Plan Review Details - Permit 21010986
Plan Review Stops For Permit 21010986
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-02-03 Cont ID  
Sent By equinone Date 2021-02-03 Time 13:36 Rev Time 0.00
Received By equinone Date 2021-02-03 Time 13:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-02-25 Cont ID  
Sent By ccole Date 2021-02-25 Time 11:49 Rev Time 0.00
Received By ccole Date 2021-02-25 Time 11:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-02 Cont ID  
Sent By ccole Date 2021-02-02 Time 15:56 Rev Time 0.00
Received By ccole Date 2021-02-02 Time 15:12 Sent To  
Notes
2021-02-02 15:57:041ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21010986
 2/2/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS RISER DRAWING IN ACCORDANCE WITH
 SECTION 107.3.5.1.5 WPB. PROVIDE THE FOLLOWING
 INFORMATION ON THE RISER PER THE FBC FG:
 A) TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM- SECTION
 402.2
 B) TOTAL DEVELOPED LENGTH FROM THE METER TO THE MOST
 REMOTE OUTLET- 402.4.1.
 C) DELIVERY PRESSURE AT THE METER- 401.7.
 D) PIPE SIZING TABLES OR SIZING METHOD USED- 402.3
 E) MAIN SUPPLY PIPE SIZE AND BRANCH PIPE POINTS OF
 CONNECTION- 401.4 & 402.2. THE DETAIL ON SHEET P101
 APPEARS TO SHOW THE 1 IN. METALLIC DOAS SUPPLY PIPE
 CONNECTING TO THE EXISTING 1-1/2 IN. PIPE WHICH IS
 CURRENTLY SUPPLYING A LOAD OF 2722 CFH. BASED ON TABLE
 402.4(5) FBC FG THE 1-1/2 IN PIPE IS UNDERSIZED FOR THE
 NEW LOAD OF 3322 CFH AT A TOTAL DEVELOPED LENGTH OF 300
 FT.
  
 2) PROVIDE A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-15 Cont ID  
Sent By lmarchan Date 2021-04-15 Time 16:16 Rev Time 0.00
Received By lmarchan Date 2021-04-08 Time 10:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-02 Cont ID  
Sent By lmarchan Date 2021-03-02 Time 14:19 Rev Time 0.00
Received By lmarchan Date 2021-02-24 Time 12:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-05 Cont ID  
Sent By lmarchan Date 2021-02-05 Time 09:24 Rev Time 0.00
Received By lmarchan Date 2021-01-27 Time 07:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-04-09 Cont ID  
Sent By medwards Date 2021-04-09 Time 07:28 Rev Time 0.00
Received By medwards Date 2021-04-09 Time 07:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 07:27 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 07:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-29 Cont ID  
Sent By medwards Date 2021-01-29 Time 15:19 Rev Time 0.00
Received By medwards Date 2021-01-29 Time 15:01 Sent To  
Notes
2021-01-29 15:19:191ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21010986
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE EQUIPMENT SIZING CALCULATIONS FOR
 THIS DOAS UNIT. FBC EC C403.2.1
  
 2) SHEET M101: PLEASE INCLUDE KEY NOTES 7 & 8 ON THIS
 SHEET. FBC 107.2.1
  
 3) SHEET M201: THERE IS A LOT OF INFORMATION ON THIS
 SHEET THAT DOES NOT APPLY FOR THE PERMIT APPLIED FOR ON
 THIS PROJECT. PLEASE REMOVE ALL INFORMATION THAT DOES
 NOT PERTAIN TO THIS PERMIT. FBC 107.2
  
 4) SHEET M102: THE DEMO ROOF PLAN AND THE NEW WORK ROOF
 PLAN DO NOT LINE UP. PLEASE MAKE SURE THE LOCATIONS
 MATCH. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-02-25 Cont ID  
Sent By ccole Date 2021-02-25 Time 11:27 Rev Time 0.00
Received By ccole Date 2021-02-25 Time 11:00 Sent To  
Notes
2021-02-25 11:28:08CONDENSATE PIPING FOR NEW ROOFTOP UNITS TO BE INSTALLED
 BY MECHANICAL CONTRACTOR.
 CCOLE- 2/25/21

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-02 Cont ID  
Sent By ccole Date 2021-02-02 Time 16:00 Rev Time 0.00
Received By ccole Date 2021-02-02 Time 14:17 Sent To  
Notes
2021-02-02 16:00:361ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21010986
 2/2/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 SHEET P001 & P101: PROVIDE THE SLOPE OF THE DOAS
 CONDENSATE PIPE AND PROVIDE PIPE SUPPORT DETAILS-
 SECTION 314.2.1 AND TABLE 308.5 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-05-07 Cont ID  
Sent By medwards Date 2021-05-07 Time 16:59 Rev Time 0.00
Received By medwards Date 2021-05-07 Time 16:59 Sent To  
Notes
2021-05-07 17:02:45ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-04-14 Cont ID  
Sent By medwards Date 2021-04-09 Time 07:30 Rev Time 0.00
Received By medwards Date 2021-04-09 Time 07:28 Sent To  
Notes
2021-04-09 07:32:04 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By medwards Date 2021-02-17 Time 08:55 Rev Time 0.00
Received By medwards Date 2021-02-17 Time 08:53 Sent To  
Notes
2021-02-17 08:56:06ORIGINAL SIGNED AND SEALED DOUCUMENTS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-27 Cont ID  
Sent By medwards Date 2021-01-27 Time 07:10 Rev Time 0.00
Received By medwards Date 2021-01-27 Time 07:09 Sent To  
Notes
2021-01-27 07:11:39ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop Z ZONING
Rev No 3 Status P Date 2021-04-15 Cont ID  
Sent By eschneid Date 2021-04-15 Time 15:59 Rev Time 0.50
Received By eschneid Date 2021-04-15 Time 14:27 Sent To  
Notes
2021-04-15 16:00:44BASED ON INFORMATION PROVIDED, THE NEW MECHANICAL
 EQUIPMENT SHOULD MEET SCREENING REQUIREMENT.
 IF IT DOES NOT, THE EQUIPMENT MUST BE PAINTED IN A SKY
 PATTERN CONSISTENT WITH OTHER ROOFTOP UNITS IN
 THE PALM BEACH OUTLETS.

Review Stop Z ZONING
Rev No 2 Status F Date 2021-03-02 Cont ID  
Sent By eschneid Date 2021-03-02 Time 13:21 Rev Time 0.50
Received By eschneid Date 2021-03-02 Time 11:47 Sent To  
Notes
2021-03-02 13:28:43FAILED
  
 REPEAT COMMENT - THE PALM BEACH OUTLETS REQUIRE THAT
 ROOFTOP MECHANICAL EQUIPMENT MUST BE SCREENED. PROVIDE
 SIGHTLINE DRAWINGS OR OTHER VERIFICATION THAT THE NEW
 ROOFTOP EQUIPMENT WILL BE SCREENED FROM THE PROPERTY
 LINES TO THE EAST AND SOUTH SIDES OF THE BUILDING.
  
 THANK YOU FOR PROVIDING PHOTOGRAPHS OF THE ROOF AND THE
 BUILDING; HOWEVER, NO INFORMATION WAS PROVIDED ON THE
 HEIGHT OF THE EQUIPMENT TO VERIFY THAT IT IS A LOWER
 HEIGHT THAN THE EXISTING PARAPET WALLS (WHICH WOULD BE
 SCREENED). IF THE EQUIPMENT IS TALLER THAN THE PARAPET
 WALLS, THEN YOU NEED TO PROVIDE EVIDENCE THAT THE
 LOCATION OF THE EQUIPMENT IN RELATIONSHIP TO THE EDGE
 OF THE BUILDING AND THE PARAPET WALLS VERIFIES THAT IT
 WOULD BE SCREENED. PHOTOS CAN SHOW THIS IF YOU HAVE
 INSTALLED A MOCK UP ON THE ROOF IN THE EXACT LOCATION
 OF THE NEW EQUIPMENT. THE PHOTOS, NOT EVEN SHOWING
 WHERE THE NEW EQUIPMENT IS PROPOSED, PROVIDE NO
 VERIFICATION THAT THE NEW EQUIPMENT WILL COMPLY WITH
 THE SCREENING REQUIREMENTS. YOU HAVE NOT PROVIDED PROOF
 THAT THE NEW ROOFTOP EQUIPMENT WILL MEET THE SCREENING
 REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-02-04 Cont ID  
Sent By eschneid Date 2021-02-04 Time 11:38 Rev Time 0.25
Received By eschneid Date 2021-02-04 Time 11:38 Sent To  
Notes
2021-02-04 11:43:47FAILED
  
 THE PALM BEACH OUTLETS REQUIRE THAT ROOFTOP MECHANICAL
 EQUIPMENT MUST BE SCREENED. PROVIDE SIGHTLINE DRAWINGS
 OR OTHER VERIFICATION THAT THE NEW ROOFTOP EQUIPMENT
 WILL BE SCREENED FROM THE PROPERTY LINES TO THE EAST
 AND SOUTH SIDES OF THE BUILDING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  