Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-03-04 Cont ID  
Sent By ccole Date 2021-03-04 Time 08:13 Rev Time 0.00
Received By ccole Date 2021-03-04 Time 08:13 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-02-23 Cont ID  
Sent By ccole Date 2021-02-23 Time 17:20 Rev Time 0.00
Received By ccole Date 2021-02-23 Time 16:02 Sent To  
Notes
2021-02-23 17:20:332ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21020232
 2/23/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 NEW COMMENTS.
  
 1) GAS RISER: THE TOTAL GAS LOAD OF 1,789 MBH LISTED
 APPEARS TO BE INCORRECT BASED ON THE INDIVIDUAL
 APPLIANCE LOADS SHOWN WHICH ADD UP TO 994 MBH. PLEASE
 NOTE THAT USING THE PIPE SIZING TABLE LISTED AN 1-1/4
 IN. GALVANIZED PIPE CAN DELIVER A MAXIMUM 1280 MBH AT
 63 FT. DEVELOPED LENGTH. IT ALSO APPEARS THAT ONE OF
 THE COOKING APPLIANCES ON THE LINE IS NOT LISTED. THE
 RISER SHOWS 7 PIPE OUTLETS ON THE LINE BUT ONLY 6
 COOKING APPLIANCES ARE LISTED.
  
 2) GAS RISER: INDICATE THE TYPE AND SIZE OF PIPE
 SUPPLYING THE WATER HEATER, AND THE SIZE AND LENGTH OF
 THE MAIN SUPPLY PIPE FROM THE METER TO THE FIRST TEE-
 SECTION 402.2 & 402.3 FBC FG.
  
 3) THE CONTRACTOR OR QUALIFIER SHALL PROVIDE HIS
 SIGNATURE ON THE DRAWING- SECTION 107.2.1 WPB.
  
 THE 1ST REVIEW COMMENTS THAT WERE NOT ADDRESSED ARE
 LISTED BELOW.
  
 2) GAS RISER:
  
 C) LIST THE PIPE SIZING TABLES USED FOR EACH TYPE OF
 PIPE IN THE SYSTEM- 402.2 & 402.3. CSST PIPE TABLE NOT
 LISTED.
  
 E) LABEL THE WATER HEATER AND COOKING APPLIANCES AS
 EITHER NEW OR EXISTING- SECTION 107.2.1 WPB.
  
 F) SHOW THE LOCATIONS OF APPLIANCE SHUT OFF VALVES-
 SECTION 409.5 FBC FG.
  
 4) LABEL THE HEATER AS EITHER STORAGE TANK OR TANKLESS
 ON THE RISER, AND PROVIDE VENTING SPECIFICATIONS-
 SECTIONS 624.1 AND 503.1 FBC FG.
  
 5) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW
 THE AIR WILL BE PROVIDED- SECTION 304.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-10 Cont ID  
Sent By ccole Date 2021-02-10 Time 10:50 Rev Time 0.00
Received By ccole Date 2021-02-10 Time 09:23 Sent To  
Notes
2021-02-10 10:52:581ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21020232
 2/10/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REVIEW THE ENGINEER OF RECORD'S NOTE ON SHEET
 P.1 OF THE APPROVED RESTAURANT PLANS UNDER PERMIT
 20071220. THE ENGINEER SPECIFIED THE CONTRACTOR SHALL
 SUBMIT A SEPARATE GAS PERMIT AND PLAN INCLUDING "AN
 ISOMETRIC DRAWING WITH PIPE SIZES, MATERIALS & LENGTHS,
 THE TYPE OF GAS, THE BTUH LOAD FOR EACH APPLIANCE, THE
 SIZING TABLES USED, & SPEC SHEETS/INSTALLATION MANUAL
 FOR THE GAS EQUIPMENT & APPLIANCES." THE SUBMITTED
 ISOMETRIC IS INCOMPLETE ACCORDING TO THE NOTE AND ALSO
 SECTION 401.3 & 401.4 FBC FG.
  
 2) GAS RISER:
 A) SHOW THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM
 THE METER TO THE MOST REMOTE OUTLET, AND THE BRANCH
 PIPING LENGTHS TO EACH APPLIANCE- SECTION 402.4.1 &
 402.4.2 FBC FG.
 B) SHOW THE TYPES OF PIPING USED IN THE SYSTEM- 403.1.
 C) SHOW THE DELIVERY PRESSURE AT THE METER AND PIPE
 SIZING TABLES USED FOR EACH TYPE OF PIPE IN THE SYSTEM-
 402.2 & 402.3.
 D) SHOW THE BTUH LOAD OF THE WATER HEATER AND THE LOAD
 OF EACH COOKING APPLIANCE- 402.1.
 E) LABEL THE WATER HEATER AND COOKING APPLIANCES AS
 EITHER NEW OR EXISTING- SECTION 107.2.1 WPB.
 F) SHOW THE LOCATIONS OF APPLIANCE SHUT OFF VALVES-
 409.5
 G) SHOW THE LOCATIONS OF REGULATORS- 410.1 & 410.2
 H) SHOW THE LOCATION OF THE AUTO SHUTOFF VALVE FOR THE
 GAS TO THE COOKING LINE- SEC.10.4.1 NFPA 96.
  
 3) THE UNDERGROUND CSST IS PROHIBITED UNLESS IT IS
 ENCASED IN A CONDUIT OF WROUGHT IRON, PLASTIC OR STEEL
 PIPE, OR OTHER APPROVED MATERIALS- SECTION 404.14.
 PLEASE INDICATE THE GAS PIPE AND CONDUIT WILL BE BURIED
 A MINIMUM OF 12 INCHES BELOW GRADE, WILL BE PROTECTED
 FROM CORROSION- SECTIONS 404.11 & 404.12 FBC FG.
  
 4) AS NOTED IN COMMENT #1 PLEASE SUBMIT SPECS FOR THE
 WATER HEATER AND THE COOKING APPLIANCES- SECTIONS 301.3
 & 305.1 FBC FG. ALL APPLIANCES SHALL BE LISTED AND
 LABELED. LABEL THE HEATER AS EITHER STORAGE TANK OR
 TANKLESS ON THE RISER, AND PROVDE VENTING
 SPECIFICATIONS- SECTIONS 624.1 AND 503.1 FBC FG.
  
 5) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW
 THE AIR WILL BE PROVIDED- SECTION 304.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
2021-02-10 09:27:23THE SUBMITTTED GAS DRAWING IS SEVERELY DEFICIENT WITH
 REQUIRED INFORMATION. PLEASE SUBMIT THE FOLLWING
 INFORMATION:
 1)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aoliver Date 2021-03-04 Time 12:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-02-23 Time   Rev Time 0.00
Received By ccarvaja Date 2021-02-17 Time 05:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-02-10 Time   Rev Time 0.00
Received By aoliver Date 2021-02-04 Time 15:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-03-04 Cont ID  
Sent By ccole Date 2021-03-04 Time 08:12 Rev Time 0.00
Received By ccole Date 2021-03-04 Time 08:12 Sent To  
Notes
2021-03-04 08:13:09PLUMBING FOR TANKLESS WATER HEATER UNDER A SEPARATE
 PERMIT.

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-02-23 Cont ID  
Sent By ccole Date 2021-02-23 Time 17:22 Rev Time 0.00
Received By ccole Date 2021-02-23 Time 16:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-02-10 Cont ID  
Sent By ccole Date 2021-02-10 Time 10:54 Rev Time 0.00
Received By ccole Date 2021-02-10 Time 08:35 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-02-11 Cont ID  
Sent By shill Date 2021-02-11 Time 17:26 Rev Time 0.00
Received By shill Date 2021-02-11 Time 17:26 Sent To  
Notes
2021-02-11 17:26:46PRIVATE PROVIDER INSPECTIONS ONLY, REVIEWED UNDER
 MASTER
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-02-10 Cont ID  
Sent By ccole Date 2021-02-10 Time 10:54 Rev Time 0.00
Received By ccole Date 2021-02-10 Time 08:35 Sent To  
Notes
***NONE***