Plan Review Details - Permit 21020172
Plan Review Stops For Permit 21020172
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-09-13 Cont ID  
Sent By cpuell Date 2021-09-13 Time 08:38 Rev Time 0.00
Received By cpuell Date 2021-09-13 Time 08:38 Sent To  
Notes
2021-09-13 08:39:23ADDRESSING APPROVED AS FOLLOWS:
  
 PROPOSED THE FOLLOWING ADDRESSES, WAITING TO HEAR FROM
 OWNER:
  
 416 CLEMATIS ST - PHARMACY
 418 CLEMATIS ST - VETERINARY
 416 CLEMATIS ST # 200
 416 CLEMATIS ST # 201
 416 CLEMATIS ST # 202
 416 CLEMATIS ST # 203
 416 CLEMATIS ST # 204
 416 CLEMATIS ST # 205
 416 CLEMATIS ST # 206
 416 CLEMATIS ST # 207
 416 CLEMATIS ST # 208
  

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-09-10 Cont ID  
Sent By cpuell Date 2021-09-10 Time 16:04 Rev Time 0.00
Received By cpuell Date 2021-09-10 Time 16:04 Sent To  
Notes
2021-09-10 16:05:50PROPOSED THE FOLLOWING ADDRESSES, WAITING TO HEAR FROM
 OWNER:
  
 416 CLEMATIS ST ? PHARMACY
 418 CLEMATIS ST ? VETERINARY
 416 CLEMATIS ST # 200
 416 CLEMATIS ST # 201
 416 CLEMATIS ST # 202
 416 CLEMATIS ST # 203
 416 CLEMATIS ST # 204
 416 CLEMATIS ST # 205
 416 CLEMATIS ST # 206
 416 CLEMATIS ST # 207
 416 CLEMATIS ST # 208
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-09-09 Cont ID  
Sent By cpuell Date 2021-09-09 Time 09:38 Rev Time 0.00
Received By cpuell Date 2021-09-09 Time 09:38 Sent To  
Notes
2021-09-09 09:38:59NEW ENTRANCE REQUIRES A NEW ADDRESS, PLEASE CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS
 ADDRESSING OPTIONS.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status P Date 2021-08-30 Cont ID  
Sent By jleahy Date 2021-08-30 Time 12:57 Rev Time 0.00
Received By jleahy Date 2021-08-30 Time 12:57 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status F Date 2021-07-19 Cont ID  
Sent By jwitmer Date 2021-07-19 Time 11:03 Rev Time 0.00
Received By jwitmer Date 2021-07-19 Time 08:59 Sent To  
Notes
2021-07-19 11:03:26TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-06-15 Cont ID  
Sent By jwitmer Date 2021-06-15 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2021-06-14 Time 10:30 Sent To  
Notes
2021-06-15 10:18:15COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-04-05 Cont ID  
Sent By jwitmer Date 2021-04-05 Time 09:25 Rev Time 0.00
Received By jwitmer Date 2021-04-05 Time 07:29 Sent To  
Notes
2021-04-05 09:21:34TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-02-19 Cont ID  
Sent By jwitmer Date 2021-02-19 Time 15:53 Rev Time 0.00
Received By jwitmer Date 2021-02-19 Time 15:45 Sent To  
Notes
2021-02-19 15:53:08TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] . THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2021-09-16 Cont ID  
Sent By pvalenti Date 2021-09-16 Time 08:43 Rev Time 0.00
Received By pvalenti Date 2021-09-14 Time 09:02 Sent To  
Notes
2021-09-16 09:03:54 
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED WITH PROVISOS:
  
 THIS PERMIT IS FOR SHELL ONLY. SEPARATE PERMITS ARE
 REQUIRED FOR TENANT BUILDOUTS.
  
 PLEASE SEE NOTE ON SHEET S-1 REGARDING WELDING
 REQUIREMENTS:
  
 AWS D1.1 CLAUSE 5.2 & 6.7: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S.
 SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING:
 BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO
 BE USED.
 AWS D1.1 CLAUSE 6.16: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE
 W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO
 VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS
 IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2021-08-24 Cont ID  
Sent By jwitmer Date 2021-08-24 Time 09:57 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-08-24 09:57:24WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020172
 ADD: 416 CLEMATIS ST.
 CONT: STUART M LEDIS LLC
 TEL: 561-718-7162
 E-MAIL: [email protected]
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 3RD REVIEW / NEW DESIGN TEAM
 DATE: TUES. AUGUST 24, 2021
 ACTION: DENIED
  
 1) COMPLIED
  
 2A) (1) 3RD REVIEW, I SEE WHERE THE DESIGNER OF RECORD
 IS TRYING TO KEEP A OPEN MEZZANINE AS THE DESIGN
 PARAMETERS. THE CONCEPT OF THE OPEN MEZZANINE AND HOW
 THE AREAS WERE FIGURED IS MISLEADING. IN THE MEETING WE
 HAD I KEPT TRYING TO SHOW WHAT AREAS COULD BE USED IN
 ALLOWABLE FLOOR AREA, ALLOWABLE FLOOR AREA IS THAT AREA
 THAT ATMOSPHERICALLY COMMUNICATES. YOU USE THE FLOOR
 AREA ON THE 1ST FLOOR (GROUND FLOOR) WHICH THE DEMO
 SHEET SHOWS 1776.34 SQ. FT. THEN YOU DIVIDE THIS AREA
 BY 1/3 (2020 FBC-B 505.2.1) WHICH WILL GIVE YOU 592 SQ.
 FT. THE ALLOWABLE AREA FOR MEZZANINE. YOU ARE TAKING
 EXCEPTION # 2 FOR TYPE I, TYPE II CONSTRUCTION. THE
 1776 SQ. FT. / 2 = 888 SQ. FT. ALLOWABLE AREA FOR
 MEZZANINES. THE EXISTING MEZZANINE 405 SQ. FT. + 1305.8
 SQ. FT. NEW MEZZANINE = 1711 SQ. FT. (SHOWN ON THE D-1
 SHEET) OVER THE ALLOWABLE AREA. THE OTHER ISSUE WITH
 EXCEPTION # 2 IS THAT THIS BUILDING TYPE IS DECLARED AS
 TYPE VB CONSTRUCTION SPRINKLERED.
  
 2A)(2) PLEASE NOTE THE ATRIUM AREA IS THE ONLY WAY TO
 FIGURE THE 2ND STORY AREA OVER THE VETERINARY TENANT
 AREA. THE QUESTION IS WITH THE REMAINDER OF THE
 EXISTING MEZZANINE HOW WILL THIS AREA BE HANDLED WILL
 IT BE WALLED OFF TO THE ATRIUM OR A GLASS ENCLOSURE
 WITH A FIRE CURTAIN ON BOTH SIDES. 107.2.1.2
 2ND REVIEW, SAME COMMENT FOR THE NEW AREA OF THE 2ND
 STORY HOW THE NEW FLOOR AREA WILL BE SEPARATED FROM THE
 2-STORY HIGH ATRIUM, ONE HOUR SEPARATION IS REQUIRED.
 SINCE THERE IS TO BE NEW 2ND STORY AREA, THIS AREA NOW
 NEEDS SEPARATION FROM THE 2-STORY ATRIUM AREA (1 HOUR
 RATED WALLS OR GLASS WALL WITH A WATER CURTAIN BOTH
 SIDES AND GASKETED GLAZING). SHEETS A-1 & S-1. WITH THE
 NEW PARTIAL 2ND FLOOR EXPANSION THERE LEAVES AN AREA
 OPEN TO THE 2ND STORY, THIS IS ONLY ALLOWED WHEN IT IS
 A MEZZANINE. THE AREA IN QUESTION IS OVER 1/3RD OF THE
 FLOOR AREA THAT WAS OPEN AREA. THE COVERSHEET INDICATES
 THAT THIS BUILDING IS FIRE SPRINKLERED. THE OPEN AREA
 THAT IS NOW AN OPEN 2 STORY AREA WILL NOW NEED TO MEET
 THE REQUIREMENTS FOR A ATRIUM. SEE SECTION 404.6
 ENCLOSURES OF ATRIUMS AND EXCEPTIONS.
  
 2B) NEW COMMENT. CAF?/ MERCANTILE. PLEASE REVIEW
 SECTION 301.1 & 301.2 OF THE 2020 FBC-BUILDING CODE ON
 HOW TO CLASSIFY THIS OCCUPANCY AND OCCUPANT LOADS.
  
 2C) THE NEW FRONT DOOR # 2 INDICATES A SIDE APPROACH
 WHERE YOU HAVE SHOWN 48 INCHES OF WIDTH. THE 2020
 FBC-ACCESS. CODE SEE FIGURE 404.2.4.1(I) REQUIRES A
 MINIMUM OF 54 INCHES IN WIDTH TO BE ABLE TO MAKE THE
 TURN AND AN ADDITIONAL 24 INCHES FROM THE LATCH SIDE OF
 THE DOOR PARALLEL WITH THE DOOR.
  
 2D) THERE IS A NEW COUNTER IN THE NEW CORRIDOR 6 FEET
 LONG AT 34 INCHES IN HEIGHT THE PLANS DO NOT INDICATE
 IF THIS IS A WALL HUNG COUNTER AND OR IF IT HAS LEGS,
 SHOW COMPLIANCE WITH THE 2020 ACCESSIBILITY CODE
 SECTION PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 2E) THERE IS NO ACTUAL 2ND FLOOR PLAN FOR EGRESS, THE
 DEMO SHEET SHOWS A MEASUREMENT OF 70.7 FEET IN LENGTH =
 11.1 FEET ACROSS THE MEZZANINE AND AN ADDITIONAL 19
 FEET TO TWO MEANS OF EGRESS. PLEASE SHOW ON A LIFE
 SAFETY SHEET COMPLIANCE WITH COMMON PATH OF TRAVEL
 TABLE 1006.2.1 OF THE 2020 FBC-BUILDING CODE.
  
 3A) BUILDING PROVISO: SHEET S-1. PLEASE SHOW COMPLIANCE
 WITH: WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN
 CONRAD AT 561-805-6666.
  
 3B) DEFERRED SUBMITTALS. COMPONENTS & CLADDING
 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP
 VENTILATORS
  
  
 4-6) COMPLIED.
  
 7) SEE IMPACT REVIEW STOP. THE PLANS WILL NEED TO BE
 REVIEWED BY PALM BEACH COUNTY IMPACT FEE FOR THE
 INCREASE IN FLOOR AREA.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-07-19 Cont ID  
Sent By jwitmer Date 2021-07-19 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2021-07-19 Time 08:59 Sent To  
Notes
2021-07-19 11:57:07WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020172
 ADD: 416 CLEMATIS ST.
 CONT: STUART M LEDIS LLC
 TEL: 561-718-7162
 E-MAIL: [email protected]
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 2ND REVIEW / NEW DESIGN TEAM
 DATE: MON. JULY 19TH/2021
 ACTION: DENIED
 1) COMPLIED
  
 2) 2ND REVIEW, SAME COMMENT FOR THE NEW AREA OF THE 2ND
 STORY HOW THE NEW FLOOR AREA WILL BE SEPARATED FROM THE
 2-STORY HIGH ATRIUM, ONE HOUR SEPARATION IS REQUIRED.
 SINCE THERE IS TO BE NEW 2ND STORY AREA, THIS AREA NOW
 NEEDS SEPARATION FROM THE 2-STORY ATRIUM AREA (1 HOUR
 RATED WALLS OR GLASS WALL WITH A WATER CURTAIN BOTH
 SIDES AND GASKETED GLAZING). SHEETS A-1 & S-1. WITH THE
 NEW PARTIAL 2ND FLOOR EXPANSION THERE LEAVES AN AREA
 OPEN TO THE 2ND STORY, THIS IS ONLY ALLOWED WHEN IT IS
 A MEZZANINE. THE AREA IN QUESTION IS OVER 1/3RD OF THE
 FLOOR AREA THAT WAS OPEN AREA. THE COVERSHEET INDICATES
 THAT THIS BUILDING IS FIRE SPRINKLERED. THE OPEN AREA
 THAT IS NOW AN OPEN 2 STORY AREA WILL NOW NEED TO MEET
 THE REQUIREMENTS FOR A ATRIUM. SEE SECTION 404.6
 ENCLOSURES OF ATRIUMS AND EXCEPTIONS.
  
 3) BUILDING PROVISO: SHEET S-1. PLEASE SHOW COMPLIANCE
 WITH: WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN
 CONRAD AT 561-805-6666.
  
 4-6) COMPLIED.
  
 7) SEE IMPACT REVIEW STOP. THE PLANS WILL NEED TO BE
 REVIEWED BY PALM BEACH COUNTY IMPACT FEE FOR THE
 INCREASE IN FLOOR AREA.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-15 Cont ID  
Sent By jwitmer Date 2021-06-15 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2021-06-14 Time 10:30 Sent To  
Notes
2021-06-14 11:10:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020172
 ADD: 416 CLEMATIS ST.
 CONT: STUART M LEDIS LLC
 TEL: 561-718-7162
 E-MAIL: [email protected]
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 1ST REVIEW / NEW DESIGN TEAM
 DATE: TUES. JUNE 15TH/2021
 ACTION: DENIED
 1) SHEET A-1 NEW 1ST FLOOR PLAN:
  
 1A) UNDER THE HEADING OF COMPLIANCE W/ FBC 2020 7TH
 EDITION THE NEW CONSTRUCTION TYPE IS LISTED AS VB.
 EXISTING CONSTRUCTION LISTED AS IV PROTECTED (AUTOMATIC
 SPRINKLER SYSTEM). IN THE 2020 FBC-B TYPE IV THERE IS
 NO A OR B. TYPE IV IS HEAVY TIMBER. IN ALL OTHER
 CONSTRUCTION TYPE, A- MEANS AT LEAST 1-HOUR FIRE
 PROTECTION. B USUALLY MEANS NOT PROTECTED EXCEPT FOR
 TYPE I-B WHERE ALL STRUCTURAL COMPONENTS ARE 2 HOURS
 RATED EXCEPT FOR THE ROOF CONSTRUCTION AND ASS.
 SECONDARY FRAMING MEMBERS.
  
 1B) UNDER THE SCOPE OF WORK 1. BUILDING IT STATES THE
 ALTERATION LEVEL IS A LEVEL 2 BUT ALSO STATES TO ADD
 NEW STEEL BAR JOIST. THIS IS CREATING A VERTICAL
 ADDITION, A SECTION OF THE 2ND STORY, AN ADDITION, NEW
 FLOOR AREA. 107.2.1.2. PLEASE REVIEW IN THE 2020
 FBC-EXISTING BUILDING CODE 1103.3.1 VERTICAL ADDITIONS,
 AND 1101.2 CREATION OR EXTENSION OF NONCONFORMITY.
  
 2) SHEETS A-1 & S-1. WITH THE NEW PARTIAL 2ND FLOOR
 EXPANSION THERE LEAVES AN AREA OPEN TO THE 2ND STORY,
 THIS IS ONLY ALLOWED WHEN IT IS A MEZZANINE. THE AREA
 IN QUESTION IS OVER 1/3RD OF THE FLOOR AREA THAT WAS
 OPEN AREA. THE COVERSHEET INDICATES THAT THIS BUILDING
 IS FIRE SPRINKLERED. THE OPEN AREA THAT IS NOW A OPEN 2
 STORY AREA WILL NOW NEED TO MEET THE REQUIREMENTS FOR A
 ATRIUM. SEE SECTION 404.6 ENCLOSURES OF ATRIUMS AND
 EXCEPTIONS.
  
 3) SHEET S-1. PLEASE SHOW COMPLIANCE WITH: WELDED OR
 BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN
 CONRAD AT 561-805-6666.
  
 4A) THE SHEET A-1 GIVE A PARTIAL OF WIND DESIGN
 CRITERIA, MISSING THE MEAN ROOF HEIGHT, SHEET S-1 GIVES
 DESIGN WIND PRESSURES FOR WINDOW AND DOORS, WORST CASE
 SCENARIO. WITH THE MISSING MEAN ROOF HEIGHT, WE DO NOT
 KNOW WHAT MULTIPLIERS WERE USED IN DERIVING THE
 PRESSURES. 2020 FBC-B TABLE 1609.7.2/ ASCE 7-16 TABLE
 30.3.1.
  
 4B) SINCE THE WIND DESIGN ON THE SHEET A-1 WAS GIVEN IN
 VULT (170 MPH VULT) CAN IT BE ASSUMED THE PRESSURES
 LISTED ON S-1 WOULD ALSO BE IN VULT IF SO, THEY ARE
 LOW. IF THEY ARE IN VASD THEN PLEASE NOTE AND PROVIDE
 THE MEAN ROOF HEIGHT. THANK YOU.
  
 5A) IN THIS REVIEW NO PRODUCT APPROVALS WERE SUBMITTED
 FOR REVIEW, NOR ON THE COVERSHEET A REQUEST FOR
 DEFERRED SUBMITTALS. COMPONENTS & CLADDING. 2020 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
  
 5B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 5C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5D) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6) SHEET A-1. THE ORIGINAL DESIGN OF THIS BUILDING WAS
 WHEN IT WAS BUILT A SINGLE TENANT BUILDING WITH (AT THE
 TIME IT WAS BUILT EITHER A MEZZANINE OR 2N D FLOOR).
 THE ISSUE AT HAND WITH THE BUILDING BEING SPLIT UP, AND
 WITH ADDING ADDITIONAL SQUARE FOOTAGE TO THE SECOND
 FLOOR THE MEANS OF EGRESS TO AND FROM THE 2ND FLOOR AND
 COMPLIANCE WITH:
 2020 FBC-B SECTION 1016.2(2)
 ALSO SECTION 1016.2(3)
  
 7) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH
 COUNTY IMPACT FEE FOR THE INCREASE IN FLOOR AREA.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2021-04-05 Time 09:26 Rev Time 0.00
Received By jwitmer Date 2021-04-05 Time 07:29 Sent To  
Notes
2021-04-05 09:16:24WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020172
 ADD: 416 CLEMATIS ST.
 CONT: STUART M LEDIS LLC
 TEL: 561-718-7162
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 19TH/2021
 ACTION: DENIED
  
 1) THE TITLE SHEET T-1:
 1A) COMPLIED.
  
 1B) SEMI-COMPLIED. FOR LIFE SAFETY YOU ALWAYS ROUND UP
 TO THE NEXT WHOLE OCCUPANT. BOAF INTERPRETATION.
 BUILDING OFFICIALS OF FLORIDA, INFORMAL INTERPRETATION.
 1ST ROUND OF COMMENTS. UNDER THE HEADING OCCUPANCY
 SUMMARY THE DESIGNER OF RECORD LIST THE TENANT SPACE AS
 BUSINESS OCCUPANCY 1430 SQ. FT. USING A OCCUPANT LOAD
 FACTOR OF 100 S. F. GROSS. PLEASE REVIEW THE 2020 FBC-B
 TABLE 1004.1.2 FOR CHANGE IN THE OCCUPANT LOAD FACTOR
 IS NOW 150 S. F. GROSS. 1430 / 150= 9.53 OR 10
 OCCUPANTS, YOU ALWAYS ROUND UP TO THE NEXT WHOLE
 OCCUPANT.
  
 2) SHEET A-1 THE FLOOR PLAN:
 2A) COMPLIED.
  
 2B) 2ND REQUEST, SEMI-COMPLIED. CORRECTED THE MEAN ROOF
 HEIGHT BUT IN THE WIND DESIGN CRITERIA THERE IS A NEW
 STATEMENT THAT THIS BUILDING IS PARTIALLY OPEN
 STRUCTURE. PLEASE EXPLAIN HOW THIS BUILDING QUALIFIES
 AS A PARTIALLY OPEN BUILDING AS FAR AS WIND DESIGN
 GOES. ON THE INTERIOR OF THE BUILDING IT IS CURRENTLY A
 PARTIAL ONE STORY, AND PARTIAL 2 STORY BUILDING.
  
 1ST ROUND OF COMMENTS. DESIGN CRITERIA (WIND). LIST THE
 MEAN ROOF HEIGHT OF THIS BUILDING AT 14 FEET 7 INCHES.
 THIS IS A FULL 2 STORY BUILDING. WITH ATTIC SPACE ON
 THE 2ND FLOOR BETWEEN THE CEILING JOIST AND ROOF
 RAFTERS. PLEASE UPDATE PLANS. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. PLANS ALSO STATE THE STRUCTURE
 IS PARTIAL OPEN, PLEASE EXPLAIN?
  
 2C)SHEET A-1, A-3 NOR THE NEW SHEETS S-1 OR S2 SHOW
 WHAT LOADS ARE TO BE CONSIDERED FOR THE STAIRS AND NEW
 PORTION OF THE 2ND FLOOR. SEE THE 2020 FBC-B TABLE
 1607.1.
 1ST ROUND OF COMMENTS. THE SHEET ALSO LIST ON SHEET A-1
 LIVE LOADS OF 30 PSF AND DEAD LOADS OF 25 PSF, THERE IS
 NO LISTING AS TO FLOOR LOADS, STAIRS, ROOF LOADS ETC.
 PLEASE REVIEW TABLE 1607.1 MINIMUM UNIFORMLY
 DISTRIBUTED LIVE LOADS.
  
 2D)(1) COMPLIED.
  
 2E) WITH THE NEW PARTIAL 2ND FLOOR EXPANSION THERE
 LEAVES AN AREA OPEN TO THE 2ND STORY, THIS IS ONLY
 ALLOWED WHEN IT IS A MEZZANINE. THE AREA IN QUESTION IS
 OVER 1/3RD OF THE FLOOR AREA THAT WAS OPEN AREA. THE
 COVERSHEET INDICATES THAT THIS BUILDING IS FIRE
 SPRINKLERED. THE OPEN AREA THAT IS NOW A OPEN 2 STORY
 AREA WILL NOW NEED TO MEET THE REQUIREMENTS FOR A
 ATRIUM. SEE SECTION 404.6 ENCLOSURES OF ATRIUMS AND
 EXCEPTIONS.
  
 1ST ROUND OF COMMENTS. THE UPPER HALF OF THE FLOOR PLAN
 THERE IS A VACANT SPACE, THERE IS NO INFORMATION AS IF
 THIS SPACE IS PART OF THIS PERMIT AND IF IT IS WHAT
 WORK IS TO OCCUR IN THIS SPACE. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. THE PROPOSED PLAN IT WOULD
 APPEAR ON THE 1ST FLOOR BUT THERE IS NO TENANT ADDRESS
 AS TO TENANT SPACE. 2020 FLORIDA BUILDING CODE W 2020
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED.
  
 2F) COMPLIED.
  
 3) NEW COMMENT. SHEETS S-1:
 3A) PLEASE NOTE THE SCOPE OF WORK HAS INCREASED WIT THE
 ADDITION OF THE 2ND FLOOR BUT THE VALUE OF THE PERMIT
 HAS NOT INCREASED.
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3B) THERE IS A PERMIT APPLICATION THAT HAS BEEN IN FOR
 THE 1ST REVIEW, WHAT IS GOING TO HAPPEN TO THAT PERMIT?
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3C) PLEASE SHOW COMPLIANCE WITH: WELDED OR BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN
 CONRAD AT 561-805-6666.
  
 3D) NEITHER SHEET S-1 NOR S2 PROVIDE THE COMPONENT AND
 CLADDING PRESSURES FOR THE NEW STOREFRONT GLAZING
 SYSTEM AND DOORS.
 3D)(1). DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 3D)(2) WIND SPEED CONVERSION VULT TO VASD.
  
 3E) PROVIDE PRODUCT APPROVALS. COMPONENTS & CLADDING.
 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS
  
 3F) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 3G) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 4) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH
 COUNTY IMPACT FEE FOR THE INCREASE IN FLOOR AREA.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-19 Cont ID  
Sent By jwitmer Date 2021-02-19 Time 17:02 Rev Time 0.00
Received By jwitmer Date 2021-02-19 Time 15:46 Sent To  
Notes
2021-02-19 17:02:29WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020172
 ADD: 416 CLEMATIS ST.
 CONT: STUART M LEDIS LLC
 TEL: 561-718-7162
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 19TH/2021
 ACTION: DENIED
  
 1) THE TITLE SHEET T-1:
 1A) GENERAL NOTE # 1 INDICATES THE GOVERNING CODES
 ASCE-7-10. PLEASE UPDATE THE REFERENCE TO THE 2020
 FBC-B CHAPTER 35 ASCE-7-16.
  
 1B) UNDER THE HEADING OCCUPANCY SUMMARY THE DESIGNER OF
 RECORD LIST THE TENANT SPACE AS BUSINESS OCCUPANCY 1430
 SQ. FT. USING A OCCUPANT LOAD FACTOR OF 100 S. F.
 GROSS. PLEASE REVIEW THE 2020 FBC-B TABLE 1004.1.2 FOR
 CHANGE IN THE OCCUPANT LOAD FACTOR IS NOW 150 S. F.
 GROSS. 1430 / 150= 9.53 OR 10 OCCUPANTS, YOU ALWAYS
 ROUND UP TO THE NEXT WHO OCCUPANT.
  
 2) SHEET A-1 THE FLOOR PLAN:
 2A) DESIGN CRITERIA (WIND). PLEASE NOTE THE PLAN
 REFERENCES THE 2017 6TH EDITION OF THE FBC-B AND ASCE
 7-10. DEC. 31/ 2020 THE 7TH EDITION OF THE 2020 FBC-B
 WAS ADOPTED STATEWIDE AND THE ASCE 7-16, PLEASE UPDATE
 TO THE CURRENT CODES.
  
 2B) DESIGN CRITERIA (WIND). LIST THE MEAN ROOF HEIGHT
 OF THIIS BUILDING AT 14 FEET 7 INCHES. THIS IS A FULL 2
 STORY BUILDING. WITH ATTIC SPACE ON THE 2ND FLOOR
 BETWEEN THE CEILING JOIST AND ROOF RAFTERS. PLEASE
 UPDATE PLANS. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED. PLANS ALSO STATE THE STRUCTURE IS PARTIAL
 OPEN, PLEASE EXPLAIN?
  
 2C) THE SHEET ALSO LIST ON SHEET A-1 LIVE LOADS OF 30
 PSF AND DEAD LOADS OF 25 PSF, THERE IS NO LISTING AS TO
 FLOOR LOADS, STAIRS, ROOF LOADS ETC. PLEASE REVIEW
 TABLE 1607.1 MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS.
  
 2D) THE PLAN DOES NOT CLEARLY SHOW HOW EGRESS IS TO BE
 OBTAINED TO THE 2ND FLOOR WITHOUT GOING THROUGH ANOTHER
 TENANT SPACE. PLEASE ALSO SHOW THE ELEVATOR CLEARLY FOR
 THE REQUIRED VERTICAL ACCESSIBILITY. 2020 FBC-B SECTION
 1016.2 EGRESS THROUGH INTERVENING SPACES. 2020
 FBC-ACCESSIBILITY CODE SECTION 201.1.1. VERTICAL
 ACCESSIBILITY.
  
 2E) THE UPPER HALF OF THE FLOOR PLAN THERE IS A VACANT
 SPACE, THERE IS NO INFORMATION AS IF THIS SPACE IS PART
 OF THIS PERMIT AND IF IT IS WHAT WORK IS TO OCCUR IN
 THIS SPACE. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED. THE PROPOSED PLAN IT WOULD APPEAR ON THE 1ST
 FLOOR BUT THERE IS NO TENANT ADDRESS AS TO TENANT
 SPACE. 2020 FLORIDA BUILDING CODE W 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2F) THE TITLEBLOCK INDICATES WORK FOR THIS PERMIT IS
 FOR A VETERINARY OFFICE. THE PERMIT APPLICATION STATES
 UNDER THE DESCRIPTION OF WORK INTERIOR RENOVATION,
 PHARMACY & VETERINARY OFFICE. THE PLANS DO NOT SHOW
 WORK TO BE COMPLETED FOR A PHARMACY.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-08-30 Cont ID  
Sent By jleahy Date 2021-08-30 Time 12:56 Rev Time 0.00
Received By jleahy Date 2021-08-30 Time 12:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-14 Cont ID  
Sent By jleahy Date 2021-06-14 Time 17:03 Rev Time 0.00
Received By jleahy Date 2021-06-14 Time 16:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-02 Cont ID  
Sent By equinone Date 2021-04-02 Time 11:37 Rev Time 0.00
Received By equinone Date 2021-04-02 Time 11:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-16 Cont ID  
Sent By equinone Date 2021-02-16 Time 16:19 Rev Time 0.00
Received By equinone Date 2021-02-16 Time 14:14 Sent To  
Notes
2021-02-16 16:19:35CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEETS E-1 AND E-2: WILL NEW PANEL A SUPPLY ALL NEW
 AND EXISTING CIRCUITS? IT SEEMS THAT PANEL SCHEDULE
 SUBMITTED DOES NOT INCLUDE THE EXISTING CIRCUITS. FOR
 EXAMPLE, AN EXISTING A/C UNIT IS SHOWN ON POWER PLAN,
 BUT IT IS NOT SHOWN ON PANEL SCHEDULE. IF ONLY PANEL A
 WILL BE USED PLEASE INCLUDE ALL EXISTING CIRCUITS ON
 PANEL SCHEDULE AND CALCULATIONS AND IF THERE IS ANOTHER
 PANEL, PLEASE SHOW IT ON DRAWINGS AND SUBMIT PANEL
 SCHEDULE.
 2) PLEASE ADD NOTES/SPECIFICATIONS TO ELECTRICAL POWER
 AND LIGHTING SYSTEMS TO SHOW COMPLIANCE WITH SECTION
 C405, FBC, ENERGY CONSERVATION CODE 2020 EDITION.
 3) SHEET E-2 ? PLEASE MODIFY ELECTRICAL NOTE 1 TO
 CLEARLY SPECIFY COMPLIANCE WITH FBC 2020 7TH EDITION
 AND NEC 2017.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2021-09-13 Cont ID  
Sent By pleduc Date 2021-09-13 Time   Rev Time 0.00
Received By pleduc Date 2021-09-13 Time 14:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2021-08-19 Cont ID  
Sent By pleduc Date 2021-08-19 Time   Rev Time 0.00
Received By pleduc Date 2021-08-19 Time 10:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-07-16 Cont ID  
Sent By pleduc Date 2021-07-16 Time   Rev Time 0.00
Received By pleduc Date 2021-07-16 Time 12:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-06-10 Cont ID  
Sent By pleduc Date 2021-06-10 Time   Rev Time 0.00
Received By pleduc Date 2021-06-10 Time 12:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-04-06 Cont ID  
Sent By pleduc Date 2021-04-06 Time   Rev Time 0.00
Received By pleduc Date 2021-04-06 Time 11:13 Sent To  
Notes
2021-04-06 11:15:151) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 7TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2018 EDITION OF NFPA 1 AND NFPA 101.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND
 COMPLIANCE.
  
 PLEASE UPDATE YOUR RECORDS FOR FUTURE PROJECTS
  
 THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2016 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2016 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2018 EDITION.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-02-05 Cont ID  
Sent By pleduc Date 2021-02-05 Time   Rev Time 0.00
Received By pleduc Date 2021-02-05 Time 14:48 Sent To  
Notes
2021-02-05 15:01:581) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 7TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2018 EDITION OF NFPA 1 AND NFPA 101.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND
 COMPLIANCE.
  
 PLEASE UPDATE YOUR RECORDS FOR FUTURE PROJECTS
  
 THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2016 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2016 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2018 EDITION.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-09-26 Cont ID  
Sent By lmarchan Date 2021-09-26 Time 09:07 Rev Time 0.00
Received By lmarchan Date 2021-09-10 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-09-03 Cont ID  
Sent By lmarchan Date 2021-09-03 Time 08:38 Rev Time 0.00
Received By lmarchan Date 2021-08-18 Time 06:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-08-06 Cont ID  
Sent By cthroop Date 2021-08-06 Time 09:41 Rev Time 0.00
Received By cthroop Date 2021-07-15 Time 15:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-23 Cont ID  
Sent By jgomez Date 2021-06-23 Time 17:02 Rev Time 0.00
Received By jgomez Date 2021-06-09 Time 09:00 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-04-06 Time   Rev Time 0.00
Received By aoliver Date 2021-04-01 Time 09:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-19 Cont ID  
Sent By jwitmer Date 2021-02-19 Time 17:03 Rev Time 0.00
Received By jwitmer Date 2021-02-03 Time 15:50 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2021-10-14 Cont ID  
Sent By lmarchan Date 2021-10-14 Time 11:24 Rev Time 0.00
Received By lmarchan Date 2021-09-24 Time 15:35 Sent To  
Notes
2021-10-07 12:15:08RECEIPT MU-2021-047250 - $12,337.42 - PAID
2021-09-24 15:30:4009/24/21 IMPACT FEE QUESTIONNAIRE UPLOADED. EMAILED PBC
 IMPACT FEES OFFICE. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2021-06-15 Cont ID  
Sent By jwitmer Date 2021-06-15 Time 10:22 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-06-15 10:20:22ADDITIONAL SQUARE FOOTAGE TO THE 2ND FLOOR SEE
 STRUCTURAL SHEET S-1.
 IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2021-04-05 Cont ID  
Sent By jwitmer Date 2021-04-05 Time 09:25 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-04-05 09:19:59IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-02-19 Cont ID  
Sent By jwitmer Date 2021-02-19 Time 15:47 Rev Time 0.00
Received By jwitmer Date 2021-02-19 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2021-09-17 Cont ID  
Sent By hmoser Date 2021-09-17 Time 09:26 Rev Time 0.00
Received By hmoser Date 2021-09-16 Time 14:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2021-08-21 Cont ID  
Sent By medwards Date 2021-08-21 Time 06:47 Rev Time 0.00
Received By medwards Date 2021-08-21 Time 06:47 Sent To  
Notes
2021-08-21 06:47:305TH REVIEW FBC-2020 MECHANICAL
 PERMIT-21020172
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1 OF 2: THE DRYER DUCT PENETRATING THE RATED
 WALL MUST COMPLY WITH FBC M 504.2
  
 2) SHEET M1 OF 2: OUTDOOR AIR CALCULATIONS SHOW
 EXISTING BUSINESSES ON 1ST FLOOR AND ON THE 2ND FLOOR
 BUT THE SCOPE OF WORK SHOWN ON THE DRAWING INDICATES
 ONLY THE NEW VET BUSINESS. PLEASE CLARIFY. FBC 107.2.1
  
 3) THERE ARE 2 M1 OF 2 SHEETS ONE IS THE VET BUSINESS
 AND THE OTHER IS THE ROOF PLAN. IS THERE ANOTHER SHEET?
 THERE APPEARS TO BE MORE WORK ON THE A SHEETS. PLEASE
 CLARIFY. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-07-20 Cont ID  
Sent By medwards Date 2021-07-20 Time 15:43 Rev Time 0.00
Received By medwards Date 2021-07-20 Time 15:43 Sent To  
Notes
2021-07-20 15:43:254TH REVIEW FBC-2020 MECHANICAL
 PERMIT-21020172
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DRYER DUCT AND DRYER BOX ARE IN A RATED WALL,
 THIS DRYER BOX MUST BE FIRE RATED AND THE DUCT MUST BE
 PROTECTED FROM WHERE IT LEAVES THE DRYER BOX TO THE
 EXTERIOR TERMINATION LOCATION. FBC M 504.2 DUCTS THAT
 EXHAUST CLOTHES DRYERS SHALL NOT PENETRATE OR BE
 LOCATED WITHIN ANY FIRE BLOCKING, DRAFT STOPPING OR ANY
 WALL, FLOOR/CEILING OR OTHER ASSEMBLY REQUIRED BY THE
 FLORIDA BUILDING CODE, BUILDING TO BE FIRE-RESISTANCE
 RATED, UNLESS SUCH DUCT IS CONSTRUCTED OF GALVANIZED
 STEEL OR ALUMINUM OF THE THICKNESS SPECIFIED IN SECTION
 603.4 AND THE FIRE-RESISTANCE RATING IS MAINTAINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 FIRE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS AND ANY
 SIMILAR DEVICES THAT WILL OBSTRUCT THE EXHAUST FLOW
 SHALL BE PROHIBITED IN CLOTHES DRYER EXHAUST DUCTS.
  
 2) THE WALL AROUND THE AH-7 APPEARS TO BE RATED. PLEASE
 SHOW THE PROTECTION IN THIS WALL BY THE 8 INCH OUTDOOR
 AIR DUCT PENETRATION. FBC M 607
  
 3) PLEASE EXPLAIN THE CONDENSATE LINES RUNNING UP TO
 ROOF. IS THERE A CONDENSATE PUMP THAT IS NOT LISTED OR
 SHOWN ON THE DRAWINGS?
  
 4) IT DOES NOT APPEAR THAT THIS IS A PET SHOP SO PLEASE
 PROVIDE THE CORRECT OCCUPANCY CLASSIFICATION. THIS NEW
 TENANT SPACE APPEARS TO BE A DR. OFFICE. IF IT WERE TO
 BE A PET SHOP YOU WOULD NEED TO PROVIDE 1,029 CFM OF
 EXHAUST IN THE ANIMAL AREAS. I DO NOT SEE AN ANIMAL
 AREA.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-06-14 Cont ID  
Sent By medwards Date 2021-06-14 Time 16:00 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 16:00 Sent To  
Notes
2021-06-14 16:00:401ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020172
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: PLEASE PROVIDE PENETRATION PROTECTION
 WHERE THE MECHANICAL DUCTS PENETRATE THE NEW RATED WALL
 THAT DIVIDES THE VETERINARY OFFICE FROM THE OTHER
 TENANT SPACE. FBC M 607
  
 2) PLEASE REPLACE THE 24 INCH FLEX DUCT FOR THE RETURN
 FOR NEW AHU-7 THAT IS RUNNING THROUGH THE RATED TENANT
 SEPARATION WALL. FBC M 607
  
 3) PLEASE SHOW THE CONDENSATION PIPING AND TERMINATION
 LOCATION FOR AHU-7. FBC M 307
  
 4) PLEASE SHOW THE NEW DRYER EXHAUST DUCT WORK AND
 TERMINATION LOCATION. FBC M 501.3 AND 504
  
 5) THE VETERINARY BUSINESS IS A NEW USE OF SPACE SO
 THEREFORE PLEASE BREAK DOWN THE OUTDOOR AIR
 CALCULATIONS PER USE OF SPACE. I.E. THE RECEPTION AREA
 WILL BE MORE CONCENTRATED THAN THE EXAM ROOMS. FBC M
 403.3.1.1 AND TABLE 403.3.1.1
  
 6) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE NEW AHU-7. FBC EC 403.2.1 AND FBC
 M 312
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-04-02 Cont ID  
Sent By medwards Date 2021-04-02 Time 13:46 Rev Time 0.00
Received By medwards Date 2021-04-02 Time 13:46 Sent To  
Notes
2021-04-02 13:47:42PLEASE ADDRESS COMMENTS FROM 1ST CYCLE REVIEW.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-02-09 Cont ID  
Sent By medwards Date 2021-02-09 Time 15:17 Rev Time 0.00
Received By medwards Date 2021-02-09 Time 15:16 Sent To  
Notes
2021-02-09 15:17:011ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020172
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON USE
 OF SPACE FROM TABLE 403.3.1.1. DO NOT USE ARCHITECTURAL
 OCCUPANT COUNT. PLEASE PICK THE OCCUPANCY
 CLASSIFICATION THAT BEST FITS THIS BUSINESS OCCUPANCY
 AND IDENTIFY ALL SPACES IN THIS BUILDING IN THE OUTDOOR
 AIR CALCULATIONS. FBC M 403.3.1.1, TABLE 403.3.1.1
  
 2) PLEASE SHOW THE FA-1 IN THE AIR BALANCE SCHEDULE.
 FBC 107.2.1
  
 3) PLEASE EXPLAIN THE USE OF THE FA-1, IS THE NEW
 MECHANICAL SYSTEM DESIGNED TO REMOVE THE HUMIDITY THIS
 FAN WILL BRING INTO THE BUILDING?
  
 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATION. FBC EC C403.2.1
  
 5) PLEASE SHOW THE CALCULATIONS FOR THE EXISTING
 MECHANICAL SYSTEMS SUPPLYING THE REQUIRED OUTDOOR AIR
 FOR THE ENTIRE AREA, SHOW UNIT SIZES. FBC M 403.3.1.1
  
 6) PLEASE IDENTIFY THE AHU AND THE ACU MENTIONED IN THE
 AIR BALANCE SCHEDULE. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2021-09-21 Cont ID  
Sent By ccole Date 2021-09-21 Time 17:21 Rev Time 0.00
Received By ccole Date 2021-09-17 Time 11:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2021-08-27 Cont ID  
Sent By ccole Date 2021-08-27 Time 09:35 Rev Time 0.00
Received By ccole Date 2021-08-26 Time 15:28 Sent To  
Notes
2021-08-27 09:35:345TH REVIEW FBC-2020 PLUMBING
 PERMIT- 21020172
 8/27/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED
 BELOW WITH NOTES ADDED FOR FURTHER CLARIFICATION. THIS
 IS THE FIFTH REVIEW OF THE PROJECT AND MANY OF THE
 DEFICIENCIES ON THE PLAN WERE DISCUSSED AT A PREVIOUS
 MEETING AT CITY HALL WITH THE DESIGN PROFESSIONALS AND
 THE CONTRACTOR. PLEASE CONTACT ME IF YOU HAVE QUESTIONS
 ABOUT THE COMMENTS OR ADDITIONAL INFORMATION IS NEEDED.
  
 3) FAILED. A1. P1 & P2: THE PLANS APPEAR TO SHOW A
 MIXED OCCUPANCY OF OFFICES, PHARMACY, COFFEE/JUICE BAR,
 AND VETERINARY CLINIC- BUSINESS AND MERCANTILE
 OCCUPANCIES. PLEASE PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P BASED
 ON THE OCCUPANT LOADS SHOWN. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED NUMBER OF PLUMBING
 FIXTURES. VERIFY THAT ALL TENANT OCCUPANTS WILL HAVE
 ACCESS TO THE FIXTURES. BASED ON THE REVISED PLANS AND
 INCREASED OCCUPANT LOADS PLUMBING FIXTURES APPEAR
 COMPLIANT FOR THE ANIMAL HOSPITAL (UNSIEX TOILET ROOM
 INSIDE THE SEPARATE TENANT SPACE), AND FOR THE COMBINED
 IST FLOOR MERCANTILE, BUSINESS AND STORAGE OCCUPANCIES
 (EXISTING 1ST FLOOR MEN'S AND WOMEN'S TOILET ROOMS,
 SERVICE SINK AND DRINKING FOUNTAIN). PLEASE VERIFY THAT
 THE MINIMUM REQUIRED FIXTURES FOR THE SECOND FLOOR
 BUSINESS OCCUPANCIES ARE EXISTING- MINIMUM OF ONE MEN'S
 WATER CLOSET AND LAVATORY, AND ONE WOMEN'S WATER CLOSET
 AND LAVATORY.
  
 4) FAILED. P1, P2, P3: A GREASE INTERCEPTOR IS REQUIRED
 FOR THE NEW COFFEE SHOP IN ACCORDANCE WITH SECTION
 1003.3.1 FBC P. PLEASE REVISE THE PLAN: A) SHOW THE
 LOCATION OF THE INTERCEPTOR. B) PROVIDE AN EQUIPMENT
 SCHEDULE AND SIZING CALCULATIONS. C) PROVIDE NEW
 PLUMBING FLOOR PLAN AND ISOMETRIC DRAWING THAT
 INCORPORATE THE REQUIRED INTERCEPTOR. D) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALL GUIDELINES.
 THE REVISED PLANS DO NOT SHOW THE DISHWASHER INDIRECT
 WASTE RECEPTOR DRAINING INTO THE INTERCEPTOR, AND THE
 INTERCEPTOR SIZING CALCULATIONS HAVE NOT BEEN PROVIDED-
 SECTIONS 802.1.7 & 1003.3.1 FBC P. A) PLEASE PROVIDE A
 COMPLETE SUBMITTAL FOR THE NEW INTERCEPTOR AND AN
 ENLARGED INSTALLATION DETAIL- SECTION 1003.3.1 FBC P.
  
 9) FAILED. P1 & P2: PROVIDE ENLARGED SANITARY AND WATER
 SUPPLY PLAN FOR THE COFFEE/JUICE BAR THAT SHOWS THE
 LOCATIONS OF ALL FLOOR SINKS, HUB DRAIN, AND FLOOR
 DRAINS NEEDED FOR BEVERAGE DISPENSER, ICE MAKER, WATER
 FILTER, AND REFRIGERATOR AND FREEZER EQUIPMENT DRAINAGE
 ETC. PLEASE SHOW THE LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS AND BACKFLOW PREVENTERS FOR SUPPLY LINES TO
 THE EQUIPMENT- SECTION 604.9 & 608.3 FBC P. B) FILTERED
 WATER SUPPLY CONNECTIONS TO COFFEE BAR EQUIPMENT SUCH
 AS BREWER, EXPRESSO MACHINE, ICE MAKER ETC. NOT SHOWN.
 C) BACKFLOW PROTECTION FOR THE WATER FILTER AND
 FILTERED SUPPLY LINES TO EQUIPMENT NOT SHOWN. D)
 MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED FOR
 THE COFFEE BAR EQUIPMENT. THE CURRENT SCHEULE DOES NOT
 LIST MAKES AND MODEL NUMBERS, HOWEVER THE SUBMITTALS
 MAY BE DEFERRED PER SECTION 107.3.4.1 WPB. PLEASE NOTE
 THAT THE COFFEE BAR FILTERED WATER PIPING PLAN ANSD
 MANUFACTURER?S SPECIFICATIONS FOR COFFEE BAR EQUIPMENT
 AND APPLIANCES MAY BE DEFERRES SUBMITTALS IF NECESSARY-
 SECTION 107.3.4.1 WPB.
  
 13) FAILED. P1, P2, & P3: PROVIDE ENLARGED PIPING
 DRAWINGS FOR THE WATER HEATERS SHOWING LOCATIONS OF
 THERMAL EXPANSION TANKS, RECIRCULATION PUMPS, SHUTOFF
 VALVES, CHECK VALVES, RELIEF VALVE, ETC.- SECTIONS
 502.1, 607.2.1.2, 607.3 FBC P. THE NEW WH DETAIL SHOWS
 A THERMAL EXPANSION TANK ON THE HW LINE WHICH IS NOT
 REQUIRED AND NOT IN ACCORDANCE WITH THE CODE OR
 MANUFACTURER'S SPECIFICATIONS. PLEASE REVISE THE DETAIL
 AND SHOW THE HW RETUN LINE AND LOCATION OF THE
 RECIRCULATION PUMP AND PIPING CONNECTIONS- SECTION
 607.2 & 607.3 FBC P.
  
 18) FAILED. P1: LABEL THE TWO FIXTURES ABOVE THE FLOOR
 DRAINS IN THE VET CLINIC AND PROVIDE A PLUMBING FIXTURE
 SCHEDULE FOR THE VET CLINIC- SECTION 107.2.1 WPB.
 INDICATE HOW THE FLOOR DRAINS ARE VENTED IN THE RISER
 DRAWING- SECTION 901.2.1 FBC P. A) THE PLANS APPEAR TO
 SHOW EITHER A DEPRESSED SLAB AREA WITH FLOOR DRAINS OR
 A BUILT UP OR FACTORY-MADE BASIN WITH FLOOR DRAINS
 BELOW. PLEASE INDICATE WHAT THESE FIXTURES ARE AND
 PROVIDE EITHER CONSTRUCTION DETAILS OR MANUFACTURER'S
 SPECIFICATIONS. VENT SYSTEM THEN THE WATER CLOSET
 CANNOT DRAIN INTO THE LINE- SECTION 910.1 & 911.1 FBC
 P.
  
 19) FAILED. P1, P2, & A1: INDICATE THE TYPE OF FINISH
 WALL AND FLOOR MATERIALS TO BE INSTALLED IN THE NEW AND
 "EXISTING" TOILET ROOMS AND AT THE MOP SINKS IN THE VET
 CLINIC AND THE COFFEE/JUICE BAR- SEE SECTIONS 310.3 FBC
 P AND 1210.2. FBC B. THE REVISED PLAN INDICATES
 IMPERVIOUS MATERIALS HOWEVER THE CODE REQUIRES A
 SMOOTH, HARD, NONABSORBENT SURFACE TO BE INSTALLED.
 THIS WOULD EXCLIDE INSTALLATION OF PAINTED DRYWALL.
 PLEASE BE MORE SPECIFIC ABOUT THE FINISH MATERIAL.
  
 22) FAILED. P1 & P2: REFER TO SECTION 212.3 FBC ACC.
 SINKS AND INDICATE WHICH SINKS IN THE VET CLINIC AND
 PHARMACY WILL BE MADE ACCESSIBLE. PLEASE NOTE WHERE
 SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER
 THAN ONE, OF EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM
 OR SPACE SHALL COMPLY WITH 606. SHOW THE CLEAR FLOOR
 SPACE DIAGRAM AND DIMENSION AT EACH ACCESSIBLE SINK ON
 THE FLOOR PLAN AND PROVIDE AN ELEVATION DRAWING SHOWING
 SINK HEIGHT AND KNEE AND TOE CLEARANCES- SECTIONS 606.2
 & 606.3 FBC P. NOT PROVIDED. PLEASE SHOW THE FORWARD OR
 PARALLEL APPROACH CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS AT THE ACCESSIBLE SINK LOCATIONS- SECTION
 606.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2021-07-20 Cont ID  
Sent By ccole Date 2021-07-20 Time 10:36 Rev Time 0.00
Received By ccole Date 2021-07-19 Time 14:53 Sent To  
Notes
2021-07-20 10:36:243RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21020172
 6/14/2021
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST AND 2ND REVIEWS ARE LISTED BELOW WITH NOTES ADDED
 FOR FURTHER CLARIFICATION.
  
 3) FAILED. A1. P1 & P2: THE PLANS APPEAR TO SHOW A
 MIXED OCCUPANCY OF OFFICES, PHARMACY, COFFEE/JUICE BAR,
 AND VETERINARY CLINIC- BUSINESS AND MERCANTILE
 OCCUPANCIES. PLEASE PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P BASED
 ON THE OCCUPANT LOADS SHOWN. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED NUMBER OF PLUMBING
 FIXTURES. VERIFY THAT ALL TENANT OCCUPANTS WILL HAVE
 ACCESS TO THE FIXTURES. A) FIXTURE REQUIREMENTS FOR THE
 SEPARATE ANIMAL HOSPITAL TENANT SPACE APPROVED. B)
 PLEASE CORRECT A1 FLOOR PLAN NOTE TO INDICATE THE
 COFFEE SHOP IS A B OCCUPANCY, AND NOT AN M- SECTION
 303.1.2 FBC B. C) THERE IS CONTRADICTORY SQUARE FOOTAGE
 CALCULATIONS SHOWN FOR THE DRUG STORE(M). IT IS
 INDICATED AT 2905 SQ. FT. IN THE TABULATIONS BOX (A1)
 AND 1987 IN THE MERCANTILE OCCUPANT LOAD NOTE- PLEASE
 CORRECT. D) REFER TO SECTION 403.1.1 FBC P- FOR
 CALCULATIONS INVOLVING MULTIPLE OCCUPANCIES, SUCH
 FRACTIONAL NUMBERS FOR EACH OCCUPANCY SHALL FIRST BE
 SUMMED AND THEN ROUNDED UP TO THE NEXT WHOLE NUMBER.
 THE FACILITY IS PROVIDING COMMON USE FIXTURES ON THE
 FIRST AND SECOND FLOORS FOR BOTH PUBLIC AND EMPLOYEE
 USE. AS PREVIOUSLY REQUESTED, PROVIDE A FIXTURE
 CALCULATION SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF PLUMBING FIXTURES USING PERCENTAGES
 FOR THE BUSINESS AND MERCANTILE OCCUPANCIES. THE PLANS
 APPEAR TO BE NON-COMPLIANT- NO SERVICE SINK HAS BEEN
 PROVIDED FOR THE B AND M OCCUPANCIES.
  
 4) FAILED. P1 & P2: A GREASE INTERCEPTOR IS REQUIRED
 FOR THE NEW COFFEE SHOP IN ACCORDANCE WITH SECTION
 1003.3.1 FBC P. PLEASE REVISE THE PLAN: A) SHOW THE
 LOCATION OF THE INTERCEPTOR. B) PROVIDE AN EQUIPMENT
 SCHEDULE AND SIZING CALCULATIONS. C) PROVIDE NEW
 PLUMBING FLOOR PLAN AND ISOMETRIC DRAWING THAT
 INCORPORATE THE REQUIRED INTERCEPTOR. D) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALL GUIDELINES.
 NOT PROVIDED. THE CITY OF WPB BUILDING DEPARTMENT IN
 ACCORDANCE WITH SECTION 1003.3.1 FBC P AND SECS. 90-126
 & 127 WPB CODE OR ORDINANCES REQUIRES GREASE
 INTERCEPTORS TO RECEIVE THE DRAINAGE FROM FIXTURES AND
 EQUIPMENT WITH GREASE LADEN WASTE. MILK AND OTHER
 PRODUCTS USED IN COFFEE SHOPS CONTAIN FATS AND OILS
 WHICH ARE PROHIBITED FROM THE DRAINING INTO THE CITY
 SANITARY SYSTEM. PLEASE NOTE THAT HAND SINKS SHALL NOT
 DRAIN INTO THE GREASE WASTE LINE- SECTION 1003.3.1 FBC
 P.
  
 5) FAILED. P1 & P2: PROVIDE AN INTERCEPTOR FOR THE
 WASHING MACHINE IN ACCORDANCE WITH SECTION 1003.6 FBC
 P. CLOTHES WASHERS SHALL DISCHARGE THROUGH AN
 INTERCEPTOR THAT IS PROVIDED WITH A WIRE BASKET OR
 SIMILAR DEVICE, REMOVABLE FOR CLEANING, THAT PREVENTS
 PASSAGE INTO THE DRAINAGE SYSTEM OF SOLIDS 1/2 INCH OR
 LARGER IN SIZE, STRING, RAGS, BUTTONS OR OTHER
 MATERIALS DETRIMENTAL TO THE PUBLIC SEWAGE SYSTEM. LIST
 THE MAKE AND MODEL OF THE WASHING MACHINE AND
 INTERCEPTOR ON THE PLAN, AND SUBMIT MANUFACTURER?S
 SPECIFICATIONS, REVISE THE PLUMBING DRAWINGS. NOT
 PROVIDED. THE INTEGRAL PUMP FILTER IS NOT AN
 INTERCEPTOR. PLEASE SEE DEFINITION OF DISCHARGE PIPE- A
 PIPE THAT CONVEYS THE DISCHARGE FROM PLUMBING FIXTURES
 OR APPLIANCES- SECTION 202. PLEASE PROVIDE THE
 INTERCEPTOR.
  
 9) FAILED. P1 & P2: PROVIDE ENLARGED SANITARY AND WATER
 SUPPLY PLAN FOR THE COFFEE/JUICE BAR THAT SHOWS THE
 LOCATIONS OF ALL FLOOR SINKS, HUB DRAIN, AND FLOOR
 DRAINS NEEDED FOR BEVERAGE DISPENSER, ICE MAKER, WATER
 FILTER, AND REFRIGERATOR AND FREEZER EQUIPMENT DRAINAGE
 ETC. PLEASE SHOW THE LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS AND BACKFLOW PREVENTERS FOR SUPPLY LINES TO
 THE EQUIPMENT- SECTION 604.9 & 608.3 FBC P. A) GREASE
 INTERECEPTOR AND GREASE WASTE LINE NOT PROVIDED. B)
 FILTERED WATER SUPPLY CONNECTIONS TO COFFEE BAR
 EQUIPMENT SUCH AS BREWER, EXPRESSO MACHINE, ICE MAKER
 ETC. NOT SHOWN. C) BACKFLOW PROTECTION FOR THE WATER
 FILTER AND FILTERED SUPPLY LINES TO EQUIPMENT NOT
 SHOWN. D) MANUFACTURER'S SPECIFICATIONS SHALL BE
 SUBMITTED FOR THE COFFEE BAR EQUIPMENT. THE CURRENT
 SCHEULE DOES NOT LIST MAKES AND MODEL NUMBERS, HOWEVER
 THE SUBMITTALS MAY BE DEFERRED PER SECTION 107.3.4.1
 WPB. E) PLEASE NOTE THE FLOOR DRAINS TRAPS IN THE
 ANIMAL HOSPITAL ARE NOT VENTED PROPERLY. IF THE INTENT
 IS TO PROVIDE A COMBINATION DRAIN AND VENT SYSTEM THEN
 THE WATER CLOSET CANNOT DRAIN INTO THE LINE- SECTION
 910.1 & 911.1 FBC P.
  
 10) FAILED. P1 & P2: PROVIDE AN ENLARGED INDIRECT WASTE
 DETAIL FOR THE 3-COMPARTMENT SINK- SECTION 802.1.1 FBC
 P. NOT PROVIDED. THE SPEC SHEET DOES NOT SHOW EACH WELL
 OF THE 3-COMPARTMENT SINK DISCHARGING INDEPENDENTLY
 INTO THE FLOOR SINK. THE FLOOR SINK SHOULD BE CENTERED
 FOR DRAIN ACCESS.
  
 12) FAILED. P1 & P2: PLEASE PROVIDE EQUIPMENT SCHEDULES
 FOR THE WEST AND EAST WATER HEATERS AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 502.1 FBC P.
 EQUIPMENT SCHEDULES NOT PROVIDED. PLEASE NOTE THE
 TANKLESS WATER HEATER SPEC SHEET SHOWS TWO DIFFERENT
 MODELS. PLEASE CHOOSE ONE OR THE OTHER AND SPECIFY IT
 ON THE PLAN.
  
 13) FAILED. P1 & P2: PROVIDE ENLARGED PIPING DRAWINGS
 FOR THE WATER HEATERS SHOWING LOCATIONS OF THERMAL
 EXPANSION TANKS, RECIRCULATION PUMPS, SHUTOFF VALVES,
 CHECK VALVES, RELIEF VALVE, ETC.- SECTIONS 502.1,
 607.2.1.2, 607.3 FBC P. THERMAL EXPANSION TANK
 REQUIRED.
  
 14) FAILED. P1 & P2: PROVIDE PANS AND PAN DRAINS FOR
 THE NEW WATER HEATERS. SHOW THE TYPE AND SIZE OF PANS,
 AND THE TYPE AND SIZE OF PAN DRAIN PIPES, THE DRAIN
 PIPE RUNS AND DISCHARGE LOCATIONS- SECTIONS 504.6-
 504.7.2 FBC P. A PAN DRAIN IS NOTED FOR THE WEST WATER
 HEATER HOWEVER THE PAN DRAIN LINE AND DISCHARGE
 LOCATION NOT SHOWN. NO PAN OR PAN DRAIN HAS BEEN
 SPECIFIED FOR THE TANKLESS WATER HEATER P&T RELIEF
 VALVE DISCHARGE.
  
 15) FAILED. P1 & P2: LABEL THE LAVATORY IN THE WEST
 WATER RISER- SECTION 419.1 FBC P. REFER TO SECTION
 C404.5.1 AND TABLE C404.5.1 FBC ENERGY CONSERVATION-
 THE RISER SHOWS THE LENGTH OF THE 1/2-INCH HOT WATER
 SUPPLY PIPE TO THE LAVATORY FROM THE WATER HEATER HAS
 EXCEED THE MAXIMUM ALLOWABLE LENGTH OF 2FT. EITHER A
 POINT OF USE WATER HEATER AT THE LAVATORY OR A
 RECIRCULATION PUMP FOR THE HOT WATER SYSTEM SHALL BE
 INSTALLED. NOT PROVIDED. THERE IS A NOTE AT THE WEST
 RISER SPECIFYING A RECIRCULATION PUMP HOWEVER THE
 RECIRCULATION LINE IS NOT SHOWN. NO SPEC FOR THE
 RECIRCULATION PUMP PROVIDED.
  
 16) FAILED. P1 & P2: WHERE HOT WATER IS SUPPLIED TO A
 LAVATORY, THE WATER SHALL BE TEMPERED IN ACCORDANCE
 WITH SECTIONS 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A
 MIXING VALVE THAT CONFORMS TO ASSE 1070. NOT PROVIDED.
  
 18) FAILED. P1: LABEL THE TWO FIXTURES ABOVE THE FLOOR
 DRAINS IN THE VET CLINIC, AND PROVIDE A PLUMBING
 FIXTURE SCHEDULE FOR THE VET CLINIC- SECTION 107.2.1
 WPB. INDICATE HOW THE FLOOR DRAINS ARE VENTED IN THE
 RISER DRAWING- SECTION 901.2.1 FBC P. A) THE PLANS
 APPEAR TO SHOW EITHER A DEPRESSED SLAB AREA WITH FLOOR
 DRAINS OR A BUILT UP OR FACTORY-MADE BASIN WITH FLOOR
 DRAINS BELOW. PLEASE INDCATE WHAT THESE FIXTURES ARE
 AND PROVIDE EITHER CONSTRUCTION DETAILS OR
 MANUFACTURER?S SPECIFICATIONS. B) PLEASE NOTE THE FLOOR
 DRAINS TRAPS IN THE ANIMAL HOSPITAL ARE NOT VENTED
 PROPERLY. IF THE INTENT IS TO PROVIDE A COMBINATION
 DRAIN AND VENT SYSTEM THEN THE WATER CLOSET CANNOT
 DRAIN INTO THE LINE- SECTION 910.1 & 911.1 FBC P.
  
 19) FAILED. P1, P2, & A1: INDICATE THE TYPE OF FINISH
 WALL AND FLOOR MATERIALS TO BE INSTALLED IN THE NEW AND
 "EXISTING" TOILET ROOMS AND AT THE MOP SINKS IN THE VET
 CLINIC AND THE COFFEE/JUICE BAR- SEE SECTIONS 310.3 FBC
 P AND 1210.2. FBC B. WALL FINISH MATERIALS NOT
 PROVIDED.
  
 20) FAILED. P2: THE ACCESSIBILITY DETAILS FOR THE
 TOILET ROOMS APPEAR TO INCOMPLETE AND NOT CORRECT.
 PLEASE REFER TO FBC ACC AND PROVIDED ENLARGED DRAWINGS
 AND DETAILS SHOWING: SEE ITEMS BELOW.
 C) TURNING SPACE DIAMETERS- SECTION 304.3. NOT
 PROVIDED.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3 MUST SHOW THE
 MEASUREMENT TO THE REFLECTIVE SURFACE.
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604. HEIGHTS OF THE GRAB BARS NOT PROVIDED.
 J) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7. NOT PROVIDED.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2. NOT PROVIDED.
  
 22) FAILED. P1 & P2: REFER TO SECTION 212.3 FBC ACC.
 SINKS AND INDICATE WHICH SINKS IN THE VET CLINIC AND
 PHARMACY WILL BE MADE ACCESSIBLE. PLEASE NOTE WHERE
 SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER
 THAN ONE, OF EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM
 OR SPACE SHALL COMPLY WITH 606. SHOW THE CLEAR FLOOR
 SPACE DIAGRAM AND DIMENSION AT EACH ACCESSIBLE SINK ON
 THE FLOOR PLAN, AND PROVIDE AN ELEVATION DRAWING
 SHOWING SINK HEIGHT AND KNEE AND TOE CLEARANCES-
 SECTIONS 606.2 & 606.3 FBC P.
 NOT PROVIDED.
  
 23) FAILED P2: REFER TO TABLE C403.2.10 FBC EC AND
 PROVIDE HOT WATER PIPE INSULATION SPECIFICATIONS.
 SPECIFICATIONS NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-06-14 Cont ID  
Sent By ccole Date 2021-06-14 Time 13:40 Rev Time 0.00
Received By ccole Date 2021-06-14 Time 13:40 Sent To  
Notes
2021-06-14 13:40:493RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21020172
 6/14/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. NEW PLANS HAVE BEEN
 SUBMITTED. THE ORIGINAL PLANS THAT FAILED 1ST AND 2ND
 REVIEWS HAVE BEEN REMOVED FROM THE SETS.
 NEW COMMENTS.
  
 1) SHEETS A1 & D1: BOTH OF THESE SHEETS ARE LABELED IN
 THE MARGINS AS "LEVEL #2 INTERIOR REMODELING ONLY"
 HOWEVER THE A1 FLOOR PLAN INDICATES "NEW FIRST FLOOR
 PLAN" THE NEW FIRST FLOOR PLAN ALSO SHOWS MANY
 "EXISTING" ROOMS INCLUDING TWO UNISEX TOILET ROOM AND
 AN ACCESSIBLE DRINKING FOUNTAIN. THE ORIGINAL PLANS
 THAT WERE WITHDRAWN SHOW AN OPEN SPACE WHERE THE NEW
 PLANS INDICATE "EXISTING". I AM UNABLE TO LOCATE A
 PERMIT AND PLANS FOR THOSE ROOMS IN THE WPB DEPT.
 BUILDING RECORDS. PLEASE ADVISE OF THE PERMIT FOR THOSE
 ROOMS OR REVISE THE PLANS TO SHOW THEM AS "NEW"-
 SECTION 107.2.1 WPB.
  
 2) SHEETS P1 & P2: : BOTH OF THESE SHEETS ARE LABELED
 IN THE MARGINS AS "LEVEL #2 INTERIOR REMODELING ONLY"
 HOWEVER THE P1 FLOOR PLAN INDICATES "NEW FIRST FLOOR
 PLUMBING PLAN"- SECTION 107.2.1 WPB.
  
 3) A1. P1 & P2: THE PLANS APPEAR TO SHOW A MIXED
 OCCUPANCY OF OFFICES, PHARMACY, COFFEE/JUICE BAR, AND
 VETERINARY CLINIC- BUSINESS AND MERCANTILE OCCUPANCIES.
 PLEASE PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.1 FBC P BASED ON THE OCCUPANT
 LOADS SHOWN. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED NUMBER OF PLUMBING FIXTURES.
 VERIFY THAT ALL TENANT OCCUPANTS WILL HAVE ACCESS TO
 THE FIXTURES.
  
 4) P1 & P2: A GREASE INTERCEPTOR IS REQUIRED FOR THE
 NEW COFFEE SHOP IN ACCORDANCE WITH SECTION 1003.3.1 FBC
 P. PLEASE REVISE THE PLAN: A) SHOW THE LOCATION OF THE
 INTERCEPTOR. B) PROVIDE AN EQUIPMENT SCHEDULE AND
 SIZING CALCULATIONS. C) PROVIDE NEW PLUMBING FLOOR PLAN
 AND ISOMETRIC DRAWING THAT INCORPORATE THE REQUIRED
 INTERCEPTOR. D) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALL GUIDELINES.
  
 5) P1 & P2: PROVIDE AN INTERCEPTOR FOR THE WASHING
 MACHINE IN ACCORDANCE WITH SECTION 1003.6 FBC P.
 CLOTHES WASHERS SHALL DISCHARGE THROUGH AN INTERCEPTOR
 THAT IS PROVIDED WITH A WIRE BASKET OR SIMILAR DEVICE,
 REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE INTO THE
 DRAINAGE SYSTEM OF SOLIDS 1/2 INCH OR LARGER IN SIZE,
 STRING, RAGS, BUTTONS OR OTHER MATERIALS DETRIMENTAL TO
 THE PUBLIC SEWAGE SYSTEM. LIST THE MAKE AND MODEL OF
 THE WASHING MACHINE AND INTERCEPTOR ON THE PLAN, AND
 SUBMIT MANUFACTURER?S SPECIFICATIONS, REVISE THE
 PLUMBING DRAWINGS.
  
 6) P1: THE SANITARY PIPING LAYOUT PLAN AND ISOMETRIC
 DRAWING DO NOT INCLUDE THE ?EXISTING? TOILET ROOMS,
 ?EXISTING? DRINKING FOUNTAINS. ?EXISTING? DOUBLE SINK
 IN THE PHARMACY- SECTION 107.2.1 & 107.3.5.3.1 FBC P.
 NOTE- NOT REQUIRED IF PROOF OF PERMIT AND INSPECTION
 CAN BE PROVIDED.
  
 7) P1: PROVIDE A NEW EAST WATER RISER THAT INCLUDES THE
 SUPPLY LINES TO THE "EXISTING" TOILET ROOMS, "EXISTING"
 DRINKING FOUNTAINS. "EXISTING" DOUBLE SINK IN THE
 PHARMACY, AND THE NEW COFFEE/JUICE BAR- SECTION 107.2.1
 & 107.3.5.3.1 FBC P. NOTE- NOT REQUIRED IF PROOF OF
 PERMIT AND INSPECTION CAN BE PROVIDED'
  
 8) P1: PROVIDE A NUMBERED EQUIPMENT PLAN AND
 CORRESPONDING NUMBER EQUIPMENT SCHEDULE FOR THE
 COFFEE/JUICE BAR- SECTION 107.2.1 WPB.
  
 9) P1: PROVIDE ENLARGED SANITARY AND WATER SUPPLY PLAN
 FOR THE COFFEE/JUICE BAR THAT SHOWS THE LOCATIONS OF
 ALL FLOOR SINKS, HUB DRAIN, AND FLOOR DRAINS NEEDED FOR
 BEVERAGE DISPENSER, ICE MAKER, WATER FILTER, AND
 REFRIGERATOR AND FREEZER EQUIPMENT DRAINAGE ETC. PLEASE
 SHOW THE LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS
 AND BACKFLOW PREVENTERS FOR SUPPLY LINES TO THE
 EQUIPMENT- SECTION 604.9 & 608.3 FBC P.
  
 10) P1 & P2: PROVIDE AN ENLARGED INDIRECT WASTE DETAIL
 FOR THE 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P.
  
 11) P1 & P2: THE NEW WEST WATER RISER SHOWS A WATER
 HEATER FOR THE WEST HOWEVER NO EAST RISER HAS BEEN
 PROVIDED TO SHOW REQUIRED HOT WATER BEING PROVIDED TO
 THE FIXTURES- SECTION 607.1 FBC P.
  
 12) P1 & P2: PLEASE PROVIDE EQUIPMENT SCHEDULES FOR THE
 WEST AND EAST WATER HEATERS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 502.1 FBC P.
  
 13) P1 & P2: PROVIDE ENLARGED PIPING DRAWINGS FOR THE
 WATER HEATERS SHOWING LOCATIONS OF THERMAL EXPANSION
 TANKS, RECIRCULATION PUMPS, SHUTOFF VALVES, CHECK
 VALVES, RELIEF VALVE, ETC.- SECTIONS 502.1, 607.2.1.2,
 607.3 FBC P.
  
 14) P1 & P2: PROVIDE PANS AND PAN DRAINS FOR THE NEW
 WATER HEATERS. SHOW THE TYPE AND SIZE OF PANS, AND THE
 TYPE AND SIZE OF PAN DRAIN PIPES, THE DRAIN PIPE RUNS
 AND DISCHARGE LOCATIONS- SECTIONS 504.6- 504.7.2 FBC P.
  
 15) P1 & P2: LABEL THE LAVATORY IN THE WEST WATER
 RISER- SECTION 419.1 FBC P. REFER TO SECTION C404.5.1
 AND TABLE C404.5.1 FBC ENERGY CONSERVATION- THE RISER
 SHOWS THE LENGTH OF THE 1/2-INCH HOT WATER SUPPLY PIPE
 TO THE LAVATORY FROM THE WATER HEATER HAS EXCEED THE
 MAXIMUM ALLOWABLE LENGTH OF 2FT. EITHER A POINT OF USE
 WATER HEATER AT THE LAVATORY OR A RECIRCULATION PUMP
 FOR THE HOT WATER SYSTEM SHALL BE INSTALLED.
  
 16) P1 & P2: WHERE HOT WATER IS SUPPLIED TO A LAVATORY,
 THE WATER SHALL BE TEMPERED IN ACCORDANCE WITH SECTIONS
 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A MIXING VALVE
 THAT CONFORMS TO ASSE 1070. PROVIDE A PIPING DETAIL ON
 THE PLAN FOR INSTALLATION. NOTE- NOT REQUIRED FOR THE
 EAST LAVATORIES IF PROOF OF PERMIT AND INSPECTION CAN
 BE PROVIDED.
  
 17) P1: LABEL THE LAVATORY IN THE WEST WATER RISER-
 SECTION 419.1 FBC P. IT IS INCORRECTLY LABELED AS H.S.
  
 18) P1: LABEL THE TWO FIXTURES ABOVE THE FLOOR DRAINS
 IN THE VET CLINIC, AND PROVIDE A PLUMBING FIXTURE
 SCHEDULE FOR THE VET CLINIC- SECTION 107.2.1 WPB.
 INDICATE HOW THE FLOOR DRAINS ARE VENTED IN THE RISER
 DRAWING- SECTION 901.2.1 FBC P.
  
 19) P1, P2, & A1: INDICATE THE TYPE OF FINISH WALL AND
 FLOOR MATERIALS TO BE INSTALLED IN THE NEW AND
 "EXISTING" TOILET ROOMS AND AT THE MOP SINKS IN THE VET
 CLINIC AND THE COFFEE/JUICE BAR- SEE SECTIONS 310.3 FBC
 P AND 1210.2. FBC B.
  
 20) P2: THE ACCESSIBILITY DETAILS FOR THE TOILET ROOMS
 APPEAR TO INCOMPLETE AND NOT CORRECT. PLEASE REFER TO
 FBC ACC AND PROVIDED ENLARGED DRAWINGS AND DETAILS
 SHOWING:
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 21) P2: THE ACCESSIBLE DRINKING FOUNTAIN DETAILS ARE
 INCOMPLETE AND HAVE ILLEGIBLE PRINT. REFER TO SECTIONS
 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 22) P1 & P2: REFER TO SECTION 212.3 FBC ACC. SINKS AND
 INDICATE WHICH SINKS IN THE VET CLINIC AND PHARMACY
 WILL BE MADE ACCESSIBLE. PLEASE NOTE WHERE SINKS ARE
 PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF
 EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE
 SHALL COMPLY WITH 606. SHOW THE CLEAR FLOOR SPACE
 DIAGRAM AND DIMENSION AT EACH ACCESSIBLE SINK ON THE
 FLOOR PLAN, AND PROVIDE AN ELEVATION DRAWING SHOWING
 SINK HEIGHT AND KNEE AND TOE CLEARANCES- SECTIONS 606.2
 & 606.3 FBC P.
  
 23) P2: REFER TO TABLE C403.2.10 FBC EC AND PROVIDE HOT
 WATER PIPE INSULATION SPECIFICATIONS.
  
 24) P2: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1
 WPB.
  
 25) P1 & P2: CLARIFY WHAT TYPE OF PROCEDURES WILL TAKE
 PLACE IN THE VET CLINIC AND PROVIDE MEDICAL GAS PIPING
 DETAILS AND SPECIFICATIONS IF APPLICABLE- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-04-06 Cont ID  
Sent By ccole Date 2021-04-06 Time 11:58 Rev Time 0.00
Received By ccole Date 2021-04-06 Time 07:31 Sent To  
Notes
2021-04-06 11:59:322ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21020172
 4/6/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH NOTES ADDED IN CAP LETTERS FOR FURTHER
 CLARIFICATION.
  
 6) FAILED. P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE
 INDICATING THE MAKES AND MODELS OF THE ACCESSIBLE
 TOILET FIXTURES AND FAUCET, SERVICE SINK, EXAM AND
 TREATMENT ROOM SINKS, WASHING MACHINE, HOSE BIB, FLOOR
 DRAINS, AND WATER HEATER- SECTION 107.2.1 WPB. THE EXAM
 AND SERVICE SINKS WERE NOT INCLUDED IN THE SCHEDULE.
 PLEASE NOTE THAT THE SPECS FOR THE SINKS MAY BE
 DEFERRED SUBMITTALS BY REQUEST. PLEASE LABEL THE
 SERVICE SINK ON THE PLAN. IT APPEARS TO BE LOCATED BY
 THE WASHING MACHINE.
  
 7) FAILED. P-1 & P-2: PROVIDE PLUMBING RISER DRAWINGS-
 SANITARY DRAIN AND VENT, AND WATER DISTRIBUTION-
 SECTION 107.3.5.1.3 WPB. PLEASE SHOW THE LOCATIONS OF
 THE REQUIRED SHUTOFF VALVES, WATER HAMMER ARRESTORS,
 AND BACKFLOW PREVENTERS ON THE WATER RISER- SECTIONS
 604.9, 606.1, 606.2, & 608.3 FBC P. THE SANITARY ISO IS
 SHOWING DOTTED LINES FOR DRAINS AND SOLID LINES FOR
 VENTS WHICH IS NOT IN ACCORDANCE WTHE LEGEND ON P1.
  
 10) FAILED. P-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 WATER HEATER AND SUBMIT MANUFACTURER?S SPECIFICATIONS
 SHOWING THE MAKE, MODEL, GALLON SIZE, AND EFFICIENCY
 RATING- SECTION 502.1 FBC P AND TABLE C404.2 FBC EC.
 WATER HEATER SPECS NOT SUBMITTED BUT MAY BE DEFERRED BY
 REQUEST,
  
 13) FAILED. P-1 & P-2: PROVIDE AN EQUIPMENT SCHEDULE
 FOR THE NEW WASHING MACHINE INDICATING MAKE AND MODEL
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS. WASHING
 MACHINE SPECS NOT SUBMITTED BUT MAY BE DEFERRED BY
 REQUEST,
  
 A) FAILED. 1003.6 CLOTHES WASHER DISCHARGE INTERCEPTOR.
 CLOTHES WASHERS SHALL DISCHARGE THROUGH AN INTERCEPTOR
 THAT IS PROVIDED WITH A WIRE BASKET OR SIMILAR DEVICE,
 REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE INTO THE
 DRAINAGE SYSTEM OF SOLIDS 1/2 INCH OR LARGER IN SIZE,
 STRING, RAGS, BUTTONS OR OTHER MATERIALS DETRIMENTAL TO
 THE PUBLIC SEWAGE SYSTEM. PLEASE SUBMIT SPECS FOR THE
 JR SMITH SOLIDS INTERECEPTOR SHOWN IN THE FIXTURE
 SCHEDULE TO VERIFY IT IS RECOMMENDED FOR WASHING
 MACHINE DRAINAGE. THE SPECIFIED UNIT IS DESIGNED FOR
 FLOOR MOUNTING. PLEASE PROVIDE AN ENLARGED PLUMBING
 PIPING INSTALLATION DETAIL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By ccole Date 2021-02-18 Time 14:17 Rev Time 0.00
Received By ccole Date 2021-02-18 Time 12:17 Sent To  
Notes
2021-02-18 14:18:061ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21020172
 2/18/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) T-1: THE PLUMBING FIXTURE CALCULATIONS ARE
 INDICATING DRINKING FOUNTAINS WILL BE PROVIDED. PLEASE
 SHOW THE FOUNTAIN LOCATIONS ON THE ARCHITECTURAL AND
 PLUMBING PLANS, AND PROVIDE PLUMBING PIPING DETAILS-
 SECTION 107.2.1 WPB. PLEASE NOTE THAT DRINKING
 FOUNTAINS ARE NOT REQUIRED FOR AN OCCUPANT LOAD OF 15
 OR FEWER- SECTION 410.2 FBC P. IF TO BE INSTALLED
 COMPLY WITH ITEMS A & B:
  
 A) IN ACCORDANCE WITH SECTION 211.2 FBC ACC- NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 B) DRINKING FOUNTAIN ACCESSIBILITY: REFER TO SECTIONS
 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 2) A-4: PROVIDE AN ENLARGED TOILET ROOM DETAIL SHOWING
 THE LENGTH AND WIDTH OF THE ROOM, CLEAR FLOOR SPACE
 DIAGRAMS AND DIMENSIONS FOR THE WATER CLOSET AND
 LAVATORY, AND TURNING CIRCLE DIAMETER- SECTIONS 604.3,
 606.2, & 304.3 FBC ACC.
  
 3) A-4 PROVIDE REAR GRAB BAR INSTALLATION DETAILS AS
 SHOWN IN FIGURE 604.5.2, AND REAR GRAB BAR HEIGHT-
 SECTION 609.4 FBC ACC.
  
 4) A-4: SHOW THE CORRECT INSTALLATION HEIGHT OF THE
 MIRROR FROM THE FINISHED FLOOR TO THE REFLECTIVE
 SURFACE- 606.3 FBC ACC.
  
 5) ARCHITECTURAL PLANS: IN ACCORDANCE WITH SECTION
 212.3 FBC ACC, SINKS- WHERE SINKS ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE
 PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY
 WITH 606. PLEASE SHOW THE LOCATIONS OF THE ACCESSIBLE
 EXAM ROOM AND TREATMENT AREA SINKS. SHOW THE CLEAR
 FLOOR SPACE DIAGRAM AND DIMENSION AT EACH ACCESSIBLE
 SINK LOCATION- SECTION 606.2; AND PROVIDE ELEVATION
 VIEWS SHOWING THE REQUIRED SINK HEIGHTS AND KNEE AND
 TOE CLEARANCES- SECTIONS 305, 306, AND 606.3 FBC ACC.
  
 6) P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE INDICATING
 THE MAKES AND MODELS OF THE ACCESSIBLE TOILET FIXTURES
 AND FAUCET, SERVICE SINK, EXAM AND TREATMENT ROOM
 SINKS, WASHING MACHINE, HOSE BIB, FLOOR DRAINS, AND
 WATER HEATER- SECTION 107.2.1 WPB.
  
 7) P-1 & P-2: PROVIDE PLUMBING RISER DRAWINGS- SANITARY
 DRAIN AND VENT, AND WATER DISTRIBUTION- SECTION
 107.3.5.1.3 WPB. PLEASE SHOW THE LOCATIONS OF THE
 REQUIRED SHUTOFF VALVES, WATER HAMMER ARRESTORS, AND
 BACKFLOW PREVENTERS ON THE WATER RISER- SECTIONS 604.9,
 606.1, 606.2, & 608.3 FBC P.
  
 8) P-2: THE PLAN SHOWS HOT WATER SUPPLY TO THE LAVATORY
 SAINK. INDICATE HOW TEMPERED WATER WILL BE PROVIDED-
 SECTION 419.5 AND 607.1.2 FBC P.
  
 9) P-2: THE 1/2 IN. HW LINE TO THE LAVATORY IS
 EXCEEDING THE MAXIMUM LENGTH OF 2 FT. FROM THE NEAREST
 SOURCE OF HEATED WATER- TABLE C404.5.1 FBC EC. PLEASE
 NOTE: A RECIRCULATION PUMP FOR THE SYSTEM, OR A SECOND
 WATER HEATER WITHIN 2 FT. OF THE LAVATORY WILL HAVE TO
 BE INSTALLED IF HOT WATER IS TO BE SUPPLIED TO THE
 LAVATORY. SECTION 419.5 ALLOWS EITHER COLD OR TEMPERED
 WATER TO BE PROVIDED TO THE LAVATORY.
  
 10) P-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER AND SUBMIT MANUFACTURER?S SPECIFICATIONS SHOWING
 THE MAKE, MODEL, GALLON SIZE, AND EFFICIENCY RATING-
 SECTION 502.1 FBC P AND TABLE C404.2 FBC EC.
  
 11) P-1: PROVIDE A WATER HEATER INSTALLATION DETAIL
 SHOWING THE LOCATION OF THE REQUIRED EXPANSION TANK,
 SHUTOFF VALVE, CHECK VALVE, RELIEF VALVE, RELIEF VALVE
 PIPE, DRAIN PAN, AND DRAIN PAN LINE AND TERMINATION
 LOCATION- SEE SECTIONS 502, 503, & 504 FBC P.
  
 12) P-1 & P-2: PROVIDE TRAP SEAL PROTECTION FOR THE
 FLOOR DRAINS IN THE CAGES AND THE TREATMENT AREA
 SECTION 1002.4.1 FBC P.
  
 13) P-1 & P-2: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 NEW WASHING MACHINE INDICATING MAKE AND MODEL AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 A) 1003.6 CLOTHES WASHER DISCHARGE INTERCEPTOR. CLOTHES
 WASHERS SHALL DISCHARGE THROUGH AN INTERCEPTOR THAT IS
 PROVIDED WITH A WIRE BASKET OR SIMILAR DEVICE,
 REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE INTO THE
 DRAINAGE SYSTEM OF SOLIDS 1/2 INCH OR LARGER IN SIZE,
 STRING, RAGS, BUTTONS OR OTHER MATERIALS DETRIMENTAL TO
 THE PUBLIC SEWAGE SYSTEM.
  
 14) P-1 & P-2: INDICATE HOW DRAINAGE AND/OR
 CONDENSATION FROM THE FREEZER WILL BE DISPOSED OF-
 SECTION 314.2 FBC P.
  
 15) P-1 & P-2: PLEASE CLARIFY IF A MEDICAL GAS SYSTEM
 WILL BE INSTALLED FOR THE PURPOSE OF PERFORMING
 SURGERIES- SECTION 107.2.1 WPB. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS IF APPLICABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-09-15 Cont ID  
Sent By pvalenti Date 2021-09-15 Time 10:40 Rev Time 0.00
Received By pvalenti Date 2021-09-15 Time 10:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-08-27 Cont ID  
Sent By ccole Date 2021-08-27 Time 09:51 Rev Time 0.00
Received By ccole Date 2021-08-27 Time 09:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-07-20 Cont ID  
Sent By medwards Date 2021-07-20 Time 15:56 Rev Time 0.00
Received By medwards Date 2021-07-20 Time 15:53 Sent To  
Notes
2021-07-20 15:56:25THE FOLLOWING SHEETS NEED TO BE DIGITALLY SIGNED AND
 SUBMITTED BY THE DESIGNER.: E1, E2, M1, A2.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-06-09 Cont ID  
Sent By equinone Date 2021-06-09 Time 09:18 Rev Time 0.00
Received By equinone Date 2021-06-09 Time 09:18 Sent To  
Notes
2021-06-09 09:19:11PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A PHOTOCOPIED OR PRINTED
 SIGNATURE IS NOT ACCEPTABLE. PLEASE NOTICE THAT
 ELECTRONIC SIGNATURES MUST BE PART OF THE ELECTRONIC
 PDF UPLOADED. A COPY OF THE ELECTRONIC SIGNATURE IS NOT
 ACCEPTABLE. PAPER ORIGINALS MUST HAVE A WET SEAL AND
 ORIGINAL SIGNATURE FROM THE REGISTERED PROFESSIONAL.
 PER FAC 61G15-23.003,
  
 EITHER UPLOAD DIGITALLY ELECTRONICALLY SIGNED PLANS OR
 YOU CAN SUBMIT SIGNED AND SEALED PAPER ORIGINALS WITH A
 WET SIGNATURE.
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  
 ROUTED TO STORAGE. EQ
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-02 Cont ID  
Sent By medwards Date 2021-04-02 Time 05:50 Rev Time 0.00
Received By medwards Date 2021-04-02 Time 05:47 Sent To  
Notes
2021-04-02 05:51:15ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-03 Cont ID  
Sent By medwards Date 2021-02-03 Time 16:15 Rev Time 0.00
Received By medwards Date 2021-02-03 Time 16:12 Sent To  
Notes
2021-02-03 16:15:45ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop Z ZONING
Rev No 6 Status P Date 2021-09-24 Cont ID  
Sent By ckimmerl Date 2021-09-24 Time 11:05 Rev Time 0.00
Received By ckimmerl Date 2021-09-24 Time 11:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2021-09-02 Cont ID  
Sent By ckimmerl Date 2021-09-02 Time 15:38 Rev Time 0.00
Received By ckimmerl Date 2021-09-02 Time 15:38 Sent To  
Notes
2021-09-02 15:33:21PROVISO: STOREFRONT GLASS SHALL BE CLEAR OR LOW TINT.

Review Stop Z ZONING
Rev No 4 Status P Date 2021-08-05 Cont ID  
Sent By aaponte Date 2021-08-05 Time 14:33 Rev Time 0.00
Received By aaponte Date 2021-08-05 Time 14:33 Sent To  
Notes
2021-08-05 14:33:50PROVISO: STOREFRONT GLASS SHALL BE CLEAR OR LOW TINT.

Review Stop Z ZONING
Rev No 3 Status F Date 2021-06-22 Cont ID  
Sent By aaponte Date 2021-06-22 Time 16:56 Rev Time 0.00
Received By aaponte Date 2021-06-22 Time 16:56 Sent To  
Notes
2021-06-22 16:56:371. VETERINARY CLINICS AND PET GOOMING IS NOT ALLOWED
 WITHIN THE CWD-CD. A CODE AMENDMENT HAS BEEN SUBMITTED
 BY THE APPLICANT BUT THE BUILDING PERMIT CANNOT GET
 ZONING APPROVAL UNTIL THE CODE CHANGE HAS BEEN APPROVED
 BY CITY COMMISSION.
 FOR ADDTIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 2 Status F Date 2021-04-05 Cont ID  
Sent By aaponte Date 2021-04-05 Time 16:31 Rev Time 0.00
Received By aaponte Date 2021-04-05 Time 16:31 Sent To  
Notes
2021-04-05 16:36:351. VETERINARY CLINICS AND PET GOOMING IS NOT ALLOWED
 WITHIN THE CWD-CD. A CODE AMENDMENT HAS BEEN SUBMITTED
 BY THE APPLICANT BUT THE BUILDING PERMIT CANNOT GET
 ZONING APPROVAL UNTIL THE CODE CHANGE HAS BEEN APPROVED
 BY CITY COMMISSION.
 2. PLEASE SUBMIT DRAWINGS OF THE FACADE TODEPICT THE
 PROPOSED CHANGES AND THE EXISTING CONDITIONS.
 FOR ADDTIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By elevesqu Date 2021-02-18 Time 16:24 Rev Time 0.00
Received By elevesqu Date 2021-02-18 Time 16:24 Sent To  
Notes
2021-02-18 16:24:26VETRINARY CLINICS, PET GROOMING, AND BOARDING
 FACILITIES ARE NOT PERMITTED AT THIS ADDRESS WITHIN
 CLEMATIS WATERFRONT DISTRICT-CONSERVATION DISTRICT
 ZONING DISTRICT (CWD-CD) PER SECTION 94-106(13)
  
 THE USE OF PHARMACY IS PERMITTED
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]