2021-04-22 13:00:42SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW - NO NEW DRAWINGS OR ROOFING PRODUCT
 APPROVAL WAS ADDED.
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE REQUIRED EXERIOR WALL WATER BARRIER
 FBC R703.2 WATER-RESISTIVE BARRIER.
 ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND
 BREAKS, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR
 OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED
 OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS.
 2) CODE IN EFFECT HAS CHANGED ON 1/1/2021 - PLEASE
 REVISE THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN
 EFFECT (2020 FBC AND ASCE 7-16)
 3) ROOF PRODUCT APPROVAL PROVIDED - THE ROOFING SYSTEM
 CHOSEN HAS A WIND DESIGN PRESSURE OF (-90) - PER 2020
 FBC TABLE TABLE R301.2(2) AND TABLE R301.2(3) ROOF ZONE
 3 REQUIRES A WIND DESIGN PRESSURE OF (-108.17) THIS
 SYSTEM CANNOT BE USED UNLESS PROVIDED WITH SITE
 SPECIFIC WIND DESIGN PRESSURES FROM A QUALIFIED DESIGN
 PROFESSIONAL THAT SHOW THE WIND DESIGN BELOW THE (-90)
 - SEE NOTE NUMBER 10 ON THE PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By rmcphers Date 2021-03-18 Time 09:18 Rev Time 0.00
Received By rmcphers Date 2021-03-18 Time 08:05 Sent To  
Notes
2021-03-18 09:18:01SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE REQUIRED EXERIOR WALL WATER BARRIER
 FBC R703.2 WATER-RESISTIVE BARRIER.
 ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND
 BREAKS, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR
 OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED
 OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS.
 2) CODE IN EFFECT HAS CHANGED ON 1/1/2021 - PLEASE
 REVISE THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN
 EFFECT (2020 FBC AND ASCE 7-16)
 3) ROOF PRODUCT APPROVAL PROVIDED - THE ROOFING SYSTEM
 CHOSEN HAS A WIND DESIGN PRESSURE OF (-90) - PER 2020
 FBC TABLE TABLE R301.2(2) AND TABLE R301.2(3) ROOF ZONE
 3 REQUIRES A WIND DESIGN PRESSURE OF (-108.17) THIS
 SYSTEM CANNOT BE USED UNLESS PROVIDED WITH SITE
 SPECIFIC WIND DESIGN PRESSURES FROM A QUALIFIED DESIGN
 PROFESSIONAL THAT SHOW THE WIND DESIGN BELOW THE (-90)
 - SEE NOTE NUMBER 10 ON THE PRODUCT APPROVAL.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-06-28 Cont ID  
Sent By jleahy Date 2021-06-28 Time 11:25 Rev Time 0.00
Received By jleahy Date 2021-06-28 Time 10:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-06-15 Cont ID  
Sent By jleahy Date 2021-06-15 Time 13:50 Rev Time 0.00
Received By jleahy Date 2021-06-15 Time 13:40 Sent To  
Notes
2021-06-15 13:54:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 WORK SURFACE COUNTER TOP IN LAUNDRY ROOM REQUIRES
 OUTLETS PER 210.52(C)(1)
  
 210.52(C)(1) WALL COUNTERTOP AND WORK SURFACE. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP AND WORK SURFACE THAT IS 300 MM (12 IN.) OR
 WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO
 POINT ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.)
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-04-23 Cont ID  
Sent By jleahy Date 2021-04-23 Time 07:53 Rev Time 0.00
Received By jleahy Date 2021-04-23 Time 07:48 Sent To  
Notes
2021-04-23 07:55:21SEE REVIEW NOTES FROM FIRST REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-11 Cont ID  
Sent By jleahy Date 2021-03-11 Time 09:32 Rev Time 0.00
Received By jleahy Date 2021-03-11 Time 09:27 Sent To  
Notes
2021-03-11 09:36:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NOTES ON PLANS REFERNCE 2014 NEC THIS PERMIT IS
 UNDER THE 2017 NEC AND THE 2020FBC, PLEASE CORRECT THE
 CODE EDITIONS BEING USE.
  
 2) RISER SHOWS TWO PANEL A'S PLEASE CORRECT TO A AND B
  
 3) WIRE SIZES NOT SHOWN TO ONE OF THE PANELS
  
 4) WHICH TAP RULE ARE YOU USING FOR THE FEEDERS?
  
 5) ARC FAULT CIRCUITS ARE REQUIRED IN MORE AREAS THAN
 NOTED PLEASE CORRECT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-30 Cont ID  
Sent By rmcphers Date 2021-06-30 Time 07:58 Rev Time 0.00
Received By rmcphers Date 2021-06-25 Time 13:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-21 Cont ID  
Sent By rmcphers Date 2021-06-21 Time 14:56 Rev Time 0.00
Received By rmcphers Date 2021-06-09 Time 16:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-23 Cont ID  
Sent By jleahy Date 2021-04-23 Time 07:55 Rev Time 0.00
Received By jleahy Date 2021-04-15 Time 11:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-18 Cont ID  
Sent By rmcphers Date 2021-03-18 Time 09:18 Rev Time 0.00
Received By rmcphers Date 2021-03-05 Time 11:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-06-14 Cont ID  
Sent By medwards Date 2021-06-14 Time 16:07 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 16:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-04-20 Cont ID  
Sent By medwards Date 2021-04-20 Time 12:45 Rev Time 0.00
Received By medwards Date 2021-04-20 Time 12:45 Sent To  
Notes
2021-04-20 12:45:441ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020360 2ND CYCLE
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A MECHANICAL SUB-PERMIT IS REQUIRED.
  
 2) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 3) PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED
 TO BE SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
  
 THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-03-12 Cont ID  
Sent By medwards Date 2021-03-12 Time 06:17 Rev Time 0.00
Received By medwards Date 2021-03-12 Time 06:03 Sent To  
Notes
2021-03-12 06:18:061ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020360
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS
 PROJECT. FBC EC 101.5.1.1.2
  
 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC RES EC R403.7, FBC EC M1401.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-03-16 Cont ID  
Sent By abelisle Date 2021-03-16 Time 17:22 Rev Time 0.00
Received By abelisle Date 2021-03-16 Time 17:22 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2021-06-30 Cont ID  
Sent By rmcphers Date 2021-06-30 Time 07:58 Rev Time 0.00
Received By rmcphers Date 2021-06-30 Time 07:58 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2021-06-21 Cont ID  
Sent By rmcphers Date 2021-06-21 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2021-06-21 Time 14:54 Sent To  
Notes
2021-06-21 14:54:36NO ROOFING SHOWN ON THE DRAWINGS

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-04-22 Cont ID  
Sent By rmcphers Date 2021-04-22 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2021-04-22 Time 13:01 Sent To  
Notes
2021-04-22 13:01:19SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By rmcphers Date 2021-03-18 Time 09:18 Rev Time 0.00
Received By rmcphers Date 2021-03-18 Time 09:18 Sent To  
Notes
2021-03-18 09:18:35SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-10 Cont ID  
Sent By medwards Date 2021-06-10 Time 15:38 Rev Time 0.00
Received By medwards Date 2021-06-10 Time 15:38 Sent To  
Notes
2021-06-10 15:44:39ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS ROUTED TO
 STORAGE. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-04-20 Cont ID  
Sent By medwards Date 2021-04-20 Time 12:45 Rev Time 0.00
Received By medwards Date 2021-04-20 Time 12:45 Sent To  
Notes
2021-04-20 12:47:20DESIGNER OF DRAWINGS MUST DIGITALLY ISGN AND SEAL OR
 YOU MAY BRING ORIGINAL SIGNED AND SEALED PAPER DRAWINGS
 TO OUR OFFICE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-12 Cont ID  
Sent By medwards Date 2021-03-12 Time 06:20 Rev Time 0.00
Received By medwards Date 2021-03-12 Time 06:20 Sent To  
Notes
2021-03-12 06:22:15THE DRAWINGS APPEAR TO HAVE A COPY OF A SEAL AND
 SIGNATURE. THE DOCUMENTS WILL NEED TO BE DIGITALLY
 SIGNED AND SEALED.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  