Plan Review Details - Permit 21011007
Plan Review Stops For Permit 21011007
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-05-05 Cont ID  
Sent By jwitmer Date 2021-05-05 Time 09:28 Rev Time 0.00
Received By jwitmer Date 2021-05-04 Time 09:30 Sent To  
Notes
2021-05-04 17:19:10ASBETOS LETTER UPLOADED 5/05/2021. JW

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By jwitmer Date 2021-03-19 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2021-03-19 Time 09:58 Sent To  
Notes
2021-03-19 10:59:58TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-05-04 Cont ID  
Sent By jwitmer Date 2021-05-04 Time 11:13 Rev Time 0.00
Received By jwitmer Date 2021-05-04 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By jwitmer Date 2021-03-19 Time 10:58 Rev Time 0.00
Received By jwitmer Date 2021-03-19 Time 09:58 Sent To  
Notes
2021-03-19 10:48:38WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21011007
 ADD: 630 S. SAPODILLA AVE. # 315
 CONT: BUILDING DESIGN INC.
 TEL: 561-612-4300
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 19, 2021
 ACTION: DENIED
  
 1) THE FLOOR PLAN SUBMITTED BY BUILDING DESIGN INC. MAY
 HAVE THE COMPANY NAME ON THE PLAN BUT NOT THE QUALIFIER
 OF THE COMPANY. THE CONTRACTOR (QUALIFIER) THAT CREATED
 / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES).
 IF A NEW FLOOR PENETRATION IS MADE FOR THE FUTURE
 SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE WITH THE
 2020 FBC-B SECTION 714.5.1.2. THROUGH-PENETRATIONS
 FIRESTOP SYSTEMS (HORIZONTAL ASSEMBLIES). THROUGH
 PENETRATIONS SHALL BE PROTECTED BY A THROUGH
 PENETRATION FIRESTOP SYSTEM INSTALLED IN ACCORDANCE
 WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL HAVE AN F
 RATING / T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
 THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
  
 4) MISSING INFORMATION ON PLANS.
 4A) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 4B) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-17 Cont ID  
Sent By pleduc Date 2021-03-17 Time   Rev Time 0.00
Received By pleduc Date 2021-03-17 Time 14:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 17:26 Rev Time 0.00
Received By jleahy Date 2021-05-03 Time 08:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-23 Cont ID  
Sent By jesmith Date 2021-03-23 Time 14:25 Rev Time 0.00
Received By jesmith Date 2021-03-23 Time 14:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-05-11 Cont ID  
Sent By jesmith Date 2021-05-11 Time 14:14 Rev Time 0.00
Received By jesmith Date 2021-05-11 Time 14:08 Sent To  
Notes
2021-05-11 14:13:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21011007 630 S SAPODILLA AVE # 315
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 NOTE: PER WPB FBC 105.1, A PLUMBING SUB-PERMIT IS
 REQUIRED.
  
 1.NEW COMMENT: FALLS UNDER THE RULES OF THE FAIR
 HOUSING ACT. IN ACCORDANCE WITH WPB FBC 107.2.1,
 INDICATE ON THE FLOOR PLAN, COMPLIANCE WITH THE FAIR
 HOUSING ACT, INDICATING TYPE OF BATHROOM(S), (TYPE A,
 TYPE B), IN ACCORDANCE WITH GUIDELINES UNDER
 REQUIREMENT 7, INCLUDING CLEAR FLOOR SPACE AND
 MANEUVERING. IF NON-COMPLIANT YOU MAY SUBMIT A REQUEST
 FOR WAIVER IN THE FORM OF A LETTER SHOWN BELOW. THIS
 SHOULD BE SIGNED BY BOTH PARTIES (DESIGNER AND OWNER),
 BUT ONLY THE OWNER?S SIGNATURE NEEDS TO BE NOTARIZED.
  
 PROJECT ADDRESS: ______________________________________
 _____________________
 PERMIT NUMBER: ________________________
 THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE
 PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS
 OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER
 AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF
 SALE IF SO REQUESTED BY THE BUYER.
  
 SIGNATURE OF DESIGNER: ______________________________
 PRINTED NAME OF DESIGNER: ___________________________
  
 SIGNATURE OF OWNER: ________________________________
 PRINTED NAME OF OWNER: _____________________________
 NOTARY FOR OWNER?S SIGNATURE:
 STATE OF FLORIDA, COUNTY OF PALM BEACH
 THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME
 THIS _____ DAY OF ________, 20__ BY
 ___________________________ WHO IS PERSONALLY KNOWN TO
 ME OR WHO HAS PRODUCED: ___________________________ AS
 IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH.
 NOTARY SIGNATURE ___________________________________
 NOTARY PRINTED NAME ________________________________
  
  
  
  
 2.1 SECOND REQUEST: PER WPB FBC 107.3.4.3 CERTIFICATION
 BY CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DREW THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. THE
 PLUMBING CONTRACTOR SHALL PROVIDE A DRAWING(S) WITH
 PRINTED NAME, SIGNATURE AND LICENSE NUMBER.
  
 3.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE THE
 FOLLOWING: 1) A SANITARY AND WATER RISER DIAGRAM
 ADDRESSING NEW DOUBLE VANITY AND 2) PROVIDE WALL, CURB,
 LINER AND DRAIN DETAIL SHOWING COMPLIANCE WITH FBC PL
 421.5.2.1 THROUGH 421.5.2.6. SEE BELOW.
 421.5.1SUPPORT.
 FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE
 LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE.
 421.5.2SHOWER LINING.
 FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE
 PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE
 LINED AND MADE WATER TIGHT UTILIZING MATERIAL COMPLYING
 WITH SECTIONS 421.5.2.1 THROUGH 421.5.2.6. SUCH LINERS
 SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 INCHES (51
 MM) ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE
 RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT
 TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING, AND
 SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS
 THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD.
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO
 THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A
 WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET. THE
 COMPLETED LINER SHALL BE TESTED IN ACCORDANCE WITH
 SECTION 312.9.
 421.5.2.1PVC SHEETS.
 PLASTICIZED POLYVINYL CHLORIDE (PVC) SHEETS SHALL MEET
 THE REQUIREMENTS OF ASTM D4551. SHEETS SHALL BE JOINED
 BY SOLVENT WELDING IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 421.5.2.2CHLORINATED POLYETHYLENE (CPE) SHEETS.
 NONPLASTICIZED CHLORINATED POLYETHYLENE SHEET SHALL
 MEET THE REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE
 JOINED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
 421.5.2.3SHEET LEAD.
 SHEET LEAD SHALL WEIGH NOT LESS THAN 4 POUNDS PER
 SQUARE FOOT (19.5 KG/M2) AND SHALL BE COATED WITH AN
 ASPHALT PAINT OR OTHER APPROVED COATING. THE LEAD SHEET
 SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER
 THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT
 FELT OR AN EQUIVALENT. SHEET LEAD SHALL BE JOINED BY
 BURNING.
 421.5.2.4SHEET COPPER.
 SHEET COPPER SHALL CONFORM TO ASTM B152 AND SHALL WEIGH
 NOT LESS THAN 12 OUNCES PER SQUARE FOOT (3.7 KG/M2).
 THE COPPER SHEET SHALL BE INSULATED FROM CONDUCTING
 SUBSTANCES OTHER THAN THE CONNECTING DRAIN BY 15-POUND
 (6.80 KG) ASPHALT FELT OR AN EQUIVALENT. SHEET COPPER
 SHALL BE JOINED BY BRAZING OR SOLDERING.
 421.5.2.5SHEET-APPLIED, LOAD-BEARING, BONDED,
 WATERPROOF MEMBRANES.
 SHEET-APPLIED, LOAD-BEARING, BONDED, WATERPROOF
 MEMBRANES SHALL MEET REQUIREMENTS OF ANSI A118.10 AND
 SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
 421.5.2.6LIQUID-TYPE, TROWEL-APPLIED, LOAD-BEARING,
 BONDED WATERPROOF MATERIALS.
 LIQUID-TYPE, TROWEL-APPLIED, LOAD-BEARING, BONDED
 WATERPROOF MATERIALS SHALL MEET THE REQUIREMENTS OF
 ANSI A118.10 AND SHALL BE APPLIED IN ACCORDANCE WITH
 THE MANUFACTURER'S INSTRUCTIONS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
 PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED
 WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE
 NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER
 PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE
 BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO
 ISSUANCE OF A PERMIT.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21011007 630 S SAPODILLA AVE # 315

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-23 Cont ID  
Sent By jesmith Date 2021-03-23 Time 14:17 Rev Time 0.00
Received By jesmith Date 2021-03-23 Time 13:41 Sent To  
Notes
2021-03-23 14:17:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21011007 630 S SAPODILLA AVE # 315
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
  
 1.PER WPB FBC 107.3.4.3 CERTIFICATION BY CONTRACTOR.
 PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER
 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL,
 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR
 THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL
 ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER
 THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. THE PLUMBING CONTRACTOR
 SHALL PROVIDE A DRAWING(S) WITH PRINTED NAME, SIGNATURE
 AND LICENSE NUMBER.
  
 2.PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING:FLOOR PLAN
 OF BATHROOMS, SANITARY AND WATER RISER DIAGRAM
 ADDRESSING NEW DOUBLE VANITY AND PROVIDE WALL, CURB,
 LINER AND DRAIN DETAIL SHOWING COMPLIANCE WITH FBC PL
 421.5.2.1 THROUGH 421.5.2.6.
 421.5.1SUPPORT.
 FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE
 LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE.
 421.5.2SHOWER LINING.
 FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE
 PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE
 LINED AND MADE WATER TIGHT UTILIZING MATERIAL COMPLYING
 WITH SECTIONS 421.5.2.1 THROUGH 421.5.2.6. SUCH LINERS
 SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 INCHES (51
 MM) ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE
 RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT
 TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING, AND
 SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS
 THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD.
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO
 THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A
 WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET. THE
 COMPLETED LINER SHALL BE TESTED IN ACCORDANCE WITH
 SECTION 312.9.
 421.5.2.1PVC SHEETS.
 PLASTICIZED POLYVINYL CHLORIDE (PVC) SHEETS SHALL MEET
 THE REQUIREMENTS OF ASTM D4551. SHEETS SHALL BE JOINED
 BY SOLVENT WELDING IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS.
 421.5.2.2CHLORINATED POLYETHYLENE (CPE) SHEETS.
 NONPLASTICIZED CHLORINATED POLYETHYLENE SHEET SHALL
 MEET THE REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE
 JOINED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
 421.5.2.3SHEET LEAD.
 SHEET LEAD SHALL WEIGH NOT LESS THAN 4 POUNDS PER
 SQUARE FOOT (19.5 KG/M2) AND SHALL BE COATED WITH AN
 ASPHALT PAINT OR OTHER APPROVED COATING. THE LEAD SHEET
 SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER
 THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT
 FELT OR AN EQUIVALENT. SHEET LEAD SHALL BE JOINED BY
 BURNING.
 421.5.2.4SHEET COPPER.
 SHEET COPPER SHALL CONFORM TO ASTM B152 AND SHALL WEIGH
 NOT LESS THAN 12 OUNCES PER SQUARE FOOT (3.7 KG/M2).
 THE COPPER SHEET SHALL BE INSULATED FROM CONDUCTING
 SUBSTANCES OTHER THAN THE CONNECTING DRAIN BY 15-POUND
 (6.80 KG) ASPHALT FELT OR AN EQUIVALENT. SHEET COPPER
 SHALL BE JOINED BY BRAZING OR SOLDERING.
 421.5.2.5SHEET-APPLIED, LOAD-BEARING, BONDED,
 WATERPROOF MEMBRANES.
 SHEET-APPLIED, LOAD-BEARING, BONDED, WATERPROOF
 MEMBRANES SHALL MEET REQUIREMENTS OF ANSI A118.10 AND
 SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
 421.5.2.6LIQUID-TYPE, TROWEL-APPLIED, LOAD-BEARING,
 BONDED WATERPROOF MATERIALS.
 LIQUID-TYPE, TROWEL-APPLIED, LOAD-BEARING, BONDED
 WATERPROOF MATERIALS SHALL MEET THE REQUIREMENTS OF
 ANSI A118.10 AND SHALL BE APPLIED IN ACCORDANCE WITH
 THE MANUFACTURER?S INSTRUCTIONS.
  
 3. SEE BUILDING EXAMINER?S COMMENT. POST TENSION SLAB/
 NEW HOLES. THE PLAN IS SILENT AS IF THE LOCATION OF THE
 EXISTING TUB DRAIN IS GOING TO BE REUSED IN THE SAME
 LOCATION. IF NOT, THEN THE FLOOR SLAB WILL NEED TO BE
 X-RAYED TO FIND THE POST TENSION CHORD LOCATIONS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 4. SEE BUILDING EXAMINER?S COMMENT.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES).
 IF A NEW FLOOR PENETRATION IS MADE FOR THE FUTURE
 SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE WITH THE
 2020 FBC-B SECTION 714.5.1.2. THROUGH-PENETRATIONS
 FIRESTOP SYSTEMS (HORIZONTAL ASSEMBLIES). THROUGH
 PENETRATIONS SHALL BE PROTECTED BY A THROUGH
 PENETRATION FIRESTOP SYSTEM INSTALLED IN ACCORDANCE
 WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL HAVE AN F
 RATING / T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
 THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
 PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED
 WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE
 NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER
 PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE
 BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO
 ISSUANCE OF A PERMIT.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21011007 630 S SAPODILLA AVE # 315

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 17:26 Rev Time 0.00
Received By jleahy Date 2021-05-13 Time 17:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By jwitmer Date 2021-03-19 Time 10:58 Rev Time 0.00
Received By jwitmer Date 2021-03-19 Time 09:58 Sent To  
Notes
2021-03-19 10:58:49SEE BUILDING PLAN REVIEW.