|
 |
 |
 |
 |
 |
Plan Review Details - Permit 21020152
| Plan Review Stops For Permit 21020152 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-02-25 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-02-25 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-02-25 |
Time |
14:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-02-18 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-02-18 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-02-18 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2021-02-18 11:41:24 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1) NEW DISCONNECT SWITCH 2P/30 A IS NOW CONNECTED TO | | | SUPPLY SIDE OF SERVICE WHICH MAKES IT A SECOND SERVICE | | | DISCONNECTING MEANS AND IT SHOULD HAVE A RATING OF NOT | | | LESS THAN 60 AMPS. AMPACITY OF CONDUCTOR SHOULD ALSO BE | | | RATED FOR 60 AMPS. NEC 230.79(D) | | | 2) PLEASE SPECIFY INTERRUPTING CAPACITY OF NEW | | | DISCONNECTING MEANS (IT SHOULD BE AT LEAST SAME AS THE | | | NEW PV PANEL) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | ENRIQUE QUINONEZ P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-02-25 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-02-25 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-02-19 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-02-18 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-02-18 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-02-10 |
Time |
12:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-02-25 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-02-25 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-02-25 |
Time |
14:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-02-18 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-02-18 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-02-18 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |