| Plan Review Stops For Permit 21020114 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-02-08 |
|
|
Cont ID |
|
| Sent By |
bdolan |
Date |
2021-02-08 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2021-02-08 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2021-02-08 13:11:47 | THE FOLLOWING COMMENTS WERE SUBMITTED BY LIEUTENANT | | | BRIAN DOLAN, BUREAU OF FIRE PREVENTION, WEST PALM BEACH | | | FIRE RESCUE: | | | | | | 25.2.1.5 WHERE ADDITION OR MODIFICATION IS MADE TO AN | | | EXISTING SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE | | | NEW PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS | | | THAN 200 PSI (13.8 BAR) FOR 2 HOURS. | | | | | | THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | | | | |
|
|