Plan Review Details - Permit 21020238
Plan Review Stops For Permit 21020238
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-07-21 Cont ID  
Sent By pvalenti Date 2021-07-21 Time 16:35 Rev Time 0.00
Received By pvalenti Date 2021-07-21 Time 16:20 Sent To  
Notes
2021-07-21 16:39:22****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 AT TIME OF INSPECTION, FOR THE REINFORCEMENT OF THE
 STEEL ROOF FRAMING, THE CONTRACTOR IS REQUIRED TO
 PROVIDE:
  
 1) WELD PROCEDURE SPECIFICATIONS
 2) QUALIFICATION OF WELDING PERSONNEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-07-09 Cont ID  
Sent By pvalenti Date 2021-07-09 Time 08:48 Rev Time 0.00
Received By pvalenti Date 2021-07-09 Time 06:34 Sent To  
Notes
2021-07-09 09:06:21****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107, PLEASE RESUBMIT THE FOLLOWING SHOP DRAWING
 PAGES: RF-1 FROM TITAN WELDING (XUAN CHEN P.E.) &
 21058-1 FROM SRM (SAMUEL MARTIN P.E.) WITH THE REVIEW
 STAMP APPROVALS FROM CURRENT ENGINEER OF RECORD (JASON
 D. BARBER P.E.).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-04-21 Cont ID  
Sent By pvalenti Date 2021-04-21 Time 14:36 Rev Time 0.00
Received By pvalenti Date 2021-04-20 Time 13:38 Sent To  
Notes
2021-04-21 14:50:45PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE MORE INFORMATION FOR THE
 NEW OUTSIDE AIR ROOF TOP UNITS. THE SUBMITTED SHOP
 DRAWING RF-1 SIGNED & SEALED BY XUAN CHEN P.E. DOES NOT
 INCLUDE THE (2) OUTSIDE AIR UNITS(OARTU1 & OARTU2).
  
 ALSO, PLEASE CLARIFY THE NOTE FOR OPERATING WEIGHT
 POUNDS FROM WITHIN THE 100% OA PACKAGED ROOFTOP A/C
 EQUIPMENT SCHEDULE ON SHEET M6-1. DOES THIS NUMBER
 (4,450) REPRESENT THE WEIGHT OF EACH UNIT OR A COMBINED
 TOTALWEIGHT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-24 Cont ID  
Sent By pvalenti Date 2021-03-24 Time 14:23 Rev Time 0.00
Received By pvalenti Date 2021-03-24 Time 11:28 Sent To  
Notes
2021-03-24 14:26:13****CORRECTIONS****
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2, PLEASE PROVIDE ENGINEER APPROVED
 STRUCTURAL ROOF DECK INFORMATION INCLUDING PROPOSED
 EQUIPMENT LOCATION AND CONNECTION DETAILS SUCH AS
 REINFORCEMENT OF ROOF FRAMING IF NECESSARY AND WINDLOAD
 RESISTANCE, AS THERE ARE NO ARCHITECTURAL OR STRUCTURAL
 SUBMITTED SHEETS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-26 Cont ID  
Sent By pvalenti Date 2021-02-26 Time 09:33 Rev Time 0.00
Received By pvalenti Date 2021-02-26 Time 08:53 Sent To  
Notes
2021-02-26 09:48:52****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2, PLEASE PROVIDE ENGINEER APPROVED
 STRUCTURAL ROOF DECK INFORMATION INCLUDING PROPOSED
 EQUIPMENT LOCATION AND CONNECTION DETAILS SUCH AS
 REINFORCEMENT OF ROOF FRAMING IF NECESSARY AND WINDLOAD
 RESISTANCE, AS THERE ARE NO ARCHITECTURAL OR STRUCTURAL
 SUBMITTED SHEETS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-07-21 Cont ID  
Sent By jleahy Date 2021-07-21 Time 16:33 Rev Time 0.00
Received By jleahy Date 2021-07-21 Time 16:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-07-08 Cont ID  
Sent By jleahy Date 2021-07-08 Time 14:19 Rev Time 0.00
Received By jleahy Date 2021-07-08 Time 14:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-04-09 Cont ID  
Sent By jleahy Date 2021-04-09 Time 08:04 Rev Time 0.00
Received By jleahy Date 2021-04-09 Time 07:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-16 Cont ID  
Sent By jleahy Date 2021-03-16 Time 14:48 Rev Time 0.00
Received By jleahy Date 2021-03-16 Time 14:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By jleahy Date 2021-02-25 Time 15:24 Rev Time 0.00
Received By jleahy Date 2021-02-24 Time 16:31 Sent To  
Notes
2021-02-25 15:27:30ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PANEL B IS TO BE INSTALLED IN AN CLASSIFIED AREA PLEASE
 INDICATE ON THE PLANS THE AREA OF CLASSIFICATION IN
 RELATION TO THE PANEL. NEC 501,502, 511

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-07-21 Cont ID  
Sent By pvalenti Date 2021-07-21 Time 16:40 Rev Time 0.00
Received By pvalenti Date 2021-07-14 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-12 Cont ID  
Sent By rmcphers Date 2021-07-12 Time 13:09 Rev Time 0.00
Received By rmcphers Date 2021-07-06 Time 11:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-21 Cont ID  
Sent By pvalenti Date 2021-04-21 Time 14:50 Rev Time 0.00
Received By pvalenti Date 2021-04-06 Time 11:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-24 Cont ID  
Sent By pvalenti Date 2021-03-24 Time 14:26 Rev Time 0.00
Received By pvalenti Date 2021-03-12 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-26 Cont ID  
Sent By pvalenti Date 2021-02-26 Time 09:48 Rev Time 0.00
Received By pvalenti Date 2021-02-18 Time 08:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-07-19 Cont ID  
Sent By medwards Date 2021-07-19 Time 15:03 Rev Time 0.00
Received By medwards Date 2021-07-19 Time 15:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-07-09 Cont ID  
Sent By medwards Date 2021-07-09 Time 07:49 Rev Time 0.00
Received By medwards Date 2021-07-09 Time 07:49 Sent To  
Notes
2021-07-09 07:49:591ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020238
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE THAT THIS PROJECT IS UNDER THE 2020
 FLORIDA BUILDING CODE.
  
 2) THE NEW DESIGNER OF RECORD NEEDS TO PROVIDE THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS BASED ON THIS
 NEW DESIGN. FBC EC C403.2.1
  
 3) THE NEW DESIGNER OF RECORD NEEDS TO PROVIDE THE
 ENERGY CALCULATIONS. FBC EC C402
  
 4) PLEASE PROVIDE AN UPDATED SHEET FA0.1 WITH THE NEW
 DESIGNER?S DIGITAL SIGNATURE. FBC 107.2.1
  
 5) PLEASE PROVIDE AN UPDATED SHEET FA2.1 WITH THE NEW
 DESIGNER?S DIGITAL SIGNATURE. FBC 107.2.1
  
 6) PLEASE PROVIDE AN UPDATED SHEET FA2-1 WITH THE NEW
 DESIGNER?S DIGITAL SIGNATURE. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 16:03 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-03-15 Cont ID  
Sent By medwards Date 2021-03-15 Time 14:59 Rev Time 0.00
Received By medwards Date 2021-03-15 Time 14:59 Sent To  
Notes
2021-03-15 15:00:432ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21020238
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TABLE 403.3.1.1 OF THE FBC M ONLY ADDRESSES EXHAUST
 IN REPAIR GARAGES. THE MINIMUM REQUIRED EXHAUST RATE
 FOR A REPAIR GARAGE IS .75 CFM X SQ.FT. OF THE SPACE.
 THE SYSTEM YOU ARE PROPOSING IS MORE IN LINE OF AN
 ENCLOSED PARKING GARAGE. THESE ARE 2 VERY DIFFERENT
 OCCUPANCIES, A PARKING GARAGE VENTILATION IS NOT
 DESIGNED WITH PEOPLE BEING INSIDE THIS SPACE FOR AN 8
 HOUR SHIFT. THE EXHAUST VENTILATION CALCULATION FOR A
 REPAIR GARAGE DOES TAKE THIS INTO CONSIDERATION. THIS
 DESIGN FOR CONDITIONING THIS REPAIR GARAGE DOES NOT
 SHOW THE REQUIRED EXHAUST AIR OF 5160 CFM. I WOULD
 SUGGEST AN AHU WITH 100% OUTDOOR AIR WHICH WOULD NEED
 TO BRING IN THE 5160 CFM AND RETURN OUTDOORS THE 5160
 CFM. SECTION 401.3 OF THE FBCM STATES VENTILATION SHALL
 BE PROVIDED DURING THE PERIODS THAT THE ROOM OR SPACE
 IS OCCUPIED. TABLE 403.3.1.1 OF THE FBC M SPECIFIES
 THAT THE 6180 SQ FT X .75 = 5,160 CFM OF EXHAUST AIR
 WHILE THE SPACE IS OCCUPIED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-02-26 Cont ID  
Sent By medwards Date 2021-02-26 Time 08:19 Rev Time 0.00
Received By medwards Date 2021-02-25 Time 15:55 Sent To  
Notes
2021-02-26 08:19:241ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020238
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) THE ADDRESS ON THE ENERGY GAUGE REPORT DOES NOT
 MATCH THE ADDRESS ON THE PERMIT APPLICATION. PLEASE
 SUBMIT AN ENERGY GAUGE REPORT FOR THE ADDRESS OF THE
 PROJECT. FBC 107.2.1
  
 2) PLEASE SHOW THAT THIS REPAIR GARAGE WILL MEET TABLE
 403.3.1.1 OF THE FBC M FOR THE .75 CFM/SQ.FT. EXHAUST
 AIRFLOW RATE.
  
 3) SHEET M7-1 SHOWS A GREENHECK/EVH-660D LOUVER, PLEASE
 SHOW THE LOCATION OF THIS LOUVER ON SHEET M2-1. FBC
 107.2.1
  
 4) PLEASE PROVIDE THE NOA FOR THE GREENHECK/EVH-660D
 LOUVER. FBC 107.2.1
  
 5) PLEASE PROVIDE THE NOA FOR THE ROOF MOUNTED EXH. FAN
 FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-07-20 Cont ID  
Sent By medwards Date 2021-07-19 Time 15:05 Rev Time 0.00
Received By medwards Date 2021-07-19 Time 15:05 Sent To  
Notes
2021-07-19 15:06:27 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-07-09 Cont ID  
Sent By medwards Date 2021-07-09 Time 07:54 Rev Time 0.00
Received By medwards Date 2021-07-09 Time 07:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-09 Cont ID  
Sent By jleahy Date 2021-04-09 Time 08:04 Rev Time 0.00
Received By jleahy Date 2021-04-09 Time 08:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-15 Cont ID  
Sent By medwards Date 2021-03-15 Time 15:06 Rev Time 0.00
Received By medwards Date 2021-03-15 Time 15:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-26 Cont ID  
Sent By medwards Date 2021-02-26 Time 08:35 Rev Time 0.00
Received By medwards Date 2021-02-26 Time 08:35 Sent To  
Notes
***NONE***