Plan Review Details - Permit 21020125
Plan Review Stops For Permit 21020125
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-05 Cont ID  
Sent By rmcdouga Date 2021-04-05 Time 10:16 Rev Time 0.00
Received By rmcdouga Date 2021-04-05 Time 10:16 Sent To  
Notes
2021-04-05 10:15:51THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM
 ANY OPENINGS INTO THE BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-26 Cont ID  
Sent By rmcdouga Date 2021-02-26 Time 15:02 Rev Time 0.00
Received By rmcdouga Date 2021-02-26 Time 15:02 Sent To  
Notes
2021-02-26 15:06:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM
 ANY OPENINGS INTO THE BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-30 Cont ID  
Sent By jleahy Date 2021-03-30 Time 16:27 Rev Time 0.00
Received By jleahy Date 2021-03-30 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-24 Cont ID  
Sent By jleahy Date 2021-02-24 Time 16:28 Rev Time 0.00
Received By jleahy Date 2021-02-24 Time 16:26 Sent To  
Notes
2021-02-24 16:30:03ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NEED YOU SUBMIT A SIGNED PLAN FOR THE ELECTRIC
  
 NEED TO SUBMIT CUT SHEETS FOR THE GENRATOR AND TRANSFER
 SWITCH
  
 JAKE LEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-05 Cont ID  
Sent By rmcdouga Date 2021-04-05 Time 10:16 Rev Time 0.00
Received By rmcdouga Date 2021-03-24 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-23 Cont ID  
Sent By pvalenti Date 2021-03-23 Time 07:49 Rev Time 0.00
Received By pvalenti Date 2021-02-12 Time 14:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-05 Cont ID  
Sent By rmcdouga Date 2021-04-05 Time 10:16 Rev Time 0.00
Received By rmcdouga Date 2021-04-05 Time 10:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-26 Cont ID  
Sent By rmcdouga Date 2021-02-26 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2021-02-26 Time 15:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-03-22 Cont ID  
Sent By kalexand Date 2021-03-22 Time 12:36 Rev Time 0.00
Received By kalexand Date 2021-03-22 Time 12:35 Sent To I
Notes
***NONE***