Plan Review Details - Permit 21020165
Plan Review Stops For Permit 21020165
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-02-25 Cont ID  
Sent By rmcphers Date 2021-02-25 Time 15:48 Rev Time 0.00
Received By rmcphers Date 2021-02-25 Time 15:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By rmcphers Date 2021-02-25 Time 12:05 Rev Time 0.00
Received By rmcphers Date 2021-02-25 Time 11:07 Sent To  
Notes
2021-02-25 12:05:35SHED
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) STATE APPROVED SHED DRAWINGS DO NOT INCLUDE THE
 TIEDOWN DRAWINGS. TIEDOWN DRAWINGS PROVIDED NEED TO BE
 THE ORIGINAL ENGINEER SIGNED AND SEALED DRAWINGS.
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-25 Cont ID  
Sent By rmcphers Date 2021-02-25 Time 12:06 Rev Time 0.00
Received By rmcphers Date 2021-02-03 Time 15:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-25 Cont ID  
Sent By rmcphers Date 2021-02-25 Time 15:48 Rev Time 0.00
Received By rmcphers Date 2021-02-25 Time 15:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By rmcphers Date 2021-02-25 Time 12:05 Rev Time 0.00
Received By rmcphers Date 2021-02-25 Time 12:05 Sent To  
Notes
2021-02-25 12:06:11SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 1 Status P Date 2021-02-22 Cont ID  
Sent By kalexand Date 2021-02-22 Time 09:48 Rev Time 0.00
Received By kalexand Date 2021-02-22 Time 09:48 Sent To  
Notes
2021-02-22 11:01:38ZONING PLAN REVIEW
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. AS STAMPED ON SURVEY: SETBACKS MUST BE 5FT FROM SIDE
 AND REAR LOT LINES PURSUANT TO SEC 94-304(B)(2)
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved