Plan Review Details - Permit 21020452
| Plan Review Stops For Permit 21020452 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-02-18 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-02-18 |
Time |
20:44 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-02-18 |
Time |
19:48 |
Sent To |
|
|
| Notes |
| 2021-02-18 20:44:49 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL CONTRACTOR NOT ALLOWED TO MAKE 480V | | | DESIGNS. ENGINEER REQUIIRED. F.S.471.003(2)(H)(2A) | | | | | | 2. 4/0 CU OR EQUIVALENT IS THE MINIMUM CONDUCTOR SIZE | | | FOR A 225AMP SERVICE. NEC 230 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-02-18 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-02-18 |
Time |
20:45 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-02-09 |
Time |
12:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-02-18 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-02-18 |
Time |
20:45 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-02-18 |
Time |
20:44 |
Sent To |
|
|
| Notes |
| 2021-02-18 20:45:20 | 480V DESIGN REQURIES ENGINEER. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2021-02-12 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2021-02-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2021-02-12 |
Time |
|
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |