Plan Review Details - Permit 21020334
Plan Review Stops For Permit 21020334
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-03-03 Time   Rev Time 0.00
Received By bdolan Date 2021-03-03 Time 14:25 Sent To  
Notes
2021-03-03 14:26:12THIS PLAN REVISION WAS REVIEWED AND APPROVED BY THE
 FIRE DEPARTMENT. FORWARD TO PERMIT LIBRARIAN
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-02-17 Cont ID  
Sent By bdolan Date 2021-02-17 Time 14:21 Rev Time 0.00
Received By bdolan Date 2021-02-17 Time 14:20 Sent To  
Notes
2021-02-17 14:20:58THIS PLAN WAS REVIEWED AND FAILED BY LT. BRIAN DOLAN,
 FIRE INSPECTOR WITH THE FOLLOWING COMMENTS:
  
 1. THE BRAIDED HOSE ASSEMBLIES (FLEX DROPS) LISTED IN
 THE PLANS AND THE HYDRAULIC CALCULATION ARE
 INCONSISTENT AND SIGNIFICANTLY DIFFERENT. PLEASE
 EXPLAIN WHICH IS THE END USE PRODUCT AND PROVIDE
 CONSISTENT LANGUAGE IN PLAN AND HYDRAULIC CALCULATIONS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-04 Cont ID  
Sent By lmarchan Date 2021-03-04 Time 10:24 Rev Time 0.00
Received By lmarchan Date 2021-02-25 Time 06:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-19 Cont ID  
Sent By ccarvaja Date 2021-02-19 Time 09:12 Rev Time 0.00
Received By ccarvaja Date 2021-02-11 Time 08:34 Sent To  
Notes
***NONE***