Plan Review Details - Permit 21020790
Plan Review Stops For Permit 21020790
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-03-29 Cont ID  
Sent By jwitmer Date 2021-03-29 Time 10:03 Rev Time 0.00
Received By jwitmer Date 2021-03-29 Time 09:16 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-02-24 Cont ID  
Sent By jwitmer Date 2021-02-24 Time 11:27 Rev Time 0.00
Received By jwitmer Date 2021-02-24 Time 09:32 Sent To  
Notes
2021-02-24 11:27:06TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-05 Cont ID  
Sent By jwitmer Date 2021-04-05 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2021-04-05 Time 12:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-29 Cont ID  
Sent By jwitmer Date 2021-03-29 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2021-03-29 Time 09:16 Sent To  
Notes
2021-03-29 10:22:05WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020790
 ADD: 400 N. FLAGLER DR.# 1503
 CONT: RICHARD MCDONALD CONSTRUCTION INC. / CBC043529
 TEL: 561-795-4055
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2NDT REVIEW
 DATE: MON. MARCH 29TH/ 2021
 ACTION: DENIED
  
 1-3) COMPLIED.
  
  
 4) 2ND REQUEST. THE PRODUCT APPROVALS SUBMITTED ON
 3/19ONLY THE TOP SHEET OF EACH PRODUCT APPROVAL WAS
 SUBMITTED. THE COMMENT STILL STANDS, WITHOUT
 IDENTIFYING IF THE SLIDING GLASS DOORS ARE RE-ENFORCED
 STEEL AND WHAT HEIGHT THE SILLS ARE A REVIEW OF THE
 PRODUCT APPROVALS CAN NOT BE ACCOMPLISHED.
 IT IS VERY COSTLY TIME WISE AND MONEY TO HAVE ORDERED
 THE WRONG WINDOWS AND SLIDING GLASS DOORS AND FINDING
 THIS OUT AT TIME OF INSPECTION.
  
 1ST ROUND OF COMMENTS. THE SUBMITTED PRODUCT APPROVALS
 DO HAVE THE SHOP DRAWING STAMP OF THE DESIGN
 PROFESSIONAL BUT NONE OF THE SUBMITTED PRODUCT APPROVAL
 HAVE IDENTIFIED THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 5-6) COMPLIED.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-02-24 Time 11:30 Rev Time 0.00
Received By jwitmer Date 2021-02-24 Time 09:32 Sent To  
Notes
2021-02-24 11:05:30WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020790
 ADD: 400 N. FLAGLER DR.# 1503
 CONT: RICHARD MCDONALD CONSTRUCTION INC. / CBC043529
 TEL: 561-795-4055
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 24TH/ 2021
 ACTION: DENIED
  
 1)SHEET A-1. FLOORING REPORTS FOR PROFLEX RCU-500 FOR
 QUARRY TILE THE REPORTS ARE ALL CODE COMPLIANT BUT THE
 FLOOR FINISH SCHEDULE STATES THE FLOORING MATERIAL IS
 TBD/ TO BE DETERMINED. PLEASE PROVIDE THE TYPE OF FLOOR
 FINISH AND REPORTS THAT MATCH.
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2) SHEET A-1. THE WIND DESIGN PROVIDED IS ASCE 7-16,
 170 VULT/ 132 VASD, EXPOSURE D, 22 STORY BUILDING
 ROUGHLY 200 FT. TALL. THERE IS A NOTE STATING THE
 DESIGN WIND PRESSURES (ASSUMED IN VASD) WINDOWS AND
 SLIDING GLASS DOORS WORST CASE WITH PRESSURES OF
 POSITIVE + 63.3 PSF AND NEGATIVE -84.7 PSF. WORST CASE
 SCENARIO IS ZONE 5 @ 10 SQUARE FEET, THE PRESSURES ARE
 -120.8 PSF AND +65.9 PSF / VASD. ASCE 7-16, COMPONENTS
 AND CLADDING.
  
 3) SHEET A-1. THE PLANS SHOW IN THE NEW DINING ROOM
 AREA A REDUCED BALCONY WITH A INSIDE CORNER WITH
 SLIDING GLASS DOORS ANCHORING TO THIS FRAMING MEMBER.
 THIS FRAMING MEMBER DOES NOT CALL OUT WHAT TYPE OF
 MATERIAL, GAUGE OF THE MATERIAL, ANCHORING OF THE
 MATERIAL TO THE CONCRETE FLOOR SLAB OR THE FLOOR/
 CEILING ASSEMBLY ABOVE. THERE WAS NO ENGINEERING FOR
 ANCHORING TO HORIZONTAL FLOOR/ CEILING ,NOR OF SLIDING
 GLASS TRACK FRAME TO THE WIND DESIGN LISTED ABOVE.
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 4) THE SUBMITTED PRODUCT APPROVALS DO HAVE THE SHOP
 DRAWING STAMP OF THE DESIGN PROFESSIONAL BUT NONE OF
 THE SUBMITTED PRODUCT APPROVAL HAVE IDENTIFIED THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE,
 LENGTH IF UNREINFORCED OR REINFORCED INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 5A) SHEET A-1. WITHOUT THE DEMOLITION PLANS LOCATIONS
 FOR SHOWERS AND TUB CAN NOT BE VERIFIED IF EXISTING
 LOCATION OR A NEW LOCATION SINCE THE PLANS SHOW A TUB
 INFILL DETAIL. THIS MEANS IF THERE ARE NEW FLOOR
 PENETRATIONS THE SLAB WILL NEED TO BE X-RAYED TO LOCATE
 THE POST TENSION CHORDS, AS TO NOT CAUSE DAMAGE TO THE
 POST TENSION CHORDS. 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 5B) SHEET A-1 INDICATES THE USE OF FIRE MORTAR 3M OR
 EQUAL. 2020 FBC-B 714.5 HORIZONTAL ASSEMBLIES,
 714.5.1.2 THROUGH PENETRATIONS (OF HORIZONTAL
 ASSEMBLIES) FIRE STOP SYSTEMS. 714.5.1.2
 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER (2.49 PA). THE SYSTEM SHALL HAVE AN F RATING/ T
 RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE
 REQUIRED RATING OF THE FLOOR PENETRATED. THE 2020 FBC-B
 TABLE 601 REQUIRES A 2-HOUR FIRE RATING FOR THE FLOOR
 ASSEMBLY.
  
  
 6) SHEET A-1. THE FLOOR PLAN DOES NOT PROVIDE WHAT TYPE
 OF WALL FINISH AND BACKER BOARD WILL BE ON THE TUB &
 SHOWER WALLS. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS.
 THIS COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN RESTROOMS & SERVICE SINK
 AREAS EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH
 HARD, NON-ABSORBENT SURFACE.
  
 6A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 6B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 6C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 6D) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 6E) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-23 Cont ID  
Sent By equinone Date 2021-03-23 Time 16:06 Rev Time 0.00
Received By equinone Date 2021-03-23 Time 16:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-02-25 Cont ID  
Sent By equinone Date 2021-02-25 Time 14:54 Rev Time 0.00
Received By equinone Date 2021-02-25 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-03-22 Cont ID  
Sent By pleduc Date 2021-03-22 Time   Rev Time 0.00
Received By pleduc Date 2021-03-22 Time 11:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-02-22 Cont ID  
Sent By pleduc Date 2021-02-22 Time   Rev Time 0.00
Received By pleduc Date 2021-02-22 Time 16:17 Sent To  
Notes
2021-02-22 16:25:24THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 7TH EDITION OF FLORIDA FIRE PREVENTION CODE
 WHICH INCLUDES THE 2018 EDITION OF NFPA 1 AND NFPA 101.
 PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND
 COMPLIANCE.
  
 FIRE SPRINKLER; NFPA 13, 2016 EDITION.
 FIRE ALARM; NFPA 72, 2016 EDITION.
 CONSTRUCTION; NFPA 241, 2013 EDITION
  
 THE SUBMITTED PLANS DO NOT APPEAR TO CONFLICT WITH
 CURRENT FFPC EDITIONS.
  
 PLEASE UPDATE YOUR RECORDS TO REFLECT CURRENT FFPC
 EDITIONS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-04-05 Time 13:57 Rev Time 0.00
Received By aoliver Date 2021-04-01 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-03-29 Time 10:28 Rev Time 0.00
Received By lmarchan Date 2021-03-19 Time 08:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-03-05 Time   Rev Time 0.00
Received By ccarvaja Date 2021-02-17 Time 15:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-23 Cont ID  
Sent By medwards Date 2021-03-23 Time 12:39 Rev Time 0.00
Received By medwards Date 2021-03-23 Time 12:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-03-02 Cont ID  
Sent By medwards Date 2021-03-02 Time 13:08 Rev Time 0.00
Received By medwards Date 2021-03-02 Time 12:58 Sent To  
Notes
2021-03-02 13:11:09PRIVISO: AN EXHAUST FAN IS REQUIRED IN THE MASTER BATH
 IN THE SHOWER AREA. FBC RES R303.3
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-03-25 Cont ID  
Sent By ccole Date 2021-03-25 Time 15:07 Rev Time 0.00
Received By ccole Date 2021-03-25 Time 15:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-05 Cont ID  
Sent By ccole Date 2021-03-05 Time 17:17 Rev Time 0.00
Received By ccole Date 2021-03-05 Time 15:53 Sent To  
Notes
2021-03-05 17:18:131ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21020790
 3/5/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE DEMOLITION PLANS SHOWING THE EXISTING
 AND NEW FLOOR PLAN- SECTION 107.2.1 WPB.
  
 2) SHEET MP-1: PROVIDE SANITARY DRAINAGE AND WATER
 SUPPLY ISOMETRIC DRAWINGS FOR THE KITCHEN- SECTION
 107.3.5.1.3 WPB.
  
 3) MP-1: SHOW THE REQUIRED 1.4 IN. PER FT. SLOPE IN THE
 DRAIN DETAIL, AND CORRECT THE CODE SECTION- SECTION
 421.5.2 FBC P.
  
 4) MP-1: ADD PLUMBING NOTES FOR TBD SHOWER VALVE AND
 BATHTUB FAUCET.
 412.3 INDIVIDUAL SHOWER VALVES. INDIVIDUAL SHOWER AND
 TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER
 COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120 DEGREES F, WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION.
 412.5 BATHTUB AND WHIRLPOOL BATHTUB VALVES. THE HOT
 WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL BATHTUBS SHALL
 BE LIMITED TO A MAXIMUM TEMPERATURE OF 120 DEGREES F BY
 A WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO
 ASSE 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION
 IS OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE
 IN ACCORDANCE WITH SECTION 412.3.
  
 5) MP-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL FOR
 PIPES PENETRATING THE EXISTING SLAB- SECTIONS 315.1 FBC
 P, AND 714.4.1.2 FBC B.
  
 6) A-1: PROVIDE THE WIDTH OF THE NEW SHOWER DOOR IN THE
 MASTER BATHROOM- SECTION 421.4.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-03-29 Time 10:28 Rev Time 0.00
Received By   Date 2021-03-29 Time 09:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-02 Cont ID  
Sent By medwards Date 2021-03-02 Time 13:12 Rev Time 0.00
Received By medwards Date 2021-03-02 Time 13:12 Sent To  
Notes
***NONE***