| Plan Review Stops For Permit 21020224 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2021-03-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-03-22 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-03-22 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2021-03-22 16:10:17 | ALREADY OBTAINED ELEC PERMITS UNDER 111 SAPODILLA | | | STATE OWNED LAND | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-03-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-03-11 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-03-11 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2021-03-11 09:52:28 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | LOOKS LIKE A LOT MORE THAN A MINI SLPIT SYSTEM PLEASE | | | EXPAND ON SCOPE OF WORK ON PERMIT.. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-03-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-12 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-08 |
Time |
07:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-02-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-08 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-04 |
Time |
16:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-03-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-12 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-12 |
Time |
14:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-02-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-08 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-08 |
Time |
06:21 |
Sent To |
|
|
| Notes |
| 2021-02-08 06:49:37 | 1) PLEASE PROVIDE MECHANICAL SIZING CALCULATIONS. FBC | | | EC C403.2.1 | | | | | | 2) PLEASE PROVIDE A SCOPE OF WORK FOR THIS PROJECT, THE | | | APPLICATION STATES ONLY THE MINI SPLIT. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-03-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-03-22 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-03-22 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2021-03-22 16:19:26 | PAPER RECEIVED, ROUTED TO STORAGE | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-03-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-12 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-12 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2021-03-12 14:52:30 | DRAWINGS ARE NOT THE ORIGINAL DIGITALLY SIGNED AND | | | SEALED DRAWINGS, THEY ARE COPIES OF THE ORIGINALS. WE | | | CANNOT ACCEPT COPIES. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-02-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-08 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-08 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2021-02-08 07:06:51 | THE DRAWINGS APPEAR TO BE COPIES OF DIGITAL DRAWINGS. | | | PLEASE UPLOAD THE ORIGINAL DIGITALLY SIGNED AND SEALED | | | DRAWINGS. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|