| 2021-03-02 17:35:13 | RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | |
| | PERMIT #21020831 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | |
| | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL4930-R14 |
| | SUBMITTED IS FOR THE 2017 CODE VERSION. AS OF DECEMBER |
| | 31, 2020, THE CURRENT CODE IS THE 2020 VERSION (SEC. |
| | 553 F.S.). PROVIDE PRODUCT APPROVAL FOR THE CURRENT |
| | CODE VERSION AND CLEARLY MARK WHICH APPROVED ASSEMBLY |
| | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. 1609.1 FBC-BUILDING. |
| | |
| | 2- NOTE: SEPARATE PERMIT FOR MECHANICAL ROOFING |
| | EQUIPMENT MAY BE REQUIRED. |
| | SEC. 102.8 CITY AMENDMENTS: EXISTING MECHANICAL |
| | EQUIPMENT. AN AGENCY OR LOCAL GOVERNMENT MAY NOT |
| | REQUIRE THAT EXISTING MECHANICAL EQUIPMENT LOCATED ON |
| | OR ABOVE THE SURFACE OF A ROOF BE INSTALLED IN |
| | COMPLIANCE WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE EXCEPT DURING REROOFING WHEN THE |
| | EQUIPMENT IS BEING REPLACED OR MOVED AND IS NOT IN |
| | COMPLIANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE RELATING TO ROOF-MOUNTED MECHANICAL UNITS. |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |