| 2021-03-02 13:06:19 | 03/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR |
| | THE MAXIMUM SYSTEM FLOW. THE 2013 EDITION ADDRESSES THE |
| | FLOW RATE IN GALLONS PER MINUTE (GPM). IT REQUIRES THAT |
| | THE MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED |
| | MAXIMUM FLOW RATE OF THE SUCTION OUTLET FITTING |
| | ASSEMBLY (DRAIN COVER). THE TDH CALCULATIONS MUST |
| | INCLUDE ALL THE SYSTEM COMPONENTS, INCLUDING SUCTION |
| | AND RETURN PIPING, FITTINGS, VALVES, HEATER, FILTER, |
| | AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT THE PUMP. |
| | |
| | 2. PLEASE SUBMIT A COPY OF THE POOL PUMP CURVE. |
| | IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC |
| | TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS |
| | NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH |
| | CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS. |
| | 4.4.9, 4.4.9.1. |
| | |
| | 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN |
| | DRAIN, CARTRIDGE FILTER, AND THE PUMP PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 4. DIGITAL SIGNATURE COULD NOT BE VERIFIRED; PLEASE |
| | CORRECT OR DROP OFF (CITY HALL DROPBOX) THE ORIGINAL |
| | SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN REVIEW |
| | REQUEST FORM" EXPLAINING THE REASON FOR SUBMITTING THE |
| | DOCUMENT OR DRAWINGS. THE PLAN REVIEW REQUEST FORM CAN |
| | BE OBTAINED BY EMAILING [email protected] AND ASKING FOR THE |
| | FORM. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |