Plan Review Details - Permit 21010946
Plan Review Stops For Permit 21010946
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-01 Cont ID  
Sent By cthroop Date 2021-04-01 Time 06:43 Rev Time 0.00
Received By cthroop Date 2021-03-31 Time 15:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By cthroop Date 2021-03-09 Time 15:08 Rev Time 0.00
Received By cthroop Date 2021-03-08 Time 08:22 Sent To  
Notes
2021-03-09 15:14:04PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: PROVISO ON PLAN PAGE S2 SEPERATE PERMIT
 REQUIRED FOR SITE WALLS.
  
 1. DEMO PLAN PAGE A-001 SHOWS FRONT DOOR TO BE REMOVED.
 PROPOSED FLOOR PLAN S1.0 DOES NOT SHOW INSTALLATION OF
 NEW DOOR. PLEASE CLARIFY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE DESIGN WIND PRESSURES FOR FRONT DOOR
 OPENING.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By cthroop Date 2021-02-18 Time 09:34 Rev Time 0.00
Received By cthroop Date 2021-02-17 Time 06:58 Sent To  
Notes
2021-02-18 09:36:54PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THESE COMMENTS APPLY TO PERMITS 21010938 AND 21010946
  
 NOTICE: THE SOW FOR PERMIT 21010938 IS THE DEMOLITION
 OF AN EXISTING POOL, STEPS AND WOODEN FENCE.
 PLANS SUBMITTED FOR REVIEW INCLUDE THE REMOVAL OF
 WINDOWS AND EXT. DOORS, THE RE-LOCATION OF AN EXISTING
 A/C UNIT, THE INSTALLATION OF A OUTDOOR SHOWER, A NEW
 POOL, NEW POOL DECK, NEW GENERATOR,NEW FRONT ENTRY DOOR
 AND NEW SLIDING GLASS DOORS WITH STRUCTURAL
 MODIFICATIONS OF EXISTING LOAD CARRYING BEAM.
  
 1. A PERMIT TO REMOVE AN EXISTING POOL WILL ONLY BE
 ISSUED IF APPLICATION IS MADE FOR A NEW POOL, INCLUDING
 ALL DESIGN REQUIREMENTS OR THE EXISTING POOL WILL BE
 FILLED IN. (I HAVE UPLOADED THE CITY'S INSTRUCTIONS FOR
 REMOVAL AND FILL-IN OF EXISTING POOL). BASED ON THE
 INFORMATION PROVIDED IT APPEARS A NEW POOL WILL BE
 INSTALLED.
  
 2. EXTERIOR DOORS AND WINDOWS MAY NOT BE REMOVED
 WITHOUT A PLAN FOR MODIFICATION OF OPENINGS AND PRODUCT
 APPROVALS REVIEWED AND APPROVED BY THE DESIGNER.
  
 3. THERE IS A COMPANION PERMIT APPLICATION, 21010946
 FOR THIS PROPERTY THAT HAS SIMILAR PLANS AND INCLUDES
 THE INSTALLATION OF SITE WALLS.
  
 RECOMMENDATION:
  
 4. THE DEMO OF THE POOL, STEPS AND WOODEN FENCE SHOULD
 REMAIN AS THE SOW FOR PERMIT 21010938. TYPE OF PERMIT
 SHOULD BE CHANGED FROM RES MISC. TO DEMO.
 AS STATED ABOVE, THE PERMIT TO DEMO AN EXISTING POOL
 WILL NOT BE ISSUED UNTIL APPLICATION IS MADE FOR A NEW
 POOL.
  
 5. ALL OTHER WORK UNDER PERMIT 21010938 SHOULD BE
 REMOVED FROM THE PLANS AND INCLUDED UNDER PERMIT
 21010946.
  
 6. SEPERATE PERMITS ARE REQUIRED FOR THE NEW POOL, THE
 NEW GENERATOR (W/SEPERATE GAS PERMIT) AND SITE WALLS.
  
 7. SUBMIT PLANS FOR STRUCTURAL MODIFICATION OF BEAM,
 REPLACEMENT OF WINDOWS AND DOORS (INCLUDE PRODUCT
 APPROVALS) PLUMBING (OUTDOOR SHOWER), ELECTRICAL AND
 MECHANICAL (RE-LOCATION OF A/C UNIT) UNDER THIS PERMIT
 NUMBER.
  
 FEEL FREE TO CALL TO DISCUSS.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-04-01 Cont ID  
Sent By cthroop Date 2021-04-01 Time 17:06 Rev Time 0.00
Received By cthroop Date 2021-03-31 Time 15:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By cthroop Date 2021-03-09 Time 15:21 Rev Time 0.00
Received By cthroop Date 2021-03-09 Time 14:44 Sent To  
Notes
2021-03-09 15:34:18PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: PROVISO ON PLAN SHEET S2-SEPERATE ELECTRICAL
 AND FUEL GAS PERMITS ARE REQUIRED FOR GENERATORS.
  
 1. PROVIDE AUTOMATIC TRANSFER SWITCH SPECS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE NEW LOAD CALC'S WITH LOAD SHEDDING.
 PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS
 FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR
 THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2.
  
  
 3. IDENTIFY WHICH PANEL WILL SERVICE NEW 20AMP AND
 30AMP CIRCUTS FOR FUTURE SAUNA.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By cthroop Date 2021-02-18 Time 09:31 Rev Time 0.00
Received By cthroop Date 2021-02-18 Time 09:19 Sent To  
Notes
2021-02-18 09:33:11PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE AN ELECTRICAL PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-05-04 Cont ID  
Sent By lcrespo Date 2021-05-04 Time 15:08 Rev Time 0.00
Received By lcrespo Date 2021-05-04 Time 12:52 Sent To  
Notes
2021-05-04 15:11:5505/04/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-04-01 Cont ID  
Sent By medwards Date 2021-04-01 Time 11:29 Rev Time 0.00
Received By medwards Date 2021-04-01 Time 11:29 Sent To  
Notes
2021-04-01 11:29:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21010946
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MORE DETAIL FOR THE STEEL PIPING
 LOCATED OUTDOORS. IS IT RAN ABOVE GROUND AND AT LEAST
 3.5 INCHES ABOVE GROUND? FBC FG 404.9
  
 2) IS THE STEEL PIPING BURIED UNDERGROUND? IF SO, HOW
 IS IT PROTECTED? FBC FG 404.11.
  
 3) IF PIPING IS BURIED PLEASE SHOW THE DEPTH OF THE
 UNDERGROUND PIPING. FBC FG 404.12
  
 4) PLEASE INDICATE DISTANCE OF GENERATOR EXHAUST FROM
 ANY OPERABLE OPENING INTO THE BUILDING. FBC RES
 R303.5.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By cthroop Date 2021-03-09 Time 15:38 Rev Time 0.00
Received By cthroop Date 2021-03-09 Time 14:45 Sent To  
Notes
2021-03-09 15:51:15PLAN REVIEW / FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 NOTICE: PROVISO ON PLAN PAGE P2.1 SEPERATE FUEL GAS
 PERMIT REQUIRED FOR GENERATORS.
  
  
 1. SUBMIT MANUFACTURERS SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR
 2017 FBC FUEL GAS RES. SEC. G2408.1.
  
 2. SUBMIT GAS REGULATOR SPECIFICATIONS. 2017 FBC FUEL
 GAS SEC.305.1 OR 2017 FBC FUEL GAS RES. SEC. G2408.1.
  
 3. REGULATORS SHALL HAVE A UNION INSTALLED WITHIN 1
 FOOT OF EITHER SIDE OF THE REGULATOR FBC FG 410.2
  
 4. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017
 FBC FG SECS. 402.2 AND 301.3 OR 2017 FBC RES. SEC.
 G2413.2 AND G2404.3.
  
 5. CHANGE GOVERNING CODE ON GAS PLAN TO 2020 FBC FUEL
 GAS
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-02-18 Cont ID  
Sent By cthroop Date 2021-02-18 Time 09:29 Rev Time 0.00
Received By cthroop Date 2021-02-18 Time 09:20 Sent To  
Notes
2021-02-18 09:31:39SEPERATE PERMITS ARE REQUIRED FOR THE PROPOSED
 GENERATOR AND GAS INSTALLATION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-04 Cont ID  
Sent By lcrespo Date 2021-05-04 Time 15:12 Rev Time 0.00
Received By lcrespo Date 2021-05-03 Time 08:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-01 Cont ID  
Sent By cthroop Date 2021-04-01 Time 17:06 Rev Time 0.00
Received By cthroop Date 2021-03-26 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-09 Cont ID  
Sent By cthroop Date 2021-03-09 Time 15:14 Rev Time 0.00
Received By cthroop Date 2021-03-05 Time 17:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-01 Cont ID  
Sent By jleahy Date 2021-03-01 Time 07:11 Rev Time 0.00
Received By jleahy Date 2021-02-03 Time 14:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-03-31 Cont ID  
Sent By medwards Date 2021-03-31 Time 06:37 Rev Time 0.00
Received By medwards Date 2021-03-31 Time 06:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By cthroop Date 2021-03-09 Time 15:14 Rev Time 0.00
Received By cthroop Date 2021-03-08 Time 08:22 Sent To  
Notes
2021-03-09 15:21:29PLAN REVIEW / MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: RE-LOCATION OF C/U
  
 1. PROVIDE STRUCTURAL TIE-DOWN DETAIL.
 PROVIDE ENGINEERING FOR INSTALLATION OF THE CONDENSER
 PAD AND MOUNTING OF THE CONDENSER- SECTIONS
 M1305.1.4.1, M1307.2 AND M1401.4 FBC RES.
  
 2. PROVIDE SERVICE DISCONNECT.
 E4101.5DISCONNECTING MEANS.
  
 3. PROVIDE EQUIPMENT SERVICE OUTLET.
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 4. M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By cthroop Date 2021-02-18 Time 09:33 Rev Time 0.00
Received By cthroop Date 2021-02-18 Time 09:18 Sent To  
Notes
2021-02-18 09:34:10PLAN REVIEW / MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A MECHANICAL PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-05-04 Cont ID  
Sent By lcrespo Date 2021-05-04 Time 15:12 Rev Time 0.00
Received By lcrespo Date 2021-05-04 Time 12:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-04-01 Cont ID  
Sent By cthroop Date 2021-04-01 Time 11:02 Rev Time 0.00
Received By cthroop Date 2021-03-31 Time 15:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By cthroop Date 2021-03-09 Time 15:34 Rev Time 0.00
Received By cthroop Date 2021-03-08 Time 08:22 Sent To  
Notes
2021-03-09 15:38:37PLAN REVIEW / PLUMBING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SANITARY RISER DIAGRAHM.
 PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION
 107.3.5.3 (12)
  
 P2601.2 CONNECTIONS TO DRAINAGE SYSTEM
 PLUMBING FIXTURES, DRAINS, APPURTENANCES AND APPLIANCES
 USED TO RECEIVE OR DISCHARGE LIQUID WASTES OR SEWAGE
 SHALL BE DIRECTLY CONNECTED TO THE SANITARY DRAINAGE
 SYSTEM OF THE BUILDING OR PREMISES, IN ACCORDANCE WITH
 THE REQUIREMENTS OF THIS CODE. THIS SECTION SHALL NOT
 BE CONSTRUED TO PREVENT INDIRECT WASTE CONNECTIONS
 WHERE REQUIRED BY THE CODE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By cthroop Date 2021-02-18 Time 09:34 Rev Time 0.00
Received By cthroop Date 2021-02-18 Time 09:19 Sent To  
Notes
2021-02-18 09:34:52PLAN REVIEW / PLUMBING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A PLUMBING PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-05-04 Cont ID  
Sent By lcrespo Date 2021-05-04 Time 15:12 Rev Time 0.00
Received By lcrespo Date 2021-05-04 Time 15:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-01 Cont ID  
Sent By cthroop Date 2021-04-01 Time 11:02 Rev Time 0.00
Received By cthroop Date 2021-03-31 Time 15:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By cthroop Date 2021-03-09 Time 14:25 Rev Time 0.00
Received By cthroop Date 2021-03-08 Time 08:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-18 Cont ID  
Sent By cthroop Date 2021-02-18 Time 09:19 Rev Time 0.00
Received By cthroop Date 2021-02-17 Time 06:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-02-26 Cont ID  
Sent By kalexand Date 2021-02-26 Time 10:23 Rev Time 0.00
Received By kalexand Date 2021-02-26 Time 10:23 Sent To I
Notes
2021-02-26 10:24:35AS STAMPED ON PLANS, SEPARATE PERMIT NEEDED FOR SITE