Plan Review Details - Permit 21020294
Plan Review Stops For Permit 21020294
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-05-10 Cont ID  
Sent By jwitmer Date 2021-05-10 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2021-05-10 Time 13:30 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-02-23 Cont ID  
Sent By jwitmer Date 2021-02-23 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2021-02-23 Time 07:27 Sent To  
Notes
2021-02-23 12:21:19COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-07-19 Cont ID  
Sent By jwitmer Date 2021-07-19 Time 14:57 Rev Time 0.00
Received By jwitmer Date 2021-07-19 Time 13:28 Sent To  
Notes
2021-07-19 14:57:49WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21020294
 ADD: 1016 CLARE UNIT: 4 BUILT IN 1946- PRE-FIRM
 CONT: PERK CONSTRUCTION INC. / U-21885
 TEL: 561-401-5984
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JULY 19TH/ 2021
 ACTION: PASSED
  
 NFIP. BUILDING BUILT IN 1946. PRE-FIRM / NOT
 SUBSTANTIAL IMPROVEMENT.
 UNIT 4 IMPROVEMENT VALUE PALM BEACH COUNTY PROPERTY
 APPRAISER OFFICE VALUE $1,937,948.00 VALUE.
 UNIT 4 IMPROVEMENT VALUE THIS PERMIT ($125,000.00) AND
 PERMIT VALUE IS INCLUDED IN THE LAST 5 YEARS $
 243,054.00 / NOT A SUBSTANTIAL IMPROVEMENT.
 NAVD 88 BFE 12.1 FEET.
 BUILDING SURVEY UNIT 6 FINISH FLOOR 16.19? NAVD88.
 SHEET S-1. VOLUNTEERING TO DRY-FLOOD PROOF. THE OLD
 TRUCK LOADING AREA LOWER FLOOR TO DRY FLOOD PROOF AND
 INSTALL FLOOD BARRIER DESIGNED TO CONFIRM WITH ASCE 24
 AND FEMA TECHNICAL BULLETIN 3-93.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2021-05-10 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2021-05-10 Time 13:30 Sent To  
Notes
2021-05-10 16:07:20WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21020294
 ADD: 1016 CLARE UNIT: 4 BUILT IN 1946
 CONT: PERK CONSTRUCTION INC. / U-21885
 TEL: 561-401-5984
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MAY 10TH/ 2021
 ACTION: DENIED
  
 1) SHEET G1.0:
 1A-1D) COMPLIED.
  
 1E) 2ND REQUEST. THIS BUILDING IS MADE UP OF SEVERAL
 FIRE WALLS, CREATING SEPARATE FIRE AREAS AND BUILDINGS.
 DEPENDING WHERE THE FIRE WALL LOCATION IS IN
 RELATIONSHIP TO THIS TENANT THE 1ST ROUND OF COMMENT
 MAY APPLY SECTION 1012 OF THE EXISTING BUILDING CODE.
 IF THIS TENANT HAS FIRE WALL CONSTRUCTION MAKING THIS A
 SEPARATE BUILDING THEN SECTION 1001.2.2 WOULD APPLY,
 BUT IN EITHER CASE THIS IS MORE THAN A LEVEL II
 ALTERATION.
 1ST ROUND OF COMMENTS. UNDER THE HEADING OF TYPE OF
 CONSTRUCTION, LEVEL OF ALTERATION IS STATED AS LEVEL
 II. PLEASE NOTE THE LAST KNOWN USE FOR THIS TENANT
 SPACE IS SELF-STORAGE, A S OCCUPANCY. THE PROPOSED USE
 IS INDICATED AS AN F-2 OCCUPANCY. THIS IS A CHANGE IN
 OCCUPANCY AND MUST BE TREATED AS SUCH. THE 2017
 EXISTING BUILDING CODE (FBC) SECTION 1001.2.2.1 PARTIAL
 CHANGE OF OCCUPANCY WITHIN A BUILDING IS TO BE
 FOLLOWED. AL SECTIONS OF SECTION 1012 OF THE 2020
 EXISTING BUILDING CODE SHALL APPLY.
  
 2-3) COMPLIED. SHEET LSP THE LIFE SAFETY PLAN.
  
 3J) NEW COMMENT 2ND REVIEW. SHEET A1.0 & A1.1. NEW
 WINDOWS IN THE EXIT PASSAGEWAY. PLEASE REVIEW IN THE
 2017 SECTION 716.6 FIRE- PROTECTION -RATED GLAZING AND
 TABLE 716.6 AND FOOTNOTE A. NOT PERMITTED EXPECT
 FIRE-RESISTANCE RATED GLAZING ASSEMBLIES TESTED TO ASTM
 E 119 OR UL 263, AS SPECIFIED IN SECTION 716.2.
  
 3K) 2017 FBC-B 716.6.4. GLASS AND GLAZING. GLAZING IN
 FIRE WINDOW ASSEMBLIES SHALL BE FIRE PROTECTION RATED
 GLAZING INSTALLED IN ACCORDANCE WITH AND COMPLYING WITH
 THE SIZE LIMITATIONS SET FORTH IN NFPA 80.
  
 4) SHEET A1.1 THE NEW REAR STOREFRONT SYSTEM DETAIL
 DOES HAVE A NOTE THAT THE NEW STOREFRONT BY OTHERS.
 PLEASE CLARIFY BY OTHERS SINCE THE CONTRACTOR SUBMITTED
 AN NOA, MIAMI-DADE NOTICE OF ACCEPTANCE 17-1114.02.
 SERIES SS-3500 ALUMINUM STOREFRONT SYSTEM. IS THIS WORK
 TO BE UNDER SEPARATE PERMIT, REVIEW AND ASSOCIATED
 FEES? 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 FOR THIS REVIEW THE ASSOCIATED QUESTIONS FOR THIS
 PRODUCT APPROVAL WILL BE ASKED.
  
 4A) SEMI-COMPLIED. THE SHOP DRAWING STAMP OF APPROVAL
 IS ON THE PRODUCT APPROVAL BUT THE CONTRACTOR NOR
 DESIGN PROFESSIONAL HAS COMPLIED WITH COMMENT 4B
 IDENTIFYING THE TYPE OF GLAZING, SIZE OF GLAZING
 ASSOCIATED PRESSURES ETC.
 W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 4B) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2021 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 5-6) COMPLIED.
  
 7) SHEET S-1 FLOOD BARRIER. THIS REVIEW A SURVEY WAS
 SUBMITTED WITH REVISIONS DATED 3/23/21. THERE ARE NEW
 ELEVATIONS ON THE SURVEY IN NAVD88 BUT THERE IS NO
 REFERENCE TO WHERE UNIT 4 IS IN RELATIONSHIP TO THE
 ELEVATIONS FOR THE FRONT OF THE BUILDING. THE ONLY UNIT
 NUMBER GIVEN ON THIS SURVEY IS UNIT # 6. WITHOUT THE
 GIVEN HEIGHT OF THE LOWER AND UPPER FLOORS KNOWN WE
 CANNOT ESTABLISH THE REQUIRED HEIGHT OF THE FLOOD LOG
 BARRIER.
 UNIT 4 IMPROVEMENT VALUE PALM BEACH COUNTY PROPERTY
 APPRAISER OFFICE VALUE $1,937,948.00 VALUE.
 UNIT 4 IMPROVEMENT VALUE THIS PERMIT AND LAST 5 YEARS $
 243,054.00.
  
 1ST ROUND OF COMMENTS. SHEET S-1 FLOOD BARRIER WALL.
 THIS BUILDING IS LOCATED IN AN AE FLOOD ZONE. PLEASE
 PROVIDE A SURVEY SHOWING THE EXISTING FLOOR ELEVATIONS
 IN NAV88. THE BASE FLOOD ELEVATION IS 12.1 FEET. IT
 APPEARS THE DESIGNER OF RECORD IS GOING TO DRY FLOOD
 PROOF THIS TENANT SPACE SINCE IT IS A COMMERCIAL
 ESTABLISHMENT.
 2017 FBC-B:
 1612.5 FLOOD HAZARD DOCUMENTATION. THE FOLLOWING
 DOCUMENTATION SHALL BE PREPARED AND SEALED BY A
 REGISTERED DESIGN
 PROFESSIONAL AND SUBMITTED TO THE BUILDING OFFICIAL:
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES:
 1.3. FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH
 ASCE 24. ALSO REVIEW FEMA?S TECHNICAL BULLETIN 3-93
 NON-RESIDENTIAL FLOODPROOFING- REQUIREMENTS AND
 CERTIFICATION.
  
 7A) FLOOD ZONE CERTIFICATES/ SURVEYORS- DEPT. OF
 AGRICULTURE
 1612.5 FLOOD HAZARD DOCUMENTATION. WEST PALM BEACH MUNI
 CODE. ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD
 PREVENTION & CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF PERMIT
 APPLICATION AFTER SEPT. 12/2016,
 AFTER OCT. 11/ 2017:
 ***********AN ADDITIONAL ONE FOOT OF FREE BOARD WILL BE
 REQUIRED OR (2) FEET ABOVE BSE FLOOD.**************
 AFTER OCT. 11/ 2017 THE BUILDING DEPARTMENT WILL HAVE
 ADOPTED THE NEW FLOOD MAPS IN NAVD 88 ELEVATIONS. YOU
 CAN GO TO THE WEBSITE:
 WWW.NGS.NOAA.GOV/TOOLS/VERTCON/VERTCON.HTML FOR
 CONVERSIONS.
  
 7B) OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018 DURING THE PERMITTING OF
 THIS STRUCTURE THERE WILL BE REQUIRED (3) DIFFERENT
 FLOOD ZONE CERTIFICATES REQUIRED:
  
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
  
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
  
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
  
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 8) COMPLIED.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-23 Cont ID  
Sent By jwitmer Date 2021-02-23 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2021-02-23 Time 07:27 Sent To  
Notes
2021-02-23 12:29:26WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21020294
 ADD: 1016 CLARE UNIT: 4
 CONT: PERK CONSTRUCTION INC. / U-21885
 TEL: 561-401-5984
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 23RD/ 2021
 ACTION: DENIED
  
 1) SHEET G1.0:
 1A) UNDER THE HEADING PROJECT DATA THE APPLICABLE CODES
 STATE THE FAMILY OF FLORIDA CODES AS THE 6TH EDITION OR
 THE 2017 FLORIDA BUILDING CODES. PLEASE NOTE ON DEC,
 31/ 2020 THE 7TH EDITION OF THE FLORIDA FAMILY OF
 CODES, THE 2020 FLORIDA BUILDING CODES WAS ADOPTED
 STATEWIDE. PLEASE UPDATE THE REFERENCE TO THE 2017 FBC
 ON ALL SHEETS PLEASE.
  
 1B) THE WIND DESIGN CRITERIA GIVEN DOES NOT STATE WHERE
 THE DESIGN AS TAKEN FROM. PLEASE NOTE WITH THE CODE
 CHANGE, THE NEW 2020 FBC-B THE REFERENCED STANDARDS
 CHAPTER 35 LIST THE ASCE 7-16 AS THE REFERENCED WIND
 DESIGN STANDARD.
  
 1C) CONSTRUCTION TYPE IS NOT GIVEN NOR IS IF THE
 BUILDING IS FIRE SPRINKLERED OR NOT?
 107.2.1.2.ADDITIONAL INFORMATION IS REQUIRED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA. 2021 FLORIDA
 BUILDING CODE W 2021 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
  
 MISSING CODE DATA:
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 PROPOSED FLOOD ELEVATION CERTIFICATE FOR STRUCTURES IN
 A SPECIFIC FLOOD HAZARD AREA
  
 1D) UNDER THE HEADING OF CONSTRUCTION TYPE THE BUILDING
 TYPE IS LISTED AS TYPE V-B. PLEASE BE AWARE THAT THE
 BUILDING TYPE IS AN IIA CONSTRUCTION TYPE, BECAUSE OF
 THE SQUARE FOOT AREA OF THE BUILDING AND STORIES, 2020
 FBC-B.
  
 1E) UNDER THE HEADING OF TYPE OF CONSTRUCTION, LEVEL OF
 ALTERATION IS STATED AS LEVEL II. PLEASE NOTE THE LAST
 KNOWN USE FOR THIS TENANT SPACE IS SELF-STORAGE, A S
 OCCUPANCY. THE PROPOSED USE IS INDICATED AS AN F-2
 OCCUPANCY. THIS IS A CHANGE IN OCCUPANCY AND MUST BE
 TREATED AS SUCH. THE 2020 EXISTING BUILDING CODE (FBC)
 SECTION 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY WITHIN A
 BUILDING IS TO BE FOLLOWED. AL SECTIONS OF SECTION 1012
 OF THE 2020 EXISTING BUILDING CODE SHALL APPLY.
  
 2) I KNOW THERE IS A SEPARATE DEMO PERMIT, BUT THIS MAY
 NOT GET CAUGHT IN THE DEMO-PERMIT SEE SHEETS AD2.0 AND
 LSP THE LIFE SAFETY PLAN. ON THE RIGHT SIDE OF THE
 SHEET THERE IS WHAT APPEARS AS A VERTICAL STAIRWAY
 EXIT, A FIRE RATED EXIT DOOR WITHIN THE VERTICAL EXIT
 MARKED AS D5 DEMO NOTE D5 STATES TO REMOVE THE DOOR AND
 FRAME. THEN THERE IS A RAMPED PORTION OF AN EXIT
 PASSAGEWAY TO THE TRUE EXIT DISCHARGE DOOR TO THE
 EXTERIOR OF THE BUILDING.
 IN THE 2020 FBC-B SECTION 1024.1 EXIT PASSAGEWAYS
 DISCUSS THE REQUIREMENTS OF THE EXIT PASSAGEWAY.
 OPENINGS INTO THE EXIT PASSAGEWAY ARE DISCUSSED IN
 1024.5. WHERE AN INTERIOR EXIT STAIRWAY OR RAMP IS
 EXTENDED TO AN EXIT DISCHARGE OR PUBLIC WAY BY AN EXIT
 PASSAGEWAY, THE EXIT PASSAGEWAY SHALL COMPLY WITH
 SECTION 1023.3.1. OF THE 2020 FBC-B.
 SECTION 1023.1 OF THE 2020 FBC-B STATES THE FIRE
 RESISTANCE RATINGS SHALL NOT BE LESS THAN THAT REQUIRED
 FOR THE INTERIOR EXIT STAIRWAY AND RAMP. A FIRE DOOR
 ASSEMBLY COMPLYING WITH SECTION 716.5 SHALL BE
 INSTALLED IN THE FIRE BARRIER TO PROVIDE A MEANS OF
 EGRESS FROM THE INTERIOR EXIT STAIRWAY AND RAMP TO THE
 EXIT PASSAGEWAY.
  
 3) SHEET LSP THE LIFE SAFETY PLAN:
 3A) PLEASE REFER TO COMMENT NUMBER 2 AS FAR AS THE
 REQUIRED DOORWAY BETWEEN THE INTERIOR EXIT STAIRWAY
 (FBC-B 1023 AND THE EXIT PASSAGEWAY SECTION 1024 OF THE
 2020 FBC-B.
  
 3B) THE OCCUPANT LOAD TABLE LIST 3 AREAS WITH EACH AREA
 LISTING A FRACTION OR TENTH OF AN OCCUPANT. OCCUPANTS
 FOR MEANS OF EGRESS ARE ALWAYS ROUNDED UP TO THE NEXT
 WHOLE OCCUPANT, NEVER AS PART OF AN OCCUPANT. THE
 BUILDING OFFICIALS INFORMAL INTERPRETATION OF SECTION &
 TABLE 1004.1.2.
  
 3C) THE LIFE SAFETY SHEET INDICATES THAT THE OCCUPANCY
 TYPE AS F2 NAME OF THE PROJECT IS THE PUMPHOUSE COFFEE
 ROASTERS, PLEASE PROVIDE THE ACTUAL PROCESS AND
 EQUIPMENT NEEDED FOR THE ROASTING OF THE COFFEE BEAN
 AND HOW WILL THE END PRODUCT BE PACKED. WHAT CHEMICALS
 IF ANY ARE USED IN THE PROCESS AND WHAT QUANTITIES OF
 THESE CHEMICALS ARE STORED ON SITE AT ANY GIVEN TIME.
 SECTION 306.2, 307.1 HAZARDOUS MATERIALS.
  
 3D) THE LIFE SAFETY PLAN STATES A STORAGE OCCUPANCY BUT
 DOES NOT DECLARE IF THE OCCUPANCY TYPE IS AN S1 OR S2
 OCCUPANCY PLEASE PROVIDE COMPLIANCE WITH EITHER SECTION
 311.2 MODERATE-HAZARD STORAGE 311.2 S-2 LOW-HAZARD
 STORAGE OF THE 2020 FBC-B. PLEASE PROVIDE WHEN THE
 COFFEE BEAN IS DELIVERED HOW IT IS ENCLOSED, IF ON
 PALLETS ETC.
  
 3E) WITH THE TYPE OF STORAGE OCCUPANCY NOT DECLARED WE
 CAN NOT DETERMINE IF OCCUPANCY SEPARATION IS REQUIRED
 SEE TABLE 508.4. OF THE 2020 FBC-B.
  
 3F) PLEASE PROVIDE WHAT TYPE OCCUPANCIES SURROUND THIS
 TENANT SPACE AND HOURLY RATING REQUIRED. SEE TABLE
 508.4.
  
 3G) THE LIGHT INDUSTRIAL SPACE B DOES NOT SHOW ANY
 EQUIPMENT IN THIS SPACE, ONLY 4 SQUARES, WHAT ARE THE
 SQUARES, THE COMMON PATH OF TRAVEL GOES RIGHT THROUGH
 THEM. ETC.
  
 3H) PLEASE PROVIDE WHAT OCCURS IN THE UPPER LEFT-HAND
 CORNER OF THE PLAN WHERE IT APPEARS TO BE 2 LONG
 CANTILEVERED COUNTERS. WHAT TYPE OF OCCUPANCY IS THIS
 AREA? 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3I) THE LIFE SAFETY PLAN DOES SHOW 2 MEANS OF EGRESS.
 THE FLOOR PLAN SHOWS A NEW STOREFRONT GLAZING SYSTEM AT
 THE REAR OF THE BUILDING. SHEET A1.0 SHOWS THE NEW
 GLAZING SYSTEM AND NEW EXTERIOR LANDING AND STAIRS. THE
 PLAN ALSO SHOW A 6INCH STEP DOWN ONTO THE NEW EXTERIOR
 LANDING.
  
 2021 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 4) SHEET A1.1 THE NEW REAR STOREFRONT SYSTEM DETAIL
 DOES HAVE A NOTE THAT THE NEW STOREFRONT BY OTHERS.
 PLEASE CLARIFY BY OTHERS SINCE THE CONTRACTOR SUBMITTED
 AN NOA, MIAMI-DADE NOTICE OF ACCEPTANCE 17-1114.02.
 SERIES SS-3500 ALUMINUM STOREFRONT SYSTEM. IS THIS WORK
 TO BE UNDER SEPARATE PERMIT, REVIEW AND ASSOCIATED
 FEES? 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 FOR THIS REVIEW THE ASSOCIATED QUESTIONS FOR THIS
 PRODUCT APPROVAL WILL BE ASKED.
  
 4A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 4B) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2021 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 5) SHEET A1.1 SHOWS AN INTERIOR AND EXTERIOR
 PREFABRICATED STAIR, HANDRAIL/ GUARDRAIL BY OTHERS. THE
 DESIGNER OF RECORD HAS NOT GIVEN THE FABRICATOR ANY
 DESIGN CRITERIA TO BUILD THE STAIRS. 2020 FBC-B TABLE
 1607.1 FOR LIVE LOADS, SECTION 1607.8.1 HANDRAILS AND
 GUARDS, 1011.5.2 RISERS AND TREADS, 1011.5.5.3 SOLID
 RISERS, 1014 HANDRAILS OR GUARDS 10.15.
  
 6) SHEET A1.1 DOES GIVE ELEVATION VIEWS OF THE
 RESTROOMS AND INDICATES TILE ON THE WALLS OF THE
 RESTROOMS BUT THE ENLARGE RESTROOM FLOOR DETAIL DOES
 INCLUDE THE SERVICE SINK BUT THERE IS NO INFORMATION TO
 SHOW COMPLIANCE WITH 2021 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION ON 06/2020. IN RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
 2020 FBC-B 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 7) SHEET S-1 FLOOD BARRIER WALL. THIS BUILDING IS
 LOCATED IN AN AE FLOOD ZONE. PLEASE PROVIDE A SURVEY
 SHOWING THE EXISTING FLOOR ELEVATIONS IN NAV88. THE
 BASE FLOOD ELEVATION IS 12.1 FEET. IT APPEARS THE
 DESIGNER OF RECORD IS GOING TO DRY FLOOD PROOF THIS
 TENANT SPACE SINCE IT IS A COMMERCIAL ESTABLISHMENT.
 2020 FBC-B:
 1612.5 FLOOD HAZARD DOCUMENTATION. THE FOLLOWING
 DOCUMENTATION SHALL BE PREPARED AND SEALED BY A
 REGISTERED DESIGN
 PROFESSIONAL AND SUBMITTED TO THE BUILDING OFFICIAL:
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES:
 1.3. FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH
 ASCE 24. ALSO REVIEW FEMA?S TECHNICAL BULLETIN 3-93
 NON-RESIDENTIAL FLOODPROOFING- REQUIREMENTS AND
 CERTIFICATION.
  
 7A) FLOOD ZONE CERTIFICATES/ SURVEYORS- DEPT. OF
 AGRICULTURE
 1612.5 FLOOD HAZARD DOCUMENTATION. WEST PALM BEACH MUNI
 CODE. ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD
 PREVENTION & CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF PERMIT
 APPLICATION AFTER SEPT. 12/2016,
 AFTER OCT. 11/ 2017:
 ***********AN ADDITIONAL ONE FOOT OF FREE BOARD WILL BE
 REQUIRED OR (2) FEET ABOVE BSE FLOOD.**************
 AFTER OCT. 11/ 2017 THE BUILDING DEPARTMENT WILL HAVE
 ADOPTED THE NEW FLOOD MAPS IN NAVD 88 ELEVATIONS. YOU
 CAN GO TO THE WEBSITE:
 WWW.NGS.NOAA.GOV/TOOLS/VERTCON/VERTCON.HTML FOR
 CONVERSIONS.
  
 7B) OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018 DURING THE PERMITTING OF
 THIS STRUCTURE THERE WILL BE REQUIRED (3) DIFFERENT
 FLOOD ZONE CERTIFICATES REQUIRED:
  
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
  
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
  
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
  
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 8) SHEET S1.0 DOES PROVIDE THE WIND DESIGN TO THE 2020
 FBC-B HOWEVER THE MEAN ROOF HEIGHT DOES STATE THE MEAN
 ROOF HEIGHT IS FOR BUILDINGS LESS THAN 30 FEET. PLEASE
 NOTE THIS IS A 3 STORY BUILDING WITH HIGHER CEILINGS
 THAN USUAL. THE DESIGN PRESSURES ARE ALSO STATED IN
 VULT, ALL PRODUCT APPROVALS ARE STATED IN VASD. THE
 OTHER ISSUES WITH THE STATED PRESSURES ARE THE
 PRESSURES TAKEN AT WHAT TRIBUTARY AREA/ EFFECTIVE WIND
 AREA AND WALL ZONE 4 OR 5. PLEASE NOTE THERE ARE
 MULLIONS TO ALSO BE CONCERNED WITH AND THE EFFECTIVE
 WIND AREA FOR THE MULLIONS. 2021 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-07-26 Cont ID  
Sent By jleahy Date 2021-07-26 Time 19:04 Rev Time 0.00
Received By jleahy Date 2021-07-26 Time 18:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-24 Cont ID  
Sent By equinone Date 2021-05-24 Time 10:55 Rev Time 0.00
Received By equinone Date 2021-05-24 Time 10:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-05 Cont ID  
Sent By equinone Date 2021-03-05 Time 15:36 Rev Time 0.00
Received By equinone Date 2021-03-05 Time 15:36 Sent To  
Notes
2021-03-05 15:36:51CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) RISER SHOWS AN EXISTING GROUNDING ELECTRODE
 CONDUCTOR SIZED AS #2 CU. PLEASE DESCRIBE TYPE OF
 ELECTRODE SYSTEM TO DETERMINE IF GEC COMPLIES WITH
 EXCEPTIONS (A) THRU (C) OF 250.66. DETAIL 5 (E5.0) DOES
 NOT INDICATE SIZE OF GEC TO MAIN SWITCHBOARD BUT SEEMS
 TO INDICATE THE FULL-SIZE GROUND IS REQUIRED. PLEASE
 CLARIFY OR OTHERWISE PLEASE SIZE GEC AS PER TABLE
 250.66 NEC 250.66
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-08-04 Cont ID  
Sent By pleduc Date 2021-08-04 Time   Rev Time 0.00
Received By pleduc Date 2021-08-04 Time 15:38 Sent To  
Notes
2021-08-04 15:42:49FIRE PROVISO
  
 ANY VENTILATION SYSTEM/DUCT WORK FOR ANY PIECE OF
 EQUIPMENT SHALL BE INSTALLED AND SUBMITTED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-05-14 Cont ID  
Sent By pleduc Date 2021-05-14 Time   Rev Time 0.00
Received By pleduc Date 2021-05-11 Time 12:55 Sent To  
Notes
2021-05-14 13:02:58FIRE PROVISO
  
 ANY VENTILATION SYSTEM/DUCT WORK FOR ANY PIECE OF
 EQUIPMENT SHALL BE INSTALLED AND SUBMITTED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-02-22 Cont ID  
Sent By pleduc Date 2021-02-22 Time   Rev Time 0.00
Received By pleduc Date 2021-02-22 Time 14:57 Sent To  
Notes
2021-02-22 15:20:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE INSUFFICIENT DETAIL PROVIDED FOR THE TYPE OF
 PROCESSING THAT IS BEING PROPOSED.
  
 PLEASE REVIEW AND PROVIDE A DETAILED NARRATIVE OF THE
 PROPOSED PROCESS.
  
  
 1A) PLEASE PROVIDE A DETAILS AND MANUFACTURES'S
 SPECIFICATION SHEETS OF THE PROPOSED EQUIPMENT USED IN
 THE PROCESSING OF THE PROPOSED.
  
 PLEASE INCLUDE A SEQUENCE OF OPERATION, START TO
 FINISH.
  
  
 2) SHEET G 1.0 - THERE IS NO INDICATION OF COMPLIANCE
 WITH THE CURRENT FLORIDA LIFE SAFETY CODE AND ALL OTHER
 APPLICABLE CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 7TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2018 EDITION OF NFPA 1 AND NFPA 101.
  
 THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES:
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2016 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2016 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2018 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2017 EDITION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND
 COMPLIANCE.
  
  
  
 3) SHEET F 2.0 - THERE IS INDICATIONS OF FIRE SPRINKLER
 WORK; HOWEVER, THERE IS NO INDICATION THAT ALL WORK,
 INCLUDING DEMO SHALL BE UNDER SEPARATE PERMIT & SHOP
 DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT.
  
  
 3A) SHEET G 1.0 - THERE IS INDICATIONS OF FIRE ALARM
 SYSTEM; HOWEVER, THERE IS NO INDICATION THAT ALL WORK,
 INCLUDING DEMO SHALL BE UNDER SEPARATE PERMIT & SHOP
 DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT.
  
  
 3B) THE EXISTING FIRE SPRINKLER & FIRE ALARM SYSTEMS
 SHALL REMIAN ACTIVE THROUGHOUT DEMO AND RECONSTRUCTION.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT.
  
  
  
 4) SHEET LSP - THERE ARE INDICATIONS OF 1 HOUR FIRE
 RATED TENANT SEPARATION WALLS; HOWEVER, THERE ARE NO
 INDICATIONS OF THE OCCUPANCY CLASSIFICATION OF THE
 TENANTS ON EACH SIDE.
  
 PER NFPA 101, CH 6,
  
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
  
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS
 3-HOUR FIRE
 RESISTANCE?RATED, 2-HOUR FIRE RESISTANCE?RATED, OR
 1-HOUR FIRE
 RESISTANCE?RATED AND SHALL MEET THE REQUIREMENTS OF
 CHAPTER 8.
 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED
 IN TABLE
 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE
 PERMITTED TO BE
 REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED
 TO LESS THAN 1
 HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 9.7.1.1(1) AND
 SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED
 BY THE
 DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES.
 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL,
 HORIZONTAL, OR
 BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED
 TO PROVIDE
 COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE
 BUILDING.
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED FIRE SEPARATED
 RATINGS OR JUSTIFY EXISTING CONDITIONS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2021-08-09 Cont ID  
Sent By ccole Date 2021-08-09 Time 10:36 Rev Time 0.00
Received By ccole Date 2021-08-09 Time 10:36 Sent To  
Notes
2021-08-09 10:37:02* FUEL GAS PROVISO:
 THE DESIGN PROFESSIONALS OF RECORD HAVE REQUESTED THAT
 COMPLETE INSTALLATION OF THE COFFEE ROASTERS INCLUDING
 GAS HOOKUP AND EXHAUST/VENT SYSTEMS BE DONE UNDER A
 SEPARATE REVISION PERMIT TO THIS MAIN PERMIT.

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2021-08-04 Cont ID  
Sent By ccole Date 2021-08-04 Time 10:30 Rev Time 0.00
Received By ccole Date 2021-08-04 Time 07:39 Sent To  
Notes
2021-08-04 10:30:474TH REVIEW FBC-2017 FUEL GAS
 PERMIT-21020294
 8/4//2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO THE 3RD REVIEW COMMENTS PRINTED
 BELOW, THE DESIGN ENGINEER FOR THE SYSTEM SUBMITTED A
 LETTER AND ADDITIONAL EXHAUST DUCT SPECIFICATIONS
 THROUGH EMAIL, BUT THOSE DOCUMENTS WERE NOT UPLOADED
 INTO THE PROJECT DOX SYSTEM FOR REVIEW. I HAVE ALSO
 BEEN ADVISED THROUGH EMAIL THAT MORE DOCUMENTS HAVE YET
 TO BE SUBMITTED. PLEASE PROVIDE A COMPLETE SUBMITTAL
 PACKAGE FOR THE COFFEE ROASTERS AND COMBUSTION AIR AND
 EXHAUST VENTILATION SYSTEMS. THE CURRENT SUBMITTAL
 PACKAGE UPLOADED FOR IN THIS REVIEW CYCLE DOES NOT
 INCLUDE THE MANUFACTURER'S SPECIFICATIONS FOR THE
 PROBAT G90- SECTION 623.1 FBC FG.
  
 2) SHEET M.3.2: PROBAT RECOMMENDATIONS PRINTED ON THE
 SHEET IDENTIFY THE VENT SYSTEM AS A CHIMNEY. PLEASE SEE
 SECTION 202 DEFINITIONS FBC FG- A CHIMNEY IS DEFINED AS
 PRIMARILY A VERTICAL STRUCTURE. THE EXHAUST VENT SYSTEM
 SHOWN ON THE PLAN IS PRIMARILY A HORIZONTAL STRUCTURE.
 AS NOTED IN THE 3RD REVIEW COMMENTS BELOW THE SYSTEM
 DESIGN DOES NOT APPEAR TO MEET THE "STRAIGHT OUT"
 REQUIREMENT AND IN FACT, IS TRAVELING THROUGH AN AREA
 THAT WILL BE OCCUPIED BY B0TH THE PUBLIC AND OTHER
 EMPLOYEES. PROBAT RECOMMENDATIONS SPECIFCALLY STATE
 THAT WHEN USING A SINGLE WALL DUCT, THE ROASTER AREA
 CANNOT BE ACCESSED BY ANYONE OTHER THAN THE OPERATOR.
 BASED ON THESE RECOMMENDATIONS IT APPEARS THAT USE OF
 THE SINGLE WALL DUCT SYSTEM SHOULD BE ALSO CONFINED TO
 THE ROASTER AREA. PLEASE NOTE THE RECOMMENDATIONS DO
 NOT HAVE THE SAME LIMITATION OF USE FOR THE DOUBLE WALL
 DUCT.
  
 3) WITH RESPECT TO THE COMBUSTION AIR/MAKEUP AIR BEING
 SUPPLIED MECHANICALLY USING AHU-4, PLEASE ADDRESS THESE
 CODE FBC FG REQUIRMENTS:
  
 A) SECTION 304.9: PROVIDE THE COMBUSTION AIR
 CALCULATIONS USING .35 CFMS PER 1000 BTUH TOTAL INPUT
 RATING OF THE ROASTERS.
  
 B) SECTION 304.9.1: EXHAUST FANS ARE SHOWN WHICH
 REQUIRE MAKE UP AIR TO REPLACE THE EXHAUSTED AIR. THE
 EXHAUST FAN CFM CAPACITIES HAVE NOT BEEN PROVIDED AND
 MAKEUP AIR NOT CALCULATED.
  
 C) SECTION 304.9.2: THE ROASTERS SHALL BE INTERLOCKED
 WITH THE SOURCE OF THE AIR TO PREVENT GAS BURNER
 OPERATION WHEN THE MECHANICAL AIR SUPPLY SYSTEM IS NOT
 IN OPERATION. PLEASE SHOW THE INTERLOCK SYSTEM BETWEEN
 THE ROASTERS AND AHU-4. IT IS ALSO IMPORTANT TO REVIEW
 THE FBC-MECHANICAL CODE- 2017 IN REGARD TO AIR
 BALANCING AND RECIRCULATION RESTRICTION OF AIR FROM THE
 ROASTER AREA TO OTHER OCCUPIED AREAS.
  
 3RD REVIEW
 SHEET M3.2: THERE APPEAR TO BE CONFLICTS BETWEEN THE
 PROBAT AND NORDFAB SPECIFICATIONS. THE PROBAT VENTING
 RECOMMENDATIONS ON THE NEW PLAN SHEET IDENTIFY THE
 ROASTERS AS CLASS III APPLIANCES WITH POSITIVE PRESSURE
 VENTING. PLEASE CLARIFY IF CLASS III IS INTENDED TO
 MEAN CATEGORY III AS DEFINED IN THE SECTION 202 FBC FG.
  
 PROBAT RECOMMENDS:
 A) POSITIVE PRESSURE VENT SYSTEM. (THE VENT DIAGRAM
 DOES INDICATE "POSITIVE PRESSURE" USING EXHAUST FANS AT
 THE APPLIANCES).
 B) TYPE G DUCTWORK WITH THE TEMPERATURE NOT TO EXCEED
 450 DEGREES F IN THE DUCTWORK.
 C) THE SINGLE OR DOUBLE DUCT SHOULD GO "STRAIGHT OUT"
 THE WALL.
 D) DUCT JOINTS SHALL BE SEALED.
 CHECKING DUCT COMPATIBILITY FOR ITEMS A, B, C, & D, THE
 NORDFAB SPECS INDICATE:
 A) USED UNDER VARIOUS "NEGATIVE STATIC PRESSURES"
 B) NOT IDENTIFIED AS TYPE G, AND COMPLETE PROBAT SPECS
 HAVE NOT BEEN SUBMITTED SO OPERATING EQUIPMENT AND DUCT
 TEMPERATURES ARE NOT KNOWN.
 C) THE VENT DIAGRAM INDICATES INDIVIDUAL EXHAUST RISERS
 CONNECTING TO A LARGE HORIZONTAL MAIN DUCT WHICH IS
 TRAVELING THROUGH OTHER AREAS WHICH DOES NOT APPEAR TO
 MEET THE "STRAIGHT OUT" REQUIREMENT.
 D) THE DUCT AND JOINTS WILL LEAK WHEN SEALED, AND
 LEAKAGE RATES HAVE BEEN ESTABLISHED UNDER "NEGATIVE"
 PRESSURES TESTING ONLY.
  
 BASED ON THE URGENCY EXPRESSED TO ME IN EMAILS FROM THE
 OWNER, PROMPT RESPONSES TO THE ABOVE ISSUES WOULD BE
 VERY HELPFUL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-07-28 Cont ID  
Sent By ccole Date 2021-07-28 Time 15:21 Rev Time 0.00
Received By ccole Date 2021-07-23 Time 14:42 Sent To  
Notes
2021-07-28 15:24:283RD REVIEW FBC-2017 FUEL GAS
 PERMIT-21020294
 7/28/2021
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 SHEET M3.2: THERE APPEAR TO BE CONFLICTS BETWEEN THE
 PROBAT AND NORDFAB SPECIFICATIONS. THE PROBAT VENTING
 RECOMMENDATIONS ON THE NEW PLAN SHEET IDENTIFY THE
 ROASTERS AS CLASS III APPLIANCES WITH POSITIVE PRESSURE
 VENTING. PLEASE CLARIFY IF CLASS III IS INTENDED TO
 MEAN CATEGORY III AS DEFINED IN THE SECTION 202 FBC FG.
 PROBAT RECOMMENDS:
  
 A) POSITIVE PRESSURE VENT SYSTEM. (THE VENT DIAGRAM
 DOES INDICATE "POSITIVE PRESSURE" USING EXHAUST FANS AT
 THE APPLIANCES).
 B) TYPE G DUCTWORK WITH THE TEMPERATURE NOT TO EXCEED
 450 DEGREES F IN THE DUCTWORK.
 C) THE SINGLE OR DOUBLE DUCT SHOULD GO "STRAIGHT OUT"
 THE WALL.
 D) DUCT JOINTS SHALL BE SEALED.
  
 CHECKING DUCT COMPATIBILITY FOR ITEMS A, B, C, & D, THE
 NORDFAB SPECS INDICATE:
 A) USED UNDER VARIOUS "NEGATIVE STATIC PRESSURES"
 B) NOT IDENTIFIED AS TYPE G, AND COMPLETE PROBAT SPECS
 HAVE NOT BEEN SUBMITTED SO OPERATING EQUIPMENT AND DUCT
 TEMPERATURES ARE NOT KNOWN.
 C) THE VENT DIAGRAM INDICATES INDIVIDUAL EXHAUST RISERS
 CONNECTING TO A LARGE HORIZONTAL MAIN DUCT WHICH IS
 TRAVELING THROUGH OTHER AREAS WHICH DOES NOT APPEAR TO
 MEET THE "STRAIGHT OUT" REQUIREMENT.
 D) THE DUCT AND JOINTS WILL LEAK WHEN SEALED, AND
 LEAKAGE RATES HAVE BEEN ESTABLISHED UNDER "NEGATIVE"
 PRESSURES TESTING ONLY.
  
 BASED ON THE URGENCY EXPRESSED TO ME IN EMAILS FROM THE
 OWNER, PROMPT RESPONSES TO THE ABOVE ISSUES WOULD BE
 VERY HELPFUL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-05-27 Cont ID  
Sent By ccole Date 2021-05-27 Time 17:52 Rev Time 0.00
Received By ccole Date 2021-05-27 Time 09:36 Sent To  
Notes
2021-05-27 17:53:092ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21020294
 5/27/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 NFPA 58
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW ARE MARKED OR FAILED. NOTES HAVE BEEN ADDED TO
 FAILED COMMENT FOR FURTHER CLARIFICATION.
  
 1) PASSED. SHEET P3.0, GAS NOTE 3: PLEASE UPDATE THE
 2017 FBC CODE REFERENCE TO THE FBC 2020 7TH EDITION
 FUEL GAS CODE.
  
 2) PASSED. P3.0, GAS ISO: LABEL THE LP TANK LOCATION-
 SECTION 107.2.1 WPB.
  
 3) FAILED. P2.0 P3.0: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE LP TANKS SHOWING THE TANKS ARE
 DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) IN
 ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58. CURRENTLY THE LP TANK AND
 SYSTEM UNDER PERMIT 21021293 ARE NOT UNDER REVIEW.
 PLEASE CONTACT [email protected].
  
 4) FAILED. P2.0 P3.0: PROVIDE LP TANK INSTALLATION
 DETAILS SHOWING THE REQUIRED MASONRY OR OTHER
 NON-COMBUSTIBLE STRUCTURAL SUPPORTS LOCATED ON CONCRETE
 OR MASONRY FOUNDATION WITH THE CONTAINER SUPPORTS-
 SECTION 6.6.3.1 NFPA 58. SHOW HOW THE TANK WILL BE
 ANCHORED TO RESIST WIND LOAD AND WIND PRESSURES-
 SECTION 6.6.3.3 (D) NFPA 58. CURRENTLY THE LP TANK AND
 SYSTEM UNDER PERMIT 21021293 ARE NOT UNDER REVIEW.
 PLEASE CONTACT [email protected].
  
 5) FAILED. P2.0 & P3.0: BASED ON GALLON SIZES OF THE
 TANKS, AND MANIFOLDING OF THE TANKS, PROVIDE CLEARANCE
 DISTANCES FOR THE TANK RELIEF VALVES TO THE REAR DOOR
 OPENING, MECHANICAL AIR INTAKES, DIRECT VENT SYSTEM,
 AND EXTERIOR SOURCES OF IGNITION- SECTIONS 6.4.4.3 &
 6.4.4.4 AND TABLE 6.4.4.3 NFPA 58. NOT PROVIDED.
  
 6) FAILED. P2.0 & P3.0: REFER TO SECTIONS 6.10.1.4 &
 6.10.2.1 NFPA AND SHOW COMPLIANCE ON THE PLAN: A
 TWO-STAGE REGULATOR SYSTEM, AN INTEGRAL TWO-STAGE
 REGULATOR OR A 2 PSI REGULATOR IS REQUIRED FOR THE
 SYSTEM BASED ON 11 IN. WC. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE REGULATOR. NOT PROVIDED.
  
 7) FAILED. P2.0 & P3.0: REFER TO SECTION 6.10.1.7 NFPA
 58 AND INDICATE THE REQUIRED CLEARANCES FOR REGULATOR
 PRESSURE RELIEF VENT DISCHARGES TO THE DOOR OPENING,
 MECHANICAL AIR INTAKES, DIRECT VENT SYSTEM, AND ANY
 SOURCE OF IGNITION. NOT PROVIDED.
  
 8) FAILED. P3.0: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE TANKLESS WATER HEATER AND THE CONCENTRIC VENT
 SYSTEM- SECTION 624.1 FBC FG. PLEASE NOTE THE SPECS MAY
 BE DEFERRED SUBMITTALS BY REQUEST- SECTION 107.3.4.1
 WPB. NOT PROVIDED.
  
 9) PASSED. P3.0: PROVIDE A CONDENSATE DISPOSAL PLAN FOR
 THE WATER HEATER- SECTIONS 307.2- 307.6 FBC FG. PLEASE
 NOTE THE MANUFACTURER'S SPECIFICATIONS MAY RECOMMEND
 INSTALLATION OF AN ACID NEUTRALIZING DEVICE FOR THE
 CONDENSATE.
  
 10) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS-FIRED PROBAT L12 AND THE DIEDRICH IR-1-
 SECTION- 305.1 FBC FG. THE SPECS MAY BE DEFERRED
 SUBMITTALS BY REQUEST- SECTION 107.3.4.1 WPB.THE
 DIEDRICH SPECS NOT PROVIDED.
  
 11) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 PROBAT L12 AND DIEDRICH IR-1 AND INDICATE HOW THE
 COMBUSTION AIR WILL BE PROVIDED- SECTION 304.1 FBC FG.
 NOT PROVIDED ON P2 OR M3.1. IF PROVIDING COMBUSTION AIR
 MECHANICALLY PLEASE REFER TO SECTION 304.9 FBC FG AND
 PROVIDE THE CALCULATION.
  
 12) FAILED. PROVIDE VENTING DIAGRAMS AND SPECIFICATIONS
 FOR THE PROBAT L12 AND DIEDRICH IR-1- SECTIONS 305.1
 AND 503.1 FBC FG. THE VENTING DIAGRAM ON M2 IS
 INCOMPLETE. REFER TO SECTION 202 AND TABLE 503.4 AND
 SPECIFY THE TYPE OF VENT SYSTEM BASED ON THE CATEGORY
 OF THE APPLIANCES- CATEGORY I, II, III, OR IV. THE
 SUBMITTED SPECS FOR THE PROBAT INDICATES A 6- 8 INCH
 EXHAUST DUCT. PLEASE PROVIDE AN ENLARGED ELEVATION VIEW
 SHOWING THE VERTICAL EXHAUST DUCTS FROM EACH APPLIANCE
 AND HOW THEY ARE CONNECTING INTO THE 18 INCH HORIZONTAL
 DUCT. PLEASE CLARIFY HOW THE 18 INCH DUCT WAS SIZED AND
 PROVIDE DUCT MATERIAL SPECIFICATIONS. IS THE DUCT
 REQUIRED TO SLOPE? PLEASE REVIEW SECTIONS 503.6.9.1-
 503.7.9 AND PROVIDE COMPLETE DETAILS INCLDUDING HOW THE
 DUCT IS TO BE SUPPORTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By ccole Date 2021-04-07 Time 12:00 Rev Time 0.00
Received By ccole Date 2021-03-11 Time 17:08 Sent To  
Notes
2021-04-07 12:00:251ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21020294
 3/11/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 NFPA 58
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P3.0, GAS NOTE 3: PLEASE UPDATE THE 2017 FBC
 CODE REFERENCE TO THE FBC 2020 7TH EDITION FUEL GAS
 CODE.
 2) P3.0, GAS ISO: LABEL THE LP TANK LOCATION- SECTION
 107.2.1 WPB.
  
 3) P2.0 P3.0: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE LP TANKS SHOWING THE TANKS ARE DESIGNED,
 FABRICATED, TESTED AND MARKED (STAMPED) IN ACCORDANCE
 WITH THE REGULATIONS AS REQUIRED BY THE REGULATORY
 AGENCIES AND COMPLIANCE STANDARDS LISTED IN SECTION
 5.2.1.1 NFPA 58.
  
 4) P2.0 P3.0: PROVIDE LP TANK INSTALLATION DETAILS
 SHOWING THE REQUIRED MASONRY OR OTHER NON-COMBUSTIBLE
 STRUCTURAL SUPPORTS LOCATED ON CONCRETE OR MASONRY
 FOUNDATION WITH THE CONTAINER SUPPORTS- SECTION 6.6.3.1
 NFPA 58. SHOW HOW THE TANK WILL BE ANCHORED TO RESIST
 WIND LOAD AND WIND PRESSURES- SECTION 6.6.3.3 (D) NFPA
 58.
  
 5) P2.0 & P3.0: BASED ON GALLON SIZES OF THE TANKS, AND
 MANIFOLDING OF THE TANKS, PROVIDE CLEARANCE DISTANCES
 FOR THE TANK RELIEF VALVES TO THE REAR DOOR OPENING,
 MECHANICAL AIR INTAKES, DIRECT VENT SYSTEM, AND
 EXTERIOR SOURCES OF IGNITION- SECTIONS 6.4.4.3 &
 6.4.4.4 AND TABLE 6.4.4.3 NFPA 58.
  
 6) P2.0 & P3.0: REFER TO SECTIONS 6.10.1.4 & 6.10.2.1
 NFPA AND SHOW COMPLIANCE ON THE PLAN: A TWO-STAGE
 REGULATOR SYSTEM, AN INTEGRAL TWO-STAGE REGULATOR OR A
 2 PSI REGULATOR IS REQUIRED FOR THE SYSTEM BASED ON 11
 IN. WC. PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE REGULATOR.
  
 7) P2.0 & P3.0: REFER TO SECTION 6.10.1.7 NFPA 58 AND
 INDICATE THE REQUIRED CLEARANCES FOR REGULATOR PRESSURE
 RELIEF VENT DISCHARGES TO THE DOOR OPENING, MECHANICAL
 AIR INTAKES, DIRECT VENT SYSTEM, AND ANY SOURCE OF
 IGNITION.
  
 8) P3.0: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER AND THE CONCENTRIC VENT SYSTEM-
 SECTION 624.1 FBC FG. PLEASE NOTE THE SPECS MAY BE
 DEFERRED SUBMITTALS BY REQUEST- SECTION 107.3.4.1 WPB.
  
 9) P3.0: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 WATER HEATER- SECTIONS 307.2- 307.6 FBC FG. PLEASE NOTE
 THE MANUFACTURER?S SPECIFICATIONS MAY RECOMMEND
 INSTALLATION OF AN ACID NEUTRALIZING DEVICE FOR THE
 CONDENSATE.
  
 10) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 GAS-FIRED PROBAT L12 AND THE DIEDRICH IR-1- SECTION-
 305.1 FBC FG. THE SPECS MAY BE DEFERRED SUBMITTALS BY
 REQUEST- SECTION 107.3.4.1 WPB.
  
 11) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE PROBAT
 L12 AND DIEDRICH IR-1 AND INDICATE HOW THE COMBUSTION
 AIR WILL BE PROVIDED- SECTION 304.1 FBC FG.
  
 12) PROVIDE VENTING DIAGRAMS AND SPECIFICATIONS FOR THE
 PROBAT L12 AND DIEDRICH IR-1- SECTIONS 305.1 AND 503.1
 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-08-11 Cont ID  
Sent By medwards Date 2021-08-11 Time 14:47 Rev Time 0.00
Received By medwards Date 2021-08-05 Time 16:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-08-05 Cont ID  
Sent By medwards Date 2021-08-05 Time 13:41 Rev Time 0.00
Received By medwards Date 2021-07-30 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-07-28 Time   Rev Time 0.00
Received By aoliver Date 2021-07-12 Time 10:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-28 Cont ID  
Sent By shill Date 2021-05-28 Time 13:20 Rev Time 0.00
Received By shill Date 2021-05-07 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-04-07 Time   Rev Time 0.00
Received By lmarchan Date 2021-02-08 Time 09:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-08-11 Cont ID  
Sent By medwards Date 2021-08-11 Time 14:34 Rev Time 0.00
Received By medwards Date 2021-08-11 Time 14:34 Sent To  
Notes
2021-08-11 14:38:19THE MECHANICAL SYSTEM FOR THIS TENANT SPACE IS
 APPROVED. THERE IS A PRIVISO ON THE FUEL GAS FOR THE
 INSTALLATION OF ALL ROASTERS. THERE WILL BE A SEPARATE
 APPLICATION, PERMIT AND PLAN REVIEW FOR THE
 INSTALLATION OF THE ROASTERS AND THE EXHAUST. NO REVIEW
 ON THIS PERMIT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-08-05 Cont ID  
Sent By medwards Date 2021-08-05 Time 13:38 Rev Time 0.00
Received By medwards Date 2021-08-03 Time 12:54 Sent To  
Notes
2021-08-05 13:40:584TH REVIEW FBC-2020 MECHANICAL
 PERMIT-21020294
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ON 07/28/2021 MR. CIARLARIELLO SENT AN EMAIL WITH
 THE CORRECTED OCCUPANCY CLASSIFICATIONS OF EACH SPACE
 FOR THE OUTDOOR AIR CALCULATIONS. THIS NEW INFORMATION
 WAS NOT SUBMITTED IN THIS CYCLE OF REVIEWS. PLEASE
 UPDATE THE OUTDOOR AIR CALCULATIONS WITH THE CORRECTED
 OCCUPANCY CLASSIFICATIONS. PLEASE NOTE THAT AHU-3 IS A
 FUTURE UNIT SO IT WILL NOT BE COUNTED AT THIS REVIEW.
 THE NEW INFORMATION ABOUT THE MULTIPURPOSE ASSEMBLY IS
 FOR AN AREA IN THE OPEN AREA OF THE TENANT SPACE. I DO
 NOT SEE THAT YOU CAN ONLY CLASSIFY THIS PART AS A
 DIFFERENT OCCUPANCY WITHOUT WALLS BEING IN PLACE TO
 CLEARLY SEPARATE THE AREAS. THE ENTIRE UPPER AREA WOULD
 NEED TO BE CLASSIFIED AS MULTIPURPOSE ASSEMBLY. PLEASE
 EXPLAIN THE USE OF THIS MULTIPURPOSE ASSEMBLY. IS THIS
 GOING TO BE A FUTURE RESTAURANT? IS THIS AREA GOING TO
 HAVE LIVE MUSIC AND DANCING? WHAT IS THE USE OF THIS
 SPACE. RBC 107.2.1
  
 3) THIS HAS BEEN ASKED FOR IN PREVIOUS REVIEWS. PLEASE
 PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS THAT
 MATCH THE 5-TON UNITS ON THE DRAWINGS. FBC 107.2.1
  
 4) COMMENT 8 OF MY PREVIOUS COMMENTS WERE NOT ANSWERED:
 PLEASE PROVIDE THE INSTALLATION INSTRUCTIONS FOR EACH
 OF THE ROASTERS. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2021-08-04 15:42:22 
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-07-28 Cont ID  
Sent By medwards Date 2021-07-28 Time 14:25 Rev Time 0.00
Received By medwards Date 2021-07-28 Time 14:25 Sent To  
Notes
2021-07-28 14:27:033RD REVIEW FBC-2020 MECHANICAL
 PERMIT-21020294
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE UNDERSTAND THAT THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS AND THE EQUIPMENT TABLE ON SHEET
 M4.0 MUST MATCH. FBC 107.2.1, FBC EC C403.2.1
  
 2) IF AHU-3 IS NOT TO BE INSTALLED AT THIS TIME UNDER
 THIS PERMIT THEN IT MUST BE REMOVED FROM THIS PROJECT
 DOCUMENTS. FBC 107.2.1
  
 3) THE TABLES ON M3.1 ARE IDENTIFIED AS ASHRAE 62.1
 PRESSURIZATION CALCULATION, PLEASE IDENTIFY THESE AS
 MINIMUM VENTILATION RATES IN BREATHING ZONE AS THEY ARE
 TITLE IN THE REFERENCE. PLEASE ALSO LABEL THE SPACE
 NAMES ACCORDING TO THE MINIMUM VENTILATION TABLES SO I
 CAN CORRECTLY COMPARE YOUR CALCULATIONS TO THE TABLE
 USED. FBC 107.2.1 PLEASE REMEMBER THAT IF UNIT 3 IS NOT
 INSTALLED UNDER THIS PERMIT IT WILL NOT BE COUNTED IN
 THE OUTDOOR AIR CALCULATIONS.
  
 4) I DO NOT SEE A RESPONSE TO COMMENT (7) OF PREVIOUS
 CYCLE: PLEASE PROVIDE THE MANUFACTURING PROCESS IN THIS
 FACILITY. FBC 107.2.1
  
 5) I DO NOT SEE A RESPONSE TO COMMENT (8) OF PREVIOUS
 CYCLE: PLEASE PROVIDE THE EQUIPMENT SPECIFICATION
 SHEETS. FBC 107.2.1
  
 6) I DO NOT SEE A RESPONSE TO COMMENT (9) OF PREVIOUS
 CYCLE: PLEASE LIST ALL MATERIALS TO BE STORED IN THIS
 FACILITY AND THEIR QUANTITIES. FBC 107.2.1
  
 7) I DO NOT SEE A RESPONSE TO COMMENT (10) OF PREVIOUS
 CYCLE: WHAT IS THE OCCUPANCY ABOVE THE TENANT SPACE?
  
 8) THE COFFEE ROASTER MANUFACTURER MUST PROVIDE
 INSTALLATION INSTRUCTIONS FOR THE EXHAUST DUCT SYSTEM
 FOR THE ROASTERS. FBC FG TABLE 503.4
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-05-27 Cont ID  
Sent By medwards Date 2021-05-27 Time 07:53 Rev Time 0.00
Received By medwards Date 2021-05-26 Time 17:28 Sent To  
Notes
2021-05-27 07:53:321ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020294
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE TO SHEET M2.0 STATING THAT THE
 WALK-IN COOLER WILL NEED TO BE SUBMITTED AS A SEPARATE
 PERMIT AND PLAN REVIEW.
  
 2) SHEET M2.0: AHU-1 IS SUPPLYING AIR INTO THE EXIT
 PASSAGEWAY, PLEASE REMOVE THIS AS IT IS NOT ALLOWED.
 FBC 1024.7
  
 3) SHEET M4.0: AIR HANDLING UNIT SCHEDULE IDENTIFIES
 WHAT AREAS EACH UNIT SERVICES, PLEASE IDENTIFY EACH OF
 THESE AREAS ON SHEET M2.0. FBC 107.2
  
 4) PLEASE REMOVE ALL FUTURE EQUIPMENT AS THIS REVIEW IS
 ONLY FOR WHAT WILL BE INSTALLED AT THE TIME OF THE C.O.
  
 5) THE EQUIPMENT SIZING CALCULATIONS AND THE AHU UNITS
 LISTED ON SHEET M4.0 DO NOT MATCH. PROVIDE CONSISTENT
 DOCUMENTS. FBC 107.2.1
  
 6) PLEASE PROVIDE CONDENSATION DRAIN LINE TERMINATION
 THAT MEETS FBC M 307.2.1
 CONDENSATE SHALL NOT DISCHARGE INTO A STREET, ALLEY OR
 OTHER AREAS SO AS TO CAUSE A NUISANCE.
  
 7) PLEASE PROVIDE THE MANUFACTURING PROCESS IN THIS
 FACILITY. FBC 107.2.1
  
 8) PLEASE PROVIDE THE EQUIPMENT SPECIFICATION SHEETS
 FOR ALL EQUIPMENT. FBC 107.2.1
  
 9) PLEASE LIST ALL MATERIALS TO BE STORED IN THIS
 FACILITY AND THEIR QUANTITIES. FBC 107.2.1
  
 10) WHAT IS THE OCCUPANCY ABOVE THIS TENANT SPACE?
  
 11) PLEASE EXPLAIN WHAT THE 18? EXHAUST DUCT?S INTENDED
 USE IS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By medwards Date 2021-03-08 Time 09:52 Rev Time 0.00
Received By medwards Date 2021-03-08 Time 09:25 Sent To  
Notes
2021-03-08 09:52:271ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020294
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE BUILDING REVIEWERS COMMENTS. UNTIL HIS
 COMMENTS ARE ADDRESSED ABOUT CHANGE OF USE, OCCUPANCY
 CLASSIFICATION OF ALL SPACES I CANNOT DO A REVIEW.
 PLEASE MAKE SURE TO ADDRESS EACH USE OF SPACE PER THE
 UPDATED ARCHITECTURAL SHEETS BEFORE RESUBMITTING ANY
 CHANGES TO THE MECHANICAL DOCUMENTS.
  
 2) THE ENERGY CALCULATIONS AND THE MECHANICAL SIZING
 CALCULATIONS ARE FOR A PUMPHOUSE BREWERY, THE DRAWINGS
 ARE FOR A PUMPHOUSE COFFEE ROASTERS. PLEASE PROVIDE
 ENERGY AND MECHANICAL SIZING CALCS FOR THE PUMPHOUSE
 COFFEE ROASTERS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status N Date 2021-07-19 Cont ID  
Sent By jwitmer Date 2021-07-19 Time 14:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-07-19 14:58:43WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW/ NFIP
 W. P. B. PERMIT:21020294
 ADD: 1016 CLARE UNIT: 4 BUILT IN 1946- PRE-FIRM
 CONT: PERK CONSTRUCTION INC. / U-21885
 TEL: 561-401-5984
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JULY 19TH/ 2021
 ACTION: PASSED
 NFIP. BUILDING BUILT IN 1946. PRE-FIRM / NOT
 SUBSTANTIAL IMPROVEMENT.
 UNIT 4 IMPROVEMENT VALUE PALM BEACH COUNTY PROPERTY
 APPRAISER OFFICE VALUE $1,937,948.00 VALUE.
 UNIT 4 IMPROVEMENT VALUE THIS PERMIT ($125,000.00) AND
 PERMIT VALUE IS INCLUDED IN THE LAST 5 YEARS $
 243,054.00 / NOT A SUBSTANTIAL IMPROVEMENT.
 NAVD 88 BFE 12.1 FEET.
 BUILDING SURVEY UNIT 6 FINISH FLOOR 16.19? NAVD88.
 SHEET S-1. VOLUNTEERING TO DRY-FLOOD PROOF. THE OLD
 TRUCK LOADING AREA LOWER FLOOR TO DRY FLOOD PROOF AND
 INSTALL FLOOD BARRIER DESIGNED TO CONFIRM WITH ASCE 24
 AND FEMA TECHNICAL BULLETIN 3-93.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-05-28 Cont ID  
Sent By shill Date 2021-05-28 Time 13:19 Rev Time 0.00
Received By shill Date 2021-05-28 Time 13:19 Sent To  
Notes
2021-05-28 13:20:05SEE BUILDING REVIEW
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-08-09 Cont ID  
Sent By ccole Date 2021-08-09 Time 10:37 Rev Time 0.00
Received By ccole Date 2021-08-09 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-08-04 Cont ID  
Sent By ccole Date 2021-08-04 Time 10:30 Rev Time 0.00
Received By ccole Date 2021-08-04 Time 07:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-07-27 Cont ID  
Sent By ccole Date 2021-07-27 Time 12:50 Rev Time 0.00
Received By ccole Date 2021-07-23 Time 14:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-05-27 Cont ID  
Sent By ccole Date 2021-05-27 Time 16:50 Rev Time 0.00
Received By ccole Date 2021-05-27 Time 09:36 Sent To  
Notes
2021-05-27 16:50:302ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21020294
 5/27/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW ARE MARKED OR FAILED. NOTES HAVE BEEN ADDED TO
 FAILED COMMENT FOR FURTHER CLARIFICATION.
  
 1) PASSED. SHEET G1.0: PLEASE UPDATE THE APPLICABLE
 CODES TO THE FBC 2020 7TH EDITION.
  
 2) SHEETS A1.0 & A1.1: ACCESSIBILITY CORRECTIONS- FBC
 ACC.
  
 A) PASSED. THE TOILET COMPARTMENT SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY- SECTION
 603.2.3.
 B) FAILED. GRAB BAR NOT POSITIONED ACCORDING TO
 SECTIONS AND FIGURES 604.5.1 & 604.5.2. SHEET A1: THE
 SIDE GRAB BAR SHALL EXTEND A MINIMUM OF 54 INCHES FROM
 THE WALL. SHEET A1.1: REAR GRAB BAR NOT CENTERED
 PROPERLY.
 C) PASSED. CENTERLINE OF THE TOILET PAPER DISPENSER
 MEASURED FROM THE FRONTS OF THE WATER CLOSET NOT SHOWN-
 SECTION 604.7.
 D) PASSED. HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR
 TO THE REFLECTIVE SURFACE NOT SHOWN- SECTION 603.3.
 3) PASSED. A1.1: SHOW THE DEPTH OF THE WOMEN'S TOILET
 COMPARTMENTS- SECTION 405.3.1 FBC P.
  
 4) PASSED. LSP: THE OCCUPANT LOAD AND PLUMBING FIXTURE
 CALCULATIONS TABLE DO NOT INCLUDE THE LOAD FROM THE 2ND
 FLOOR- TABLE 403.1 FBC P.
  
 5) FAILED. P2.0 & P3.0: A GREASE INTERCEPTOR IS
 REQUIRED TO RECEIVE THE DRAINAGE FROM THE FIXTURES IN
 THE RETAIL BAR, COFFEE BREWING, ROASTING, AND UTILITY
 AREAS. FIXTURES REQUIRED TO DRAIN INTO THE INTERCEPTOR
 INCLUDE THE 3-COMPARTMENT SINKS, DISHWASHER, FLOOR
 SINKS, AND TRENCH DRAIN. PLEASE REVISE THE DRAWINGS AND
 DETAILS TO SHOW COMPLIANCE- SECTION 1003.3.1 FBC P. A)
 PROVIDE GREASE WASTE CALCULATIONS IN ACCORDANCE WITH
 SECTIONS 1003.3.5 OR 1003.3.7 FBC P. SHEET P2: THE
 HANDSINK IS NOT ALLOWED TO DRAIN INTO THE GREASE
 INTERCEPTOR- SECTION 1003.3.1 FBC P. A) SHEET P5.0: THE
 SIZING CALCULATIONS ARE FOR A RESTAURANT AND NOT
 APLLICABLE TO THE PROPOSED OCCUPANCY. PLEASE PROVIDE
 CALCULATIONS IN ACCORDANCE WITH SECTION 1003.3.5 FBC P.
  
 6) PASSED. P2.0- NOTE 16, & P3.0: A SEPARATE PERMIT IS
 REQUIRED FOR THE NEW BACKFLOW PREVENTER. PLEASE NOTE- A
 FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 7) FAILED. P2.0 & P3.0: PLEASE SHOW THE LOCATIONS OF
 AND PROVIDE EQUIPMENT SCHEDULES FOR REQUIRED THE
 BACKFLOW PREVENTERS FOR WATER LINES SUPPLYING THE
 PUMPHOUSE EQUIPMENT IN THE RETAIL BAR, AND COFFEE
 BREWING AREAS- SECTION 608.3 FBC P. THE BF PREVENTERS
 SHALL BE LOCATED ON THE INDIVIDUAL BRANCH LINES
 SUPPLYING EACH FIXTURE OR APPLIANCE IN ACCORDANCE WITH
 608.3. KEYNOTE 19 SHOWS THE BF PREVENTERS ON THE MAIN
 LINES SUPPLYING THE GROUPED FIXTRURES AND APPLIANCES.
 PLEASE NOTE NO BF PREVENTERS ARE SHOWN FOR THE
 DISHWASHER AND ICE MACHINE- #32 & #33. THE DESIGN
 PROFESSIONAL WANT TO PROVIDE A GENERAL KEYNOTE FOR
 REQUIRED INDIVIDUAL BF PREVENTERS SAND PLACE THAST NOTE
 AL ALL LOCATIONS.
  
 8) PASSED. P2.0 & P3.0: PLEASE INCLUDE THE FLOOR SINKS
 AND THE TRENCH DRAIN IN THE FIXTURE SCHEDULE- SECTION
 413 FBC P.
  
 9) PASSED. P2.0 & P3.0: PLEASE INCLUDE THE WALL HYDRANT
 AND HOSE BIBS IN THE FIXTURE SCHEDULE- SECTIONS 412.6
 AND 608.16.4.2 FBC P.
  
 10) FAILED. P2.0 & P3.0 INDICATE HOW TEMPERED WATER
 WILL BE PROVIDED TO THE LAVATORIES- SEE SECTIONS 419.5
 & 607.2.1 FBC P. MIXING VALVE AT LAVATORIES NOT
 PROVIDED .
  
 11) PASSED. P2.0 & P3.0: SHOW THE 2-WAY CLEANOUT IN THE
 SANITARY RISER- SECTION 708.1.3 FBC P.
  
 12) FAILED. P4.0: PROVIDE AN INDIRECT WASTE DETAIL FOR
 THE 3-COMPARTMENT SINKS- SECTION 802.1.1 FBC P. NOT
 PROVIDED.
  
 13) PASSED. P4.0: PROVIDE A WATER HEATER PLUMBING
 PIPING DIAGRAM SHOWING CW, HW, & HWR CONNECTIONS,
 LOCATIONS OF CHECK VALVES, RECIRCULATION PUMP,
 EXPANSION TANK, RELIEF VALVE, DRAIN PAN AND PAN LINE-
 SECTION- 501 FBC P.
  
 14) PASSED. P4.0: PROVIDE EQUIPMENT SCHEDULES FOR THE
 WATER HEATER, AND EXPANSION TANK- SECTIONS 501 & 607
 FBC P.
  
 15) FAILED. PROVIDE A CIVIL OR SITE PLAN SHOWING THE
 POINTS OF CONNECTIONS TO THE MAIN WATER SERVICE AND
 SEWER PIPES- SECTION 107.2.1 WPB. NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-11 Cont ID  
Sent By ccole Date 2021-03-11 Time 18:19 Rev Time 0.00
Received By ccole Date 2021-03-11 Time 14:00 Sent To  
Notes
2021-03-11 18:19:401ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21020294
 3/11/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G1.0: PLEASE UPDATE THE APPLICABLE CODES TO
 THE FBC 2020 7TH EDITION.
  
 2) SHEETS A1.0 & A1.1: ACCESSIBILITY CORRECTIONS- FBC
 ACC.
  
 A) THE TOILET COMPARTMENT SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY- SECTION 603.2.3.
  
 B) GRAB BAR NOT POSITIONED ACCORDING TO SECTIONS AND
 FIGURES 604.5.1 & 604.5.2.
  
 C) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSET NOT SHOWN- SECTION
 604.7.
  
 D) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE NOT SHOWN- SECTION 603.3.
  
 3) A1.1: SHOW THE DEPTH OF THE WOMEN'S TOILET
 COMPARTMENTS- SECTION 405.3.1 FBC P.
  
 4) LSP: THE OCCUPANT LOAD AND PLUMBING FIXTURE
 CALCULATIONS TABLE DO NOT INCLUDE THE LOAD FROM THE 2ND
 FLOOR- TABLE 403.1 FBC P.
  
 5) P2.0 & P3.0: A GREASE INTERCEPTOR IS REQUIRED TO
 RECEIVE THE DRAINAGE FROM THE FIXTURES IN THE RETAIL
 BAR, COFFEE BREWING, ROASTING, AND UTILITY AREAS.
 FIXTURES REQUIRED TO DRAIN INTO THE INTERCEPTOR INCLUDE
 THE 3-COMPARTMENT SINKS, DISHWASHER, FLOOR SINKS, AND
 TRENCH DRAIN. PLEASE REVISE THE DRAWINGS AND DETAILS TO
 SHOW COMPLIANCE- SECTION 1003.3.1 FBC P. A) PROVIDE
 GREASE WASTE CALCULATIONS IN ACCORDANCE WITH SECTIONS
 1003.3.5 OR 1003.3.7 FBC P.
  
 6) P2.0- NOTE 16, & P3.0: A SEPARATE PERMIT IS REQUIRED
 FOR THE NEW BACKFLOW PREVENTER. PLEASE NOTE- A FL.
 LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE
 PERMIT FOR INSTALLATION OF THE BACKFLOW PREVENTER IN
 ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB
 CODE OF ORDINANCES. THE DEVICE SHALL BE TESTED AND
 CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO
 FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE
 CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT
 561-822-2210 FOR FURTHER INFORMATION.
  
 7) P2.0 & P3.0: PLEASE SHOW THE LOCATIONS OF AND
 PROVIDE EQUIPMENT SCHEDULES FOR REQUIRED THE BACKFLOW
 PREVENTERS FOR WATER LINES SUPPLYING THE PUMPHOUSE
 EQUIPMENT IN THE RETAIL BAR, AND COFFEE BREWING AREAS-
 SECTION 608.3 FBC P.
  
 8) P2.0 & P3.0: PLEASE INCLUDE THE FLOOR SINKS AND THE
 TRENCH DRAIN IN THE FIXTURE SCHEDULE- SECTION 413 FBC
 P.
  
 9) P2.0 & P3.0: PLEASE INCLUDE THE WALL HYDRANT AND
 HOSE BIBS IN THE FIXTURE SCHEDULE- SECTIONS 412.6 AND
 608.16.4.2 FBC P.
  
 10) P2.0 & P3.0 INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES- SEE SECTIONS 419.5 &
 607.2.1 FBC P.
  
 11) P2.0 & P3.0: SHOW THE 2-WAY CLEANOUT IN THE
 SANITARY RISER- SECTION 708.1.3 FBC P.
  
 12) P4.0: PROVIDE AN INDIRECT WASTE DETAIL FOR THE
 3-COMPARTMENT SINKS- SECTION 802.1.1 FBC P.
  
 13) P4.0: PROVIDE A WATER HEATER PLUMBING PIPING
 DIAGRAM SHOWING CW, HW, & HWR CONNECTIONS, LOCATIONS OF
 CHECK VALVES, RECIRCULATION PUMP, EXPANSION TANK,
 RELIEF VALVE, DRAIN PAN AND PAN LINE- SECTION- 501 FBC
 P.
  
 14) P4.0: PROVIDE EQUIPMENT SCHEDULES FOR THE WATER
 HEATER, AND EXPANSION TANK- SECTIONS 501 & 607 FBC P.
  
 15) PROVIDE A CIVIL OR SITE PLAN SHOWING THE POINTS OF
 CONNECTIONS TO THE MAIN WATER SERVICE AND SEWER PIPES-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-08-11 Cont ID  
Sent By medwards Date 2021-08-11 Time 16:31 Rev Time 0.00
Received By medwards Date 2021-08-11 Time 16:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-08-11 Cont ID  
Sent By medwards Date 2021-08-11 Time 14:45 Rev Time 0.00
Received By medwards Date 2021-08-11 Time 14:45 Sent To  
Notes
2021-08-11 14:47:40SHEET M3.1 WAS SUBMITTED DIGITALLY WITH THE DESIGNERS
 STAMP AND SIGNATURE. DOCUMENTS SUBMITTED DIGITALLY
 SHOULD HAVE AN ORIGINAL DIGITAL SEAL FROM THE DESIGNER.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-27 Cont ID  
Sent By ccole Date 2021-07-27 Time 12:57 Rev Time 0.00
Received By ccole Date 2021-07-27 Time 12:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-27 Cont ID  
Sent By medwards Date 2021-05-27 Time 08:01 Rev Time 0.00
Received By medwards Date 2021-05-27 Time 08:01 Sent To  
Notes
2021-05-27 08:02:49FILES DATED 02/16/2021 STILL NEED TO HAVE A DIGITALLY
 SIGNED ORIGINAL UPLOADED AS THE ONES SUBMITTED ARE A
 COPY OF A DIGITAL SIGNATURE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By medwards Date 2021-03-08 Time 10:29 Rev Time 0.00
Received By medwards Date 2021-03-08 Time 10:29 Sent To  
Notes
2021-03-08 10:34:28THE DOCUMENTS SUBMITTED APPEAR TO BE COPIES OF THE
 ORIGINAL DIGITALLY SIGNED AND SEALED DOCUMENTS. WE
 CANNOT ACCEPT COPIES OF A DIGITAL SIGNATURE. PLEASE
 UPLOAD THE ORIGINAL DIGITALLY SIGNED AND SEALED
 DOCUMENTS. AS AN ALTERNATIVE YOU CAN BRING ORIGINAL
 SIGNED AND SEALED PAPER DOCUMENTS TO OUR OFFICE.
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-04-06 Cont ID  
Sent By kalexand Date 2021-04-06 Time 13:46 Rev Time 0.00
Received By kalexand Date 2021-04-06 Time 13:45 Sent To I
Notes
***NONE***