Plan Review Details - Permit 21011112
Plan Review Stops For Permit 21011112
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-12-23 Cont ID  
Sent By ccole Date 2021-12-23 Time 13:52 Rev Time 0.00
Received By ccole Date 2021-12-23 Time 13:05 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-12-03 Cont ID  
Sent By ccole Date 2021-12-03 Time 13:21 Rev Time 0.00
Received By ccole Date 2021-12-03 Time 13:21 Sent To  
Notes
2021-12-03 13:22:153RD REVIEW FBC-2017 RES.
 PERMIT- 21011112
 12/3/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 201
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED RISER SHOWS UNDERSIZED PIPING AND
 INACCURATE LOAD. PLEASE MAKE THESE CORRECTIONS PER
 SECTION 107.3.5.3 WPB, AND CHAPTER 24 FBC RES.
 A) INCREASE TOTAL LOAD FOR LOW PRESSURE REG A- TO
 992,000 BTU?S
 B) INCREASE TOTAL LOAD FOR LOW PRESSURE REG B- TO
 398,000 BTU?S
 C) INCREASE THE PIPE SIZES DOWNSTREAM OF REGULATORS
 BASED ON THE PIPE SIZING TABLES LISTED ON THE RISER.
 OPTION 2 WOULD BE TO RELOCATE THE LOW PRESSURE REG A SO
 IT IS SERVING ONLY THE INTERIOR APPLIANCES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-11-19 Cont ID  
Sent By ccole Date 2021-11-19 Time 17:27 Rev Time 0.00
Received By ccole Date 2021-11-19 Time 17:27 Sent To  
Notes
2021-11-19 17:30:372ND REVIEW FBC-2017 RES.
 PERMIT- 21011112
 11/19/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 201
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE FIREPLACE AND GAS PIPING WERE REMOVED FROM THE
 RESUBMITTED RISER DRAWING. PLEASE RESUBMIT THE CORRECT
 RISER DRAWING- SECTION 107.2.1 & 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-22 Cont ID  
Sent By lcrespo Date 2021-02-22 Time 13:42 Rev Time 0.00
Received By ccole Date 2021-02-22 Time 12:46 Sent To  
Notes
2021-02-22 13:43:081ST REVIEW FBC-2017 RES.
 PERMIT- 21011112
 2/22/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 201
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $720.00 JOB VALUE DOES NOT APPEAR TO INCLUDE THE
 NEW FIREPLACE. PLEASE PROVIDE THE MAKE AND MODEL OF THE
 UNIT ON THE PLANS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 107.2.1 & 109.3 WPB. PLEASE
 CLARIFY IF IT IS A VENTED OR VENTLESS FIREPLACE, AND
 PROVIDE COMBUSTION AIR CALCULATIONS- SECTIONS G2407.1,
 G2427.1, G2435.1 FBC RES.
  
 2) THE CONTRACTOR OF RECORD SHALL PROVIDE HIS/HER TITLE
 BLOCK AND SIGNATURE ON THE FLOOR PLAN DRAWING- SECTION
 107.2.1 WPB.
  
 3) THE FLOOR PLAN DRAWING SHOWS THE GENERATOR AND POOL
 HEATER LOCATED CLOSE TO OPERABLE OPENINGS AT THE
 KITCHEN. PLEASE NOTE A MINIMUM 10 FT. CLEARANCE IS
 REQUIRED PER SECTION R303.5.1 FBC RES. BOTH THE
 GENERATOR AND POOL HEATER WERE LABELED AS FUTURE
 INSTALLATIONS ON THE MAIN APPROVED PLAN UNDER PERMIT
 18060620. PLEASE LABEL THEM AS FUTURE AND UNDER
 SEPARATE PERMIT ON THE REVISED PLAN- SECTION 107.2.1
 WPB.
  
 4) THE BBQ GRILL APPEARS TO BE UNDER A PATIO ROOF WHICH
 MAY REQUIRE INSTALLATION OF AN EXHAUST HOOD PER THE
 MANUFACTURER'S SPECIFICATION. PLEASE SUBMIT SPECS FOR
 THE UNIT AND SHOW CLEARANCE DISTANCES TO OPERABLE
 OPENINGS ON THE PLAN- SECTIONS R303.5.1 AND G2447.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-12-23 Time   Rev Time 0.00
Received By aoliver Date 2021-12-17 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-12-03 Time   Rev Time 0.00
Received By aoliver Date 2021-11-29 Time 06:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-11-19 Time   Rev Time 0.00
Received By lmarchan Date 2021-11-12 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-02-22 Time   Rev Time 0.00
Received By lmarchan Date 2021-02-08 Time 09:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 2021-12-23 Cont ID  
Sent By ccole Date 2021-12-23 Time 13:52 Rev Time 0.00
Received By ccole Date 2021-12-23 Time 13:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-12-03 Cont ID  
Sent By ccole Date 2021-12-03 Time 12:18 Rev Time 0.00
Received By ccole Date 2021-12-03 Time 12:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-11-19 Cont ID  
Sent By ccole Date 2021-11-19 Time 17:27 Rev Time 0.00
Received By ccole Date 2021-11-19 Time 17:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-02-22 Cont ID  
Sent By ccole Date 2021-02-22 Time 13:44 Rev Time 0.00
Received By ccole Date 2021-02-22 Time 12:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-02-08 Cont ID  
Sent By medwards Date 2021-02-08 Time 09:44 Rev Time 0.00
Received By medwards Date 2021-02-08 Time 09:42 Sent To  
Notes
***NONE***