Plan Review Details - Permit 21011152
| Plan Review Stops For Permit 21011152 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-03-11 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-03-11 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-03-11 |
Time |
14:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-03-11 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-03-11 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-03-10 |
Time |
10:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-02-08 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2021-02-08 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2021-02-08 |
Time |
09:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2021-03-11 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-03-11 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-03-11 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2021-03-11 14:02:35 | 03/11/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2021-03-11 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-03-11 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-03-11 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2021-03-11 09:44:03 | 03/11/21 2ND REVIEW PLUMBING REVIEW**DENIED** WITH | | | COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. IT APPEARS THAT ON THE ZURN WEBSITE THIS BACKFLOW IS | | | DISCONTINUED AND IT DOES NOT SHOW IT HAS A LEAD FREE | | | CONTENT ON THE SPECIFICATION SHEET PROVIDED. IT SHALL | | | HAVE A WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR | | | LESS PER THE 2017 FBC SEC. P 605.2.1 LEAD CONTENT OF | | | DRINKING WATER PIPE AND FITTINGS. PLEASE PROVIDE | | | SUPPORTING PAPER WORK OR SEND A NEW DOCUMENTATION FOR A | | | DIFFERENT DEVICE THAT COMPLIES WITH CITY REQUIREMENTS. | | | | | | 2. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS | | | ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY | | | OF SOUTHERN CALIFORNIA (USC). | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-02-08 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2021-02-08 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2021-02-08 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2021-02-08 11:48:26 | SUBMIT SPECIFICATIONS FOR THE BACKFLOW DEVICE. THE | | | DEVICE MUST BE LEAD FREE AND BE ON THE LIST OF APPROVED | | | DEVICES FROM THE UNIVERSITY OF SOUTHERN CALIFORNIA'S | | | FOUNDATION FOR CROSS CONNECTION CONTROL AND HYDRAULIC | | | RESEARCH. |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
P |
Date |
2021-03-11 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-03-11 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-03-11 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2021-03-11 15:04:47 | PASSED PER DGRIFFITHS |
|
|
|
Account Summary | Usage Policy | Privacy Policy