| 2021-02-23 11:22:40 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21020545 |
| | 2/23/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GAS RISER IS INCOMPLETE. PLEASE PROVIDE THE |
| | FOLLOWING LIST OF ITEMS ON THE DRAWING IN COMPLIANCE |
| | WITH FBC- 2020 RES. FUEL GAS CODE: |
| | |
| | A) LABEL THE METER AS EITHER NEW OR EXISTING AND SHOW |
| | THE DELIVERY PRESSURE- SECTION G2413.2. |
| | |
| | B) DELIVERY PRESSURE AT REGULATOR- G2413.3 & G2421.1. |
| | |
| | C) COPPER PIPE SIZES- MAIN SUPPLY PIPE AT METER AND |
| | BRANCHES- G2413.4.1 & G2413.4.2. |
| | |
| | D) PROVIDE THE CORRECT BTUH OF THE TANKLESS WATER |
| | HEATER. THE SUBMITTED SPECS HAS A HIGHLIGHT INDICATING |
| | 150,000 BTUH HOWEVER THE RISER INDICATES 199,000 BTUH. |
| | |
| | E) PLEASE LABEL THE APPLIANCES AS NEW OR EXISTING. THE |
| | RISER SHOWS A POOL HEATER NOT INCLUDED IN THE PERMIT |
| | APPLICATION- SECTION 107.2.1 WPB. PLEASE NOTE THAT A |
| | COMPLETE RISER DRAWING FOR THE SYSTEM SHALL BE |
| | SUBMITTED THAT INCLUDES ALL EXISTING PIPING AND |
| | APPLIANCES IN ORDER TO ENSURE A SAFER OPERATING SYSTEM- |
| | PLEASE SEE SECTIONS G2412.3 & G2412.4 FBC RES. |
| | |
| | F) PIPE SIZING TABLES USED- FBC RES. FUEL GAS- 2020 7TH |
| | EDITION, OR FBC- 2020 7TH EDITION FUEL GAS. PLEASE NOTE |
| | THE SUBMITTED PIPE SIZING TABLE IS FROM THE OUTDATED |
| | 2017 CODE- SECTION G2413.3. |
| | |
| | G) SHOW THE LOCATIONS OF SHUT OFF VALVES AND |
| | REGULATORSD AT APPLIANCES- SECTIONS 2420.1 & 2421.1 FBC |
| | RES. GAS. |
| | |
| | 2) THE RISER AND THE FLAT LINE GAS DRAWING SHALL EACH |
| | BEAR THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR |
| | OR QUALIFIER OF RECORD, AND SHALL ALSO INDICATE THE |
| | PROJECT ADDRESS- SECTION 107.2.1 WPB. |
| | |
| | 3) SUBMIT SPECS FOR THE NEW RANGE AND POOL HEATER- |
| | SECTION G2431.1 FBC RES.GAS. |
| | |
| | 4) SUBMIT THE CORRECT OUTLET AND INLET PRESSURE TABLE |
| | FOR THE B42 REGULATOR. THE TABLE IN THE SUBMITTAL IS |
| | FOR AN OUT PRESSURE OF 2 PSI. YOU SHOULD BE DROPPING |
| | PRESSURE FROM 2 PSI TO A LOW- PRESSURE SYSTEM. PLEASE |
| | NOTE THE NAVIEN WH SPECS INDICATE AN INLET PRESSURE OF |
| | 10.5 IN/WC- SECTION 2421.1 FBC RES.GAS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |