Plan Review Details - Permit 21011189
Plan Review Stops For Permit 21011189
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-11 Cont ID  
Sent By pvalenti Date 2021-03-11 Time 07:45 Rev Time 0.00
Received By pvalenti Date 2021-03-11 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-11 Cont ID  
Sent By pvalenti Date 2021-02-11 Time 13:54 Rev Time 0.00
Received By pvalenti Date 2021-02-11 Time 10:45 Sent To  
Notes
2021-02-11 14:13:02PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2, PLEASE PROVIDE MORE CLARITY AND A
 NARRATIVE AS TO WHAT THE PROPOSED PLAN CHANGES ARE.
  
  
 IT APPEARS THAT SOME OF THE CHANGES ARE:
  
 1) CHANGING AN OPEN CASUAL ROOM TO AN OFFICE SPACE.
 2) CHANGING AN OPEN WALLED KITCHEN TO A STORAGE AREA.
 3) MOVING THE LOCATION OF A BIKE RACK.
 4) ADDING THE PROPANE TANK TO PLAN.
  
  
 THESE PLAN WILL REQUIRE MORE INFORMATION SUCH AS
 DETAILS FOR INTERIOR WALLS, DOORS, POSSIBLE ADJUSTMENT
 OF SPRINKLER HEADS AND ADJUSTMENT OF MECHANICAL A/C
 SYSTEM.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-05 Cont ID  
Sent By jleahy Date 2021-03-05 Time 15:18 Rev Time 0.00
Received By jleahy Date 2021-03-05 Time 15:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-12 Cont ID  
Sent By equinone Date 2021-02-10 Time 11:42 Rev Time 0.00
Received By jleahy Date 2021-02-10 Time 11:42 Sent To  
Notes
2021-02-12 13:15:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE A-4 SHOWS WORK BEING ADDED AND ELEIMINATED FOR
 ELECTRICIAN. PERMIT IS CLOSED FOR ELECTRICAL SO YOU
 NEED TO RE-OPEN THE PERMIT TO GET PLANS PASSED.
  
 THE LAST REVISION DID NOT ADDRESS THESE CHANGES.
2021-02-10 11:42:51CUSTOMER MENTIONED THAT NO ELECTRICAL WORK BEING DONE.
 HOWEVER, NEW SUBMITTED DRAWINGS SEEM TO HAVE ELECTRICAL
 MODIFICATIONS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-02-24 Cont ID  
Sent By pleduc Date 2021-02-24 Time   Rev Time 0.00
Received By pleduc Date 2021-02-24 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-02-02 Cont ID  
Sent By pleduc Date 2021-02-02 Time   Rev Time 0.00
Received By pleduc Date 2021-02-02 Time 15:28 Sent To  
Notes
2021-02-02 15:34:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE APPLICATION STATES TWO REVISIONS HOWEVER, THERE
 ARE NO CLEAR INDICATIONS OF WHERE THOSE REVISIONS ARE.
  
 ADDITIONALLY, IN THE TITLE BLOCK UNDER REVISIONS THAERE
 ARE NO DATED INDICATOR/MARKERS.
  
 PLEASE REVIEW AND CORRECT OR BETTER IDENTIFY WHAT AND
 WHERE THE REVISIONS ARE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-02-10 Cont ID  
Sent By tklarge Date 2021-02-10 Time 09:20 Rev Time 0.00
Received By tklarge Date 2021-02-10 Time 09:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 06:05 Rev Time 0.00
Received By medwards Date 2021-04-30 Time 06:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-22 Cont ID  
Sent By medwards Date 2021-04-22 Time 10:53 Rev Time 0.00
Received By medwards Date 2021-04-15 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 06:25 Rev Time 0.00
Received By medwards Date 2021-04-01 Time 12:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-22 Cont ID  
Sent By pvalenti Date 2021-03-22 Time 09:26 Rev Time 0.00
Received By pvalenti Date 2021-02-22 Time 14:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-19 Cont ID  
Sent By shill Date 2021-02-19 Time 08:09 Rev Time 0.00
Received By shill Date 2021-01-30 Time 11:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 06:04 Rev Time 0.00
Received By medwards Date 2021-05-04 Time 06:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-04-22 Cont ID  
Sent By medwards Date 2021-04-22 Time 10:51 Rev Time 0.00
Received By medwards Date 2021-04-21 Time 14:59 Sent To  
Notes
2021-04-22 10:52:48PLEASE CORRECT THE TITLES OF THE 2 NEWLY BUILT ROOMS AS
 THEY ARE NOT CONSISTENT WITH THE RECENT REVISED
 DRAWINGS. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 06:22 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 06:08 Sent To  
Notes
2021-04-08 06:23:29I SEE RETURN GRILLES FOR THE OFFICE AND THE STORAGE
 ROOM. I DO NOT SEE THE SUPPLY DUCT OR GRILLES, I ALSO
 DO NOT SEE THE CFM OF AIR GOING INTO EACH ROOM. AS
 REQUESTED BEFORE I DO NOT SEE THE NEW OUTDOOR AIR
 CALCULATIONS REQUIRED BECAUSE OF THIS CHANGE OF USE OF
 SPACE. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-03-05 Cont ID  
Sent By medwards Date 2021-03-05 Time 14:28 Rev Time 0.00
Received By medwards Date 2021-03-05 Time 14:28 Sent To  
Notes
2021-03-05 14:28:57PLEASE ADDRESS PREVIOUS COMMENT BELOW:
  
 1ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21011189
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BY REMOVING THE KITCHEN AND CASUAL AREA AND CREATING
 A STORAGE ROOM AND AN OFFICE THIS CHANGES THE
 MECHANICAL DESIGN OF THIS AREA OF THE BUILDING. PLEASE
 PROVIDE UPDATED MECHANICAL DRAWINGS SHOW THE SUPPLY
 DUCTS AND RETURNS FOR THIS AREA. PLEASE ALSO SHOW THE
 CFM?S BEING SUPPLIED TO THESE ROOMS AND THE REQUIRED
 OUTDOOR AIR CALCULATIONS FOR THE USE OF SPACES. FBC
 107.2.1, FBC M TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-02-16 Cont ID  
Sent By medwards Date 2021-02-16 Time 06:24 Rev Time 0.00
Received By medwards Date 2021-02-16 Time 06:24 Sent To  
Notes
2021-02-16 06:24:251ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21011189
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BY REMOVING THE KITCHEN AND CASUAL AREA AND CREATING
 A STORAGE ROOM AND AN OFFICE THIS CHANGES THE
 MECHANICAL DESIGN OF THIS AREA OF THE BUILDING. PLEASE
 PROVIDE UPDATED MECHANICAL DRAWINGS SHOW THE SUPPLY
 DUCTS AND RETURNS FOR THIS AREA. PLEASE ALSO SHOW THE
 CFM?S BEING SUPPLIED TO THESE ROOMS AND THE REQUIRED
 OUTDOOR AIR CALCULATIONS FOR THE USE OF SPACES. FBC
 107.2.1, FBC M TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-02-10 Cont ID  
Sent By tklarge Date 2021-02-10 Time 09:20 Rev Time 0.00
Received By tklarge Date 2021-02-10 Time 09:20 Sent To  
Notes
2021-02-10 09:22:11THERE WERE NO PLUMBING CHANGES IN THIS REVISION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 06:05 Rev Time 0.00
Received By medwards Date 2021-05-04 Time 06:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-04-22 Cont ID  
Sent By medwards Date 2021-04-22 Time 10:53 Rev Time 0.00
Received By medwards Date 2021-04-22 Time 10:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 06:24 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 06:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-05 Cont ID  
Sent By medwards Date 2021-03-05 Time 14:30 Rev Time 0.00
Received By medwards Date 2021-03-05 Time 14:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-17 Cont ID  
Sent By pvalenti Date 2021-02-17 Time 13:04 Rev Time 0.00
Received By pvalenti Date 2021-02-11 Time 10:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-19 Cont ID  
Sent By ajones Date 2021-03-19 Time 10:03 Rev Time 0.00
Received By ajones Date 2021-03-19 Time 10:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By ajones Date 2021-02-18 Time 09:53 Rev Time 0.00
Received By ajones Date 2021-02-18 Time 09:53 Sent To  
Notes
***NONE***