Plan Review Details - Permit 21020258
Plan Review Stops For Permit 21020258
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-14 Cont ID  
Sent By cthroop Date 2022-03-14 Time 13:07 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 05:47 Sent To  
Notes
2022-03-14 13:23:53BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: INSUFICIENT INFORMATION PROVIDED FOR A
 COMPREHENSIVE REVIEW. PLEASE REFERENCE THE BELOW
 CHECKLIST.
  
 RESIDENTIAL SITE BUILT STRUCTURES. (NEW AND ADDITIONS)
  
 CHECKLIST
  
 EVERY STRUCTURE SUBJECT TO WIND LOADS SHALL BE DESIGNED
 PER FBC RES CHPT 3 OR THE FBC BLDG. CHPT. 16 AND ASCE
 7-16.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 EXCEPTION; SHEDS AND ACCESSORY STRUCTURES
 R301.2.1.2 PROTECTION OF OPENINGS.
 STRUCTURES THAT ARE NOT DESIGNED FOR HUMAN HABITATION
 AND THAT HAVE A FLOOR AREA OF 720 SQUARE FEET (67 M2)
 OR LESS ARE NOT REQUIRED TO COMPLY WITH THE MANDATORY
 WIND-BORNE DEBRIS IMPACT STANDARD OF THIS CODE.
  
 1. PROVIDE A SITE PLAN....
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE
 AND INCLUDED BOUNDARY LINE SURVEY.
  
 2. PROVIDE THE FOLLOWING BUILDING PLANS
  
 2A) PROVIDE A FOUNDATION PLAN FOOTINGS/SLAB ON
 GRADE/REINFORCING/TIE DOWNS.
 2B) PROVIDE REQUIRED DIMENSIONS.
 2C) PROVIDE A FLOOR PLAN WITH FLOOR TO FOUNDATION
 CONNECTION DETAIL, INCLUDE CONNECTOR TYPE AND
 FASTENERS.
 2D) PROVIDE A WALL PLAN (SECTION VIEW) WITH WALL TO
 FLOOR CONNECTION DETAIL, INCLUDE CONNECTOR TYPE AND
 FASTENERS.
 2E) PROVIDE A ROOF FRAMING PLAN WITH ROOF TO WALL
 CONNECTION DETAIL, INCLUDE CONNECTOR TYPE AND
 FASTENERS.
 2F) PROVIDE A WINDOW AND/OR DOOR SCHEDULE WITH ROUGH
 OPENINGS AND DESIGN WIND LOADS. (COORDINATE SCHEDULE
 WITH OPENINGS ON FLOOR PLAN).
 2G) PROVIDE PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS,
 DOORS, AND TIE DOWNS. >720 SQ. FT. SEE R301.2.1.2
 2H) ELECTRICAL PROVIDE AN ELECTRICAL PLAN. ELECTRIC
 SUB-PERMIT REQUIRED.
 2I) MECHANICAL PROVIDE A MECHANICAL PLAN. MECHANICAL
 SUB-PERMIT REQUIRED.
 2J) PLUMBING PROVIDE A PLUMBING PLAN. PLUMBING
 SUB-PERMIT REQUIRED.
 2K) ROOFING PROVIDE A ROOF PLAN. ROOFING SUB-PERMIT
 REQUIRED.
  
 3. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 4. PROVIDE A SOILS REPORT; FOR PROPERTIES LOCATED IN
 AREAS OF QUESTIONABLE SOILS, PER CITY SOILS MAP.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOILS CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 5. PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  
 6. PROVIDE AN ENERGY SUBMITTAL; RESIDENTIAL (RE)
 R401.2COMPLIANCE.
 PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. 1.SECTIONS R401 THROUGH R404.
 2. 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED; MANDATORY.
  
 7. SIGNATURE REQUIREMENT; DESINER, (O/B, CONTRACTOR OR
 DESIGN PROFESSIONAL) SHALL PRINT THEIR NAME AND SIGN
 EACH PLAN SHEET.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-13 Cont ID  
Sent By fgiaquin Date 2022-01-13 Time 19:10 Rev Time 0.00
Received By fgiaquin Date 2022-01-13 Time 18:19 Sent To  
Notes
2022-01-13 19:10:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLEASE PROVIDE ELECTRICAL PLAN FOR REVIEW.
 ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-14 Cont ID  
Sent By cthroop Date 2022-03-14 Time 13:33 Rev Time 0.00
Received By cthroop Date 2021-12-10 Time 14:21 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-03-14 Cont ID  
Sent By cthroop Date 2022-03-14 Time 11:02 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 11:01 Sent To  
Notes
2022-03-14 11:02:55PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-13 Cont ID  
Sent By medwards Date 2021-12-13 Time 11:10 Rev Time 0.00
Received By medwards Date 2021-12-13 Time 11:10 Sent To  
Notes
2021-12-13 11:19:41PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL
 DESIGN. IS THE TOILET IN A ROOM WITH A DOOR BY ITSELF?
 IS THIS ROOM GOING TO BE VENTILATED WITH NATURAL
 VENTILATION FBC RES R303.3, AND M1507. IS THIS ADDING
 SQUARE FOOTAGE TO THE HOUSE OR BEING BUILT INSIDE
 EXISTING SQUARE FOOTAGE? FBC 107.2.1
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-29 Cont ID  
Sent By ccole Date 2021-12-29 Time 13:52 Rev Time 0.00
Received By ccole Date 2021-12-29 Time 12:51 Sent To  
Notes
2021-12-29 13:53:301ST REVIEW FBC-2020 RES.
 PERMIT- 21020258
 12/29/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SANITARY DRAINAGE AND VENT ISOMETRIC
 DRAWING FOR THE NEW BATHROOM- SEC. 107.3.5.3 WPB.
 PLEASE INCLUDE THE POINT OF CONNECTION TO THE EXISTING
 SANITARY DRAIN OR SEWER LINE.
  
 2) THE FIXTURE LAYOUT IN THE BATHROOM INDICATES THERE
 WILL NOT BE ADEQUATE SPACE TO INSTALL THE TOILET AND
 LAVATORY (CALLED FACE BASIN IN THE DRAWING). A BATHTUB
 IS TYPICALLY 5'0" IN LENGTH AND THE ROOM IS ONLY 6'8"
 IN LENGTH- SEE SEC. R307.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-03-14 Cont ID  
Sent By cthroop Date 2022-03-14 Time 11:03 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 05:47 Sent To  
Notes
2022-03-14 11:05:28ROOFING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 2. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER
 BARRIER PER FBC R905.1.1.
 UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL
 CONFORM TO THE APPLICABLE STANDARDS? AND SHALL BE
 APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION
 R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE.
  
 3. PROVIDE PRODUCT APPROVALS FOR ROOF COVERINGS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-03-14 Cont ID  
Sent By cthroop Date 2022-03-14 Time 11:05 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 05:47 Sent To  
Notes
2022-03-14 11:06:27PLANS SUBMITTED BY OWNER BUILDER, (O/B). CT