Plan Review Details - Permit 21020668
| Plan Review Stops For Permit 21020668 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-06-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-06-30 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-06-30 |
Time |
08:05 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-21 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-17 |
Time |
08:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-05-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-25 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-21 |
Time |
10:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-20 |
Time |
06:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-21 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-21 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-21 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-05-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-25 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-25 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2021-05-25 17:12:40 | THE NOTE FOR THE DRYER IS POINTING TO THE RANGE IN THE | | | KITCHEN. IS THE TOTAL DEVELOPED LENGHT MENTION IN THE | | | NOTE FROM THE RANGE OR FROM THE DRYER LOCATION ACROSS | | | THE ROOM? FBC 107.2.1 | | | PLEASE SHOW THE THE LOCATION WHERE THE NEW DRYER DUCT | | | WILL CONNECT TO THE EXISTING DRYER DUCT. FBC 107.2.1 | | | THE DRAWING HAS A COPY OF THE ENGINEER'S SIGNATURE AND | | | SEAL. PLEASE PROVIDE A DIGITAL SIGNATURE FROM THE | | | ENGINEER. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-20 |
Time |
06:18 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-20 |
Time |
06:18 |
Sent To |
|
|
| Notes |
| 2021-05-20 06:20:24 | PLEASE PROVIDE A DRAWING THAT IS CLEAR AND READABLE, | | | THIS DRAWING IS NOT CLEAR AND I CANNOT READ IT TO | | | DETERMINE EXACTLY WHAT THE SCOPE OF WORK FOR THE | | | MECHANICAL WOULD INCLUDE. PROVIDE A SCOPE OF WORK FOR | | | THE MECHANICAL WORK BEING COMPLETED IN THIS PROJECT. | | | THE MECHANICAL CONTRACTOR MUST PRINT THEIR NAME AND | | | SIGN THEIR NAME ON THE DRAWING. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-06-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-06-30 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-06-30 |
Time |
13:01 |
Sent To |
I |
|
| Notes |
| 2021-06-30 13:15:24 | DRAWING A2 WITH ENGINEER'S ORIGINAL SEAL/SIGNATURE. JG. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-21 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-21 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2021-06-21 10:16:52 | THIS IS A DIGITAL SUBMITTAL. THE DRAWINGS HAVE A COPY | | | OF THE WET SEAL AND SIGNATURE, THE DRAWINGS SUBMITTED | | | DIGITALLY WILL NEED TO BE DIGITALLY SIGNED BY THE | | | ENGINEER OF RECORD. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-20 |
Time |
06:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-20 |
Time |
06:20 |
Sent To |
|
|
| Notes |
|
|
|