| 2021-03-17 08:36:04 | 1ST REVIEW FBC-2020 RES. FUE GAS |
| | PERMIT- 21020420 |
| | 3/17/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES |
| | ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE |
| | RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO |
| | FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE: |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | F) TYPES AND SIZES OF PIPING. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | H) OUTLET PRESSURES AT REGULATORS. PLEASE LIST THE MAKE |
| | AND SELECTED MODEL REGULATOR ON THE DRAWING. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE BBQ |
| | GRILL AND PIZZA OVEN- SECTION G2406.1, G2406.3, G2447.1 |
| | FBC RES. PLEASE REVIEW THE INSTALLATION GUIDELINES AND |
| | SHOW ALL REQUIRED CLEARANCES TO COMBUSTIBLES, OVERHEAD |
| | ROOF CONSTRUCTION AND OPENINGS INTO THE BUILDING. IT |
| | APPEARS THE NEW APPLIANCES ARE BEING INSTALLED IN A |
| | PARTIALLY ENCLOSED COMBUSTIBLE STRUCTURE WHICH MAY BE |
| | PROHIBITED PER MANUFACTURER'S SPECIFICATIONS, AND MAY |
| | ALSO REQUIRE INSTALLATION OF EXHAUST HOODS. PLEASE NOTE |
| | THAT A MINIMUM 10 FT. CLEARANCE FROM THE EXHAUST OF THE |
| | APPLIANCES TO AIR INTAKES AND OPENINGS INTO THE |
| | BUILDINGS SUCH AS OPERABLE DOORS AND WINDOWS IS |
| | REQUIRED UNDER SECTION R303.5.1 FBC RES. MANUFACTURER?S |
| | SPECIFICATIONS AND INSTALLATIONS ARE REQUIRED TO BE |
| | ONSITE AT TIME OF INSPECTION- SECTION G2408.1 & G2447.1 |
| | FBC RES. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICTIONS FOR NEW GAS |
| | REGULATORS MARKED OR HIGHLISHTED TO SHOW THE SELECTED |
| | MODELS, INLET AND OUTLET PRESSURES, AND ORIFICE SIZES- |
| | SECTION G2421 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |