Plan Review Details - Permit 21020091
Plan Review Stops For Permit 21020091
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-03-01 Cont ID  
Sent By rmcphers Date 2021-03-01 Time 15:20 Rev Time 0.00
Received By rmcphers Date 2021-03-01 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-04 Cont ID  
Sent By jleahy Date 2021-03-04 Time 16:29 Rev Time 0.00
Received By jleahy Date 2021-03-04 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-16 Cont ID  
Sent By jleahy Date 2021-02-16 Time 16:31 Rev Time 0.00
Received By jleahy Date 2021-02-16 Time 16:09 Sent To  
Notes
2021-02-16 16:33:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLANS HAVE WRONG ADDRESS ON THEM, PLEASE CORRECT TO
 REFLECT THE CORRECT ADDRESS.
  
 2) SITE LIGHTING REQUIRES A SEPARTATE PERMIT.

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-03-04 Cont ID  
Sent By jleahy Date 2021-03-04 Time 16:30 Rev Time 0.00
Received By jleahy Date 2021-03-04 Time 16:30 Sent To  
Notes
2021-03-04 16:30:39VOICE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-02-09 Cont ID  
Sent By pleduc Date 2021-02-09 Time   Rev Time 0.00
Received By pleduc Date 2021-02-09 Time 16:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-02-23 Cont ID  
Sent By ccole Date 2021-02-23 Time 12:26 Rev Time 0.00
Received By ccole Date 2021-02-23 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-04 Cont ID  
Sent By jleahy Date 2021-03-04 Time 16:30 Rev Time 0.00
Received By jleahy Date 2021-03-01 Time 18:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-01 Cont ID  
Sent By rmcphers Date 2021-03-01 Time 15:20 Rev Time 0.00
Received By rmcphers Date 2021-02-03 Time 19:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-02-16 Cont ID  
Sent By hmoser Date 2021-02-16 Time 08:39 Rev Time 0.00
Received By hmoser Date 2021-02-16 Time 08:18 Sent To  
Notes
2021-02-16 08:39:05NO MECHANICAL REVISION ON THIS PLAN.

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-02-23 Cont ID  
Sent By ccole Date 2021-02-23 Time 11:55 Rev Time 0.00
Received By ccole Date 2021-02-23 Time 11:32 Sent To  
Notes
2021-02-23 11:57:49NO PLUMBING REVISIONS INDICATED. THE REVISED SHEET
 P0.01 IS GAS PIPING SITE PLAN REVISION. GAS REVIEW HAS
 BEEN ADDED.
 CCOLE- 2/23/21

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-04 Cont ID  
Sent By jleahy Date 2021-03-04 Time 16:29 Rev Time 0.00
Received By jleahy Date 2021-03-04 Time 16:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-01 Cont ID  
Sent By rmcphers Date 2021-03-01 Time 15:20 Rev Time 0.00
Received By rmcphers Date 2021-03-01 Time 15:20 Sent To  
Notes
***NONE***