Plan Review Details - Permit 21011200
Plan Review Stops For Permit 21011200
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-06 Cont ID  
Sent By pvalenti Date 2021-04-06 Time 10:35 Rev Time 0.00
Received By pvalenti Date 2021-04-06 Time 10:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-02 Cont ID  
Sent By pvalenti Date 2021-04-02 Time 16:24 Rev Time 0.00
Received By pvalenti Date 2021-04-02 Time 15:55 Sent To  
Notes
2021-04-02 16:25:41PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2, PLEASE PROVIDE A FLOOR PLAN TO INDICATE
 THE LOCATION AND DIMENSIONS OF DOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By pvalenti Date 2021-02-25 Time 06:22 Rev Time 0.00
Received By pvalenti Date 2021-02-25 Time 06:14 Sent To  
Notes
2021-02-25 06:32:13****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2, PLEASE PROVIDE A FLOOR PLAN TO INDICATE
 THE LOCATION AND DIMENSIONS OF DOORS. BE SURE TO
 INDICATE WITHIN PRODUCT APPROVALS ALL OPTIONS THAT WILL
 BE USED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-02 Cont ID  
Sent By pvalenti Date 2021-04-02 Time 16:28 Rev Time 0.00
Received By pvalenti Date 2021-03-19 Time 14:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-25 Cont ID  
Sent By pvalenti Date 2021-02-25 Time 06:43 Rev Time 0.00
Received By pvalenti Date 2021-02-03 Time 17:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-02 Cont ID  
Sent By pvalenti Date 2021-04-02 Time 16:28 Rev Time 0.00
Received By pvalenti Date 2021-04-02 Time 15:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By pvalenti Date 2021-02-25 Time 06:43 Rev Time 0.00
Received By pvalenti Date 2021-02-25 Time 06:14 Sent To  
Notes
2021-02-25 06:43:19****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURE REVIEW DENIED:
  
 PLEASE PROVIDE ENGINEER OR ARCHITECT APPROVED WINDLOAD
 PRESSURES AND INDICATION IF PANIC HARDWARE IS REQUIRED
 AT THE PROPOSED DOOR LOCATIONS.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN MAIL AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  
  