Plan Review Details - Permit 21011142
Plan Review Stops For Permit 21011142
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-03-03 Cont ID  
Sent By shill Date 2021-03-03 Time 18:14 Rev Time 0.00
Received By shill Date 2021-03-03 Time 18:13 Sent To  
Notes
2021-03-03 18:15:06SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FLORIDA STATUTE 471, ENGINEERING, DOES NOT ALLOW
 ANYONE TO PERFORM STRUCTURAL ENGINEERING UNLESS
 SPECIFICALLY EXEMPTED. THAT STATUTE WAS SENT TO THE
 CONTRACTOR VIA EMAIL. AN ENGINEER IS REQUIRED TO DESIGN
 THIS PROJECT.
  
 SEE ALSO PREVIOUS LIST. ENSURE THAT THE ENGINEER
 ADDRESSES ALL COMMENTS.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
 3. ZONING/HISTORIC REVIEW REQUIRED IN NEXT REVIEW
 CYCLE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-26 Cont ID  
Sent By jwitmer Date 2021-02-26 Time 16:44 Rev Time 0.00
Received By jwitmer Date 2021-02-26 Time 16:30 Sent To  
Notes
2021-02-26 16:41:332017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 21011142
 W. P. B. PERMIT: 20050739
 ADD: 120 S. OLIVE AVE.
 CONT: PETTERSON CONSTTRUCTION GROUP
 TEL: 954-649-5986
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. FEB. 26TH/2021
 ACTION: DENIED
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 SAME COMMENTS AS THE 1ST REVIEW, CONTRACTOR/ QUALIFIER
 MUST PRINT THIER NAME SIGN THEIR NAME AND LICANSE
 NUMBER TO THE DRAWINGS THEY ARE TAKING CREDIT FOR,
 OTHERWISE AN ENGINEER WILL NEED THEIR ELECTRONIC
 SIGNATURE AND SEAL.
  
  
 1) THE REVISION DOES NOT MAKE IT CLEAR IF THE
 ADDITIONAL LANDINGS INCLUDED IN THIS REVISION ARE NEW
 WORK (REVISION- NOT PART OF THE ORIGINAL CONTRACT) OR
 CLARIFICATION OF THE EXISTING PLANS. IT WOULD APPEAR
 THE ORIGINAL PLAN WAS FOR THE LANDING OF THE 2ND FLOOR
 LANDING AND THE REVISION IS FOR LANDINGS OF THE 3RD
 FLOOR THROUGH THE 7TH FLOOR LANDINGS. THIS WOULD BE
 CONSIDERED NEW WORK AND REQUIRE THE DOLLAR AMOUNT
 BILLED TO THE OWNER. THIS SHOULD BE INCLUDED ON THE
 REVISION FORM.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE
 SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE
 AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR
 NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED
 IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN. FOR EACH TRADE THE CONTRACTOR
 RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN
 MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE
 NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY ONE
 INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A BUILDING,
 ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT ALL THESE
 TRADES UNDER ONE SHEET.
  
 3) BUILDING PROVISO: THE SUBMITTED SKETCH SHOWS BOTH
 BOLTED AND WELDED CONNECTIONS, PLEASE SHOW COMPLIANCE
 WITH WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
 WELDING CERTIFICATES WILL NEED TO BE ON THE JOBSITE AT
 TIME OF INSPECTION SO THE INSPECTOR CAN BRING THEM INTO
 THE CITY.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-02 Cont ID  
Sent By jwitmer Date 2021-02-02 Time 09:25 Rev Time 0.00
Received By jwitmer Date 2021-02-02 Time 08:45 Sent To  
Notes
2021-02-02 09:25:462017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 21011142
 W. P. B. PERMIT: 20050739
 ADD: 120 S. OLIVE AVE.
 CONT: PETTERSON CONSTTRUCTION GROUP
 TEL: 954-649-5986
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 02/2021
 ACTION: DENIED
  
 1) THE REVISION DOES NOT MAKE IT CLEAR IF THE
 ADDITIONAL LANDINGS INCLUDED IN THIS REVISION ARE NEW
 WORK (REVISION- NOT PART OF THE ORIGINAL CONTRACT) OR
 CLARIFICATION OF THE EXISTING PLANS. IT WOULD APPEAR
 THE ORIGINAL PLAN WAS FOR THE LANDING OF THE 2ND FLOOR
 LANDING AND THE REVISION IS FOR LANDINGS OF THE 3RD
 FLOOR THROUGH THE 7TH FLOOR LANDINGS. THIS WOULD BE
 CONSIDERED NEW WORK AND REQUIRE THE DOLLAR AMOUNT
 BILLED TO THE OWNER. THIS SHOULD BE INCLUDED ON THE
 REVISION FORM.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE
 SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE
 AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR
 NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED
 IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN. FOR EACH TRADE THE CONTRACTOR
 RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN
 MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE
 NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY ONE
 INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A BUILDING,
 ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT ALL THESE
 TRADES UNDER ONE SHEET.
  
 3) BUILDING PROVISO: THE SUBMITTED SKETCH SHOWS BOTH
 BOLTED AND WELDED CONNECTIONS, PLEASE SHOW COMPLIANCE
 WITH WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
 WELDING CERTIFICATES WILL NEED TO BE ON THE JOBSITE AT
 TIME OF INSPECTION SO THE INSPECTOR CAN BRING THEM INTO
 THE CITY.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-02-02 Cont ID  
Sent By pleduc Date 2021-02-02 Time   Rev Time 0.00
Received By pleduc Date 2021-02-02 Time 14:46 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-02-03 Cont ID  
Sent By fmitner Date 2021-02-03 Time 09:01 Rev Time 0.00
Received By fmittner Date 2021-02-03 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-03 Cont ID  
Sent By shill Date 2021-03-03 Time 18:17 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-02-26 Time 16:45 Rev Time 0.00
Received By ccarvaja Date 2021-02-23 Time 06:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-03 Cont ID  
Sent By lmarchan Date 2021-02-03 Time 11:50 Rev Time 0.00
Received By lmarchan Date 2021-01-28 Time 10:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-03-03 Cont ID  
Sent By shill Date 2021-03-03 Time 18:17 Rev Time 0.00
Received By shill Date 2021-03-03 Time 18:17 Sent To  
Notes
2021-03-03 18:17:22SEE BUILDING COMMENTS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-02-26 Cont ID  
Sent By jwitmer Date 2021-02-26 Time 16:35 Rev Time 0.00
Received By jwitmer Date 2021-02-26 Time 16:34 Sent To  
Notes
2021-02-26 16:35:00SEE BUILDING REVIEW NOTES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-02 Cont ID  
Sent By jwitmer Date 2021-02-02 Time 09:18 Rev Time 0.00
Received By jwitmer Date 2021-02-02 Time 08:45 Sent To  
Notes
2021-02-02 09:18:18THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS, EACH SHEET. PLEASE PRINT YOUR NAME, SIGN
 YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN. FOR EACH TRADE THE CONTRACTOR
 RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN
 MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE
 NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY ONE
 INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A BUILDING,
 ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT ALL THESE
 TRADES UNDER ONE SHEET.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-02-03 Cont ID  
Sent By elevesqu Date 2021-02-03 Time 09:01 Rev Time 0.00
Received By fmittner Date 2021-02-03 Time 09:01 Sent To  
Notes
***NONE***