE THAN
 SIX THROWS OF THE HAND. NEC 230.71A
  
 2. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE ACCURATE
 VALUE FOR ALL MATERIALS AND LABOR, FAILURE TO PROVIDE
 AN ACCURATE VALUE MAY RESULT IN VALUE BEING SET BY
 BUILDING OFFICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2021-07-05 Cont ID  
Sent By shill Date 2021-07-05 Time 16:28 Rev Time 0.00
Received By shill Date 2021-07-05 Time 16:28 Sent To  
Notes
2021-07-05 16:28:52G PATRIE REVIEWED UNDER ELECTRICAL REVIEW #2
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-03 Cont ID  
Sent By ccarvaja Date 2021-05-03 Time 15:33 Rev Time 0.00
Received By ccarvaja Date 2021-03-31 Time 13:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-05 Cont ID  
Sent By shill Date 2021-03-05 Time 14:57 Rev Time 0.00
Received By shill Date 2021-02-17 Time 04:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-04-03 Cont ID  
Sent By fgiaquin Date 2021-04-03 Time 21:14 Rev Time 0.00
Received By fgiaquin Date 2021-04-03 Time 21:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-05 Cont ID  
Sent By shill Date 2021-03-05 Time 14:57 Rev Time 0.00
Received By shill Date 2021-03-05 Time 14:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-05-03 Cont ID  
Sent By eschneid Date 2021-05-03 Time 11:29 Rev Time 0.25
Received By eschneid Date 2021-05-03 Time 11:28 Sent To  
Notes
2021-05-03 11:29:36FULLY IN ROW
  
 STEALTH POLE

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-04 Cont ID  
Sent By eschneid Date 2021-03-04 Time 11:22 Rev Time 0.25
Received By eschneid Date 2021-03-04 Time 11:01 Sent To  
Notes
2021-03-04 11:20:14FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION, THE
 HANDHOLES, THE UNDERGROUND LINES AND THE RIGHT-OF-WAY
 LINE SO THAT STAFF CAN VERIFY THAT THE WIRELESS
 COMMUNICATION FACILITIES ARE WITHIN THE RIGHT-OF-WAY
 AND NOT ON PRIVATE PROPERTY.
  
 2) PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITIES IN
 THE RIGHT-OF-WAY.
  
 3) THE PLANS SUBMITTED WITH THE PERMIT SHOW THAT THE
 PROPOSED WIRELESS FACILITY POLE DOES NOT MEET THE CITY
 OF WEST PALM BEACH CONCEALMENT (STEALTH) OR STYLE AND
 POSSIBLY HEIGHT REQUIREMENTS LISTED IN SECTIONS
 78-411(E), 78-411(F) AND 78-411(G) OF THE CITY CODE.
 PROVIDE A POLE THAT MEETS THE CITY CODE REQUIREMENTS.
 NOTE: VERIZON HAS SHOWN POLES ON OTHER APPLICATIONS FOR
 OTHER LOCATIONS WITHIN THE CITY THAT MEET THE CITY CODE
 REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved