Plan Review Details - Permit 21020018
Plan Review Stops For Permit 21020018
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-01 Cont ID  
Sent By   Date 2021-12-01 Time   Rev Time 0.00
Received By jcclark Date 2021-12-01 Time 12:21 Sent To  
Notes
2021-12-01 12:23:50PLEASE CONSIDER THE FOLLOWING AS PROVISO:
 TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT DOORS.
 ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN.
 REQUIRING
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-02 Cont ID  
Sent By lmarchan Date 2021-12-02 Time 10:58 Rev Time 0.00
Received By lmarchan Date 2021-11-23 Time 07:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-18 Cont ID  
Sent By medwards Date 2021-10-18 Time 07:07 Rev Time 0.00
Received By medwards Date 2021-10-14 Time 14:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-11-24 Cont ID  
Sent By medwards Date 2021-11-24 Time 06:52 Rev Time 0.00
Received By medwards Date 2021-11-24 Time 06:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-18 Cont ID  
Sent By medwards Date 2021-10-18 Time 07:01 Rev Time 0.00
Received By medwards Date 2021-10-18 Time 07:01 Sent To  
Notes
2021-10-18 07:06:51PLEASE PROVIDE THE SPECIFICATIONS FOR THE WALKIN
 COOLER/FREEZER. FBC 107.2.1
 ENGINEER TO PROVIDE THE REQUIREMENTS LISTED BELOW:FBC M
 1102
  
 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE
 REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS,
 LOCATION LIMITATIONS, AND FIELD PRESSURE TEST
 REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS:
  
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN ACCORDANCE WITH SECTION 1103.3.
  
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
  
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND
 OCCUPANCY.
  
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
  
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
  
 6. NONFACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION 1108.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-23 Cont ID  
Sent By mpeterso Date 2021-11-23 Time 14:03 Rev Time 0.00
Received By mpeterso Date 2021-11-23 Time 14:03 Sent To  
Notes
2021-11-23 14:02:58REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED,
 ROUTED TO STORAGE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-15 Cont ID  
Sent By mpeterso Date 2021-10-15 Time 08:30 Rev Time 0.00
Received By mpeterso Date 2021-10-15 Time 08:29 Sent To  
Notes
2021-10-15 08:31:01NO SIGNATURE REQUIRED FOR REVEIW ON CONTRACTOR DRAWINGS