Plan Review Details - Permit 21020420
Plan Review Stops For Permit 21020420
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 08:23 Rev Time 0.00
Received By rmcphers Date 2021-05-20 Time 08:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-16 Cont ID  
Sent By rmcphers Date 2021-03-16 Time 12:27 Rev Time 0.00
Received By rmcphers Date 2021-03-16 Time 11:25 Sent To  
Notes
2021-03-16 12:27:37PATIO ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE CODE IN EFFECT HAS CHANGED ON 1/1/2021 - PLEASE
 REVISE THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN
 EFFECT (2020 FBC AND ASCE 7-16)
 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED FOR WIND
 DESIGN FBC R301.2.1
 3) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT AS
 NOTED ON THE DRAWINGS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-12 Cont ID  
Sent By equinone Date 2021-05-12 Time 15:27 Rev Time 0.00
Received By equinone Date 2021-05-12 Time 15:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-04 Cont ID  
Sent By equinone Date 2021-03-04 Time 08:54 Rev Time 0.00
Received By equinone Date 2021-03-04 Time 08:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-05-27 Cont ID  
Sent By ccole Date 2021-05-27 Time 10:29 Rev Time 0.00
Received By ccole Date 2021-05-27 Time 10:26 Sent To  
Notes
2021-05-27 10:33:08THE CURRENT PLANS ARE APPROVED WITH EXCEPTION.
 A REVISION TO THE APPROVED PLANS IS REQUIRED TO EITHER
 RELOCATE THE GAS GRILL AND PIZZA OVEN FROM BELOW THE
 COMBUSTIBLE TRELLIS, OR MODIFY THE TRELLIS TO MAKE IT A
 NON-COMBUSTIBLE STRUCTURE.
 CCOLE- 5/27/2021
  
 2ND REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21020420
 5/13/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED MANUFACTURER'S SPECIFICATIONS FOR THE
 AFPO-C ARTISAN FIRE PIZZA OVEN AND THE K750HB HYBRID
 FIRE GRILL EACH HAVE THIS STATEMENT PRINTED ON THEIR
 FRONT PAGES- "NEVER PLACE (OVEN) (GRILL) UNDERNEATH AN
 OVERHEAD COMBUSTIBLE STRUCTURE". THE ARCHITECTURAL PLAN
 APPEARS TO INDICATE AN EXISTING WOOD FRAME ROOF OR
 TRELLIS ABOVE IT. THE INSTALLATIONS ARE DENIED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-05-13 Cont ID  
Sent By ccole Date 2021-05-13 Time 09:20 Rev Time 0.00
Received By ccole Date 2021-05-13 Time 08:12 Sent To  
Notes
2021-05-13 09:20:252ND REVIEW FBC-2020 RES. FUE GAS
 PERMIT- 21020420
 5/13/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1)) THE SUBMITTED MANUFACTURER'S SPECIFICATIONS FOR THE
 AFPO-C ARTISAN FIRE PIZZA OVEN AND THE K750HB HYBRID
 FIRE GRILL EACH HAVE THIS STATEMENT PRINTED ON THEIR
 FRONT PAGES- "NEVER PLACE (OVEN) (GRILL) UNDERNEATH AN
 OVERHEAD COMBUSTIBLE STRUCTURE". THE ARCHITECTURAL PLAN
 APPEARS TO INDICATE AN EXISTING WOOD FRAME ROOF OR
 TRELLIS ABOVE IT. THE INSTALLATIONS ARE DENIED.
  
 2) THE SUBMITTAL FOR THE GOVERNOR GAS REGULATORS
 INDICATES OUTLET PRESSURES OF 8- 11 IN. W.C., HOWEVER
 THE NEW OVEN AND GRILL HAVE INPUT PRESSURES OF 7 IN.
 W.C. PLEASE SPECIFY THE CORRECT REGULATORS FOR THE
 INSTALLATIONS- SECTION G2421.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-03-17 Cont ID  
Sent By ccole Date 2021-03-17 Time 08:35 Rev Time 0.00
Received By ccole Date 2021-03-17 Time 07:12 Sent To  
Notes
2021-03-17 08:36:041ST REVIEW FBC-2020 RES. FUE GAS
 PERMIT- 21020420
 3/17/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE
 RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO
 FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 F) TYPES AND SIZES OF PIPING.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS. PLEASE LIST THE MAKE
 AND SELECTED MODEL REGULATOR ON THE DRAWING.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE BBQ
 GRILL AND PIZZA OVEN- SECTION G2406.1, G2406.3, G2447.1
 FBC RES. PLEASE REVIEW THE INSTALLATION GUIDELINES AND
 SHOW ALL REQUIRED CLEARANCES TO COMBUSTIBLES, OVERHEAD
 ROOF CONSTRUCTION AND OPENINGS INTO THE BUILDING. IT
 APPEARS THE NEW APPLIANCES ARE BEING INSTALLED IN A
 PARTIALLY ENCLOSED COMBUSTIBLE STRUCTURE WHICH MAY BE
 PROHIBITED PER MANUFACTURER'S SPECIFICATIONS, AND MAY
 ALSO REQUIRE INSTALLATION OF EXHAUST HOODS. PLEASE NOTE
 THAT A MINIMUM 10 FT. CLEARANCE FROM THE EXHAUST OF THE
 APPLIANCES TO AIR INTAKES AND OPENINGS INTO THE
 BUILDINGS SUCH AS OPERABLE DOORS AND WINDOWS IS
 REQUIRED UNDER SECTION R303.5.1 FBC RES. MANUFACTURER?S
 SPECIFICATIONS AND INSTALLATIONS ARE REQUIRED TO BE
 ONSITE AT TIME OF INSPECTION- SECTION G2408.1 & G2447.1
 FBC RES.
  
 3) SUBMIT MANUFACTURER'S SPECIFICTIONS FOR NEW GAS
 REGULATORS MARKED OR HIGHLISHTED TO SHOW THE SELECTED
 MODELS, INLET AND OUTLET PRESSURES, AND ORIFICE SIZES-
 SECTION G2421 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-05-25 Time   Rev Time 0.00
Received By aoliver Date 2021-05-11 Time 07:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-06 Cont ID  
Sent By lcrespo Date 2021-04-06 Time 11:12 Rev Time 0.00
Received By lcrespo Date 2021-03-01 Time 08:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-05-13 Cont ID  
Sent By ccole Date 2021-05-13 Time 09:20 Rev Time 0.00
Received By ccole Date 2021-05-13 Time 08:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-03-17 Cont ID  
Sent By ccole Date 2021-03-17 Time 08:20 Rev Time 0.00
Received By ccole Date 2021-03-17 Time 07:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 08:23 Rev Time 0.00
Received By rmcphers Date 2021-05-20 Time 08:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-16 Cont ID  
Sent By rmcphers Date 2021-03-16 Time 12:27 Rev Time 0.00
Received By rmcphers Date 2021-03-16 Time 12:27 Sent To  
Notes
2021-03-16 12:28:16SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 2 Status P Date 2021-05-24 Cont ID  
Sent By kalexand Date 2021-05-24 Time 15:30 Rev Time 0.00
Received By kalexand Date 2021-05-24 Time 15:30 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-04-05 Cont ID  
Sent By kalexand Date 2021-04-05 Time 09:11 Rev Time 0.00
Received By kalexand Date 2021-04-05 Time 09:11 Sent To I
Notes
2021-04-05 09:13:02ZONING PLAN REVIEW
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE TWO (2) COPIES OF A CURRENT AND/OR SURVEY,
 WHICH INCLUDES THE PROPERTY'S ADDRESS AND LEGAL
 DESCRIPTION. PLEASE ILLUSTRATE THE FOLLOWING ON THE
 SURVEY AND/OR SITE PLAN:
 - LOCATION OF THE PROPOSED WORK.
 - SETBACK DIMENSIONS FROM ANY EXTERIOR IMPROVEMENTS TO
 ALL ADJACENT PROPERTY LINES.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved