Plan Review Details - Permit 21020328
Plan Review Stops For Permit 21020328
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-03-25 Cont ID  
Sent By jwitmer Date 2021-03-25 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2021-03-25 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-10 Cont ID  
Sent By jwitmer Date 2021-03-10 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2021-03-10 Time 13:15 Sent To  
Notes
2021-03-10 14:07:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020328
 ADD: 327 HIBISCUS ST.
 CONT: SHUTTER UP INDUSTRIES INC/ QUALIFIER JEREMY S
 KOBOSKO
 TEL: 561-588-2623
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MARCH 10TH/ 2021
 ACTION: DENIED
  
 1) COMPLIED. THE CONTRACTOR (QUALIFIER/ JEREMY S
 KOBOSKO) THAT CREATED / DREW THE SET OF PLANS SHEET 1 &
 2TWILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE
 PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 2A)SEMI-COMPLIED. THERE IS A SINGLE DRAWING (ELEVATION
 OF OPENING) BUT THERE IS CONFUSION AS TO THE
 TERMINOLOGY USED AND WHAT IS SHOWN IN THE ELEVATION
 DETAIL. THERE ARE 2 OPENINGS PLEASE MAKE A ELEVATION
 DRAWING FOR EACH OPENING, PROVIDE THE OVER ALL WIDTH
 AND HEIGHT OF THE OPENING TO DETERMINE MULLION LENGTHS.
 2ND PROVIDE THE OPENING SIZE ( GLAZING FOR EACH OPENING
 BE IT WINDOW OR DOOR. IDENTIFY IF THE OPENING IS A
 WINDOW AND OR DOOR.
 1ST ROUND COMMENTS. THE PERMIT APPLICATION INDICATES
 THE REPLACEMENT OF 4 PICTURE WINDOWS AND 1 EXTERIOR
 DOOR. THE FLOOR PLAN ONLY SHOWS 2 OPENINGS. THE WRITTEN
 WORDS ARE SO SMALL WHEN THE PLANS GO TO RECORD
 RETENTION, THEY MAY NOT BE LEGIBLE FOR RECORD
 RETENTION. 107.2.1.3. QUALITY OF PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT POLICY OTHER
 STANDARDS FOR THE PLANS AND SPECIFICATIONS IN ORDER TO
 PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 2B) 2ND REQUEST, THE FLOOR PLAN IDENTIFIES 2 OPENINGS,
 OPENING # 1 APPEARS TO BE CLOSE TO AN OUTSIDE CORNER OF
 THE BUILDING BUT NO DIMENSION IS GIVEN TO HOW CLOSE
 OPENING # 1 IS TO THE CORNER OF THE BUILDING. WHEN IN A
 CORNER WALL ZONE THE PRESSURES FOR THE OPENING ARE
 HIGHER.
 1ST ROUND OF COMMENTS. THE WORDING ON THIS DOCUMENT
 APPEARS THE 4 SUPPOSED PICTURE WINDOWS ARE MULTIPLE (2)
 WINDOWS IN EACH OPENING WITH MULLIONS, ACTUALLY 2
 OPENINGS, IS THAT CORRECT? WHERE IS THE DOOR THAT IS
 GOING TO BE REPLACED. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED. NO LOCATION IS GIVEN FOR THE DOOR MAYBE IN
 ZONE 4 OR 5.
  
 3) COMPLIED. THE DESIGN PRESSURE REPORT. THE DESIGN
 PRESSURE REPORT IS NOT DESIGNED BY A PROFESSIONAL
 ENGINEER. THERE IS NO DESIGNATION AS TO WHERE THE
 SUBMITTED PRESSURES CAME FROM. CONTRACTORS CAN NOT ACT
 AS ENGINEERS, YOU MUST PULL THE DESIGN PRESSURES FROM
 ASCE 7-16, THE 2020 FBC-B OR SOME OTHER RECOGNIZED
 SOURCE. ONE AND TWO FAMILY DWELLINGS THE CONTRACTOR CAN
 USE THE TABLE IN THAT CODE BOOK WITH MULTIPLIERS FOR
 EXPOSURE AND HEIGHT FOR RESIDENTIAL UNITS.
  
 4) COMPLIED. THE DESIGN PRESSURE REPORT SUBMITTED LIST
 THE MEAN ROOF HEIGHT AS 15 FEET. GOOGLE MAPS INDICATES
 THIS BUILDING IS A 2 STORY BUILDING. THE MEAN ROOF
 HEIGHT IS HIGHER THAN 15 FEET.
  
 5) COMPLIED. THE SUBMITTED DESIGN PRESSURE SHEET LIST
 THE HEIGHT OF THE ONE OPENING AS 92 INCHES WHEREAS THE
 2ND OPENING THE HEIGHT IS LISTED AS 149 INCHES IN
 HEIGHT. MAYBE A TYPO. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 6) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-23 Cont ID  
Sent By jwitmer Date 2021-02-23 Time 16:15 Rev Time 0.00
Received By jwitmer Date 2021-02-23 Time 15:30 Sent To  
Notes
2021-02-23 16:32:09WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020328
 ADD: 327 HIBISCUS ST.
 CONT: SHUTTER UP INDUSTRIES INC/ QUALIFIER JEREMY S
 KOBOSKO
 TEL: 561-588-2623
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) THE CONTRACTOR (QUALIFIER/ JEREMY S KOBOSKO) THAT
 CREATED / DREW THE SET OF PLANS SHEET 1 & 2TWILL NEED
 TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 2A) THE PERMIT APPLICATION INDICATES THE REPLACEMENT OF
 4 PICTURE WINDOWS AND 1 EXTERIOR DOOR. THE FLOOR PLAN
 ONLY SHOWS 2 OPENINGS. THE WRITTEN WORDS ARE SO SMALL
 WHEN THE PLANS GO TO RECORD RETENTION, THEY MAY NOT BE
 LEGIBLE FOR RECORD RETENTION. 107.2.1.3. QUALITY OF
 PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENT POLICY OTHER STANDARDS FOR THE PLANS AND
 SPECIFICATIONS IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORD MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 2B) THE WORDING ON THIS DOCUMENT APPEARS THE 4 SUPPOSED
 PICTURE WINDOWS ARE MULTIPLE (2) WINDOWS IN EACH
 OPENING WITH MULLIONS, ACTUALLY 2 OPENINGS, IS THAT
 CORRECT? WHERE IS THE DOOR THAT IS GOING TO BE
 REPLACED. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 NO LOCATION IS GIVEN FOR THE DOOR MAYBE IN ZONE 4 OR 5.
  
 3) THE DESIGN PRESSURE REPORT. THE DESIGN PRESSURE
 REPORT IS NOT DESIGNED BY A PROFESSIONAL ENGINEER.
 THERE IS NO DESIGNATION AS TO WHERE THE SUBMITTED
 PRESSURES CAME FROM. CONTRACTORS CAN NOT ACT AS
 ENGINEERS, YOU MUST PULL THE DESIGN PRESSURES FROM ASCE
 7-16, THE 2020 FBC-B OR SOME OTHER RECOGNIZED SOURCE.
 ONE AND TWO FAMILY DWELLINGS THE CONTRACTOR CAN USE THE
 TABLE IN THAT CODE BOOK WITH MULTIPLIERS FOR EXPOSURE
 AND HEIGHT FOR RESIDENTIAL UNITS.
  
 4) THE DESIGN PRESSURE REPORT SUBMITTED LIST THE MEAN
 ROOF HEIGHT AS 15 FEET. GOOGLE MAPS INDICATES THIS
 BUILDING IS A 2 STORY BUILDING. THE MEAN ROOF HEIGHT IS
 HIGHER THAN 15 FEET.
  
 5) THE SUBMITTED DESIGN PRESSURE SHEET LIST THE HEIGHT
 OF THE ONE OPENING AS 92 INCHES WHEREAS THE 2ND OPENING
 THE HEIGHT IS LISTED AS 149 INCHES IN HEIGHT. MAYBE A
 TYPO. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-25 Cont ID  
Sent By jwitmer Date 2021-03-25 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2021-03-25 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-03-10 Time 14:14 Rev Time 0.00
Received By lmarchan Date 2021-03-03 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-24 Cont ID  
Sent By jleahy Date 2021-02-24 Time 07:51 Rev Time 0.00
Received By jleahy Date 2021-02-12 Time 13:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-25 Cont ID  
Sent By jwitmer Date 2021-03-25 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2021-03-25 Time 09:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-10 Cont ID  
Sent By jwitmer Date 2021-03-10 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2021-03-10 Time 13:16 Sent To  
Notes
2021-03-10 14:12:11SIGNATURE- SEMI-COMPLIED. THE SUBMITTED FLOOR PLAN DOES
 HAVE THE CONTRACTOR SIGNATURE, PRINTED NAME AND LICENSE
 NUMBER, BUT NEW PLANS ARE REQUIRED SHOWING THE
 COMPONENTS FOR EACH OPENING.
 THE CONTRACTOR WILL NEED TO SIGN AND PRINT THEIR NAME
 AND LICENSE NUMBER ON THE NEW FLOOR PLAN
 CERTIFICATION BY CONTRACTOR. 107.3.4.3.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-23 Cont ID  
Sent By jwitmer Date 2021-02-23 Time 16:15 Rev Time 0.00
Received By jwitmer Date 2021-02-23 Time 15:30 Sent To  
Notes
2021-02-23 16:33:02SEE BUILDING REVIEW.