Plan Review Details - Permit 21010878
Plan Review Stops For Permit 21010878
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-04-01 Cont ID  
Sent By jwitmer Date 2021-04-01 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2021-04-01 Time 10:47 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-02-08 Cont ID  
Sent By jwitmer Date 2021-02-08 Time 12:01 Rev Time 0.00
Received By jwitmer Date 2021-02-08 Time 10:47 Sent To  
Notes
2021-02-08 12:01:01COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-01 Cont ID  
Sent By jwitmer Date 2021-04-01 Time 11:13 Rev Time 0.00
Received By jwitmer Date 2021-04-01 Time 10:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-08 Cont ID  
Sent By jwitmer Date 2021-02-08 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2021-02-08 Time 10:47 Sent To  
Notes
2021-02-08 11:59:31WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21010878
 ADD: 8170 OKEECHOBEE BLVD. SUITE # 4
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: 561-358-4140
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 08TH/ 2021
 ACTION: DENIED
  
 1) SHEET 1.1 FLOOR PLAN DEMO & REMODEL:
 1A) PLEASE CORRECT THE EXISTING TOILET ACCESSORY
 SCHEDULE FOR GB, AND GB-1. THE NOTES INDICATE THE GRAB
 BARS ARE TO BE MEASURED33-36 INCHES AFF TO THE
 CENTERLINE OF THE GRAB BAR. PLEASE UPDATE NOTE TO READ
 33-36 INCHES AFF TO THE TOP OF THE GRASPABLE SURFACE.
 2020 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 1B) BUILDING PROVISO: PLEASE NOTE IF IN THE FIELD THE
 GRAB BARS ARE EITHER TO HIGH OR TO LOW UNDER THE 2020
 EXISTING BUILDING CODE, THE EXISTING BUILDING CODE
 REFERS BACK TO THE 2020 ACCESSIBILITY CODE AND THE 20 %
 DISPROPORTION COST RULE. UP TO $5,900 DOLLARS IN VALUE
 ABOVE THE CONTRACT VALUE CAN BE REQUIRED FOR
 ACCESSIBILITY UPGRADES. 202.4.1. DISPROPORTIONATE COST.
  
 1C) THE DEMO PLAN SHOWS THE EXISTING DRINKING FOUNTAIN
 TO BE RELOCATED. THE NEW PROPOSED FLOOR PLAN SHOWS THE
 NEW LOCATION FOR THE DRINKING FOUNTAIN BUT NOT
 ELEVATIONS AND COMPLIANCE WITH THE 2020 ACCESSIBILITY
 CODE SECTIONS:
  
 1C)(1) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 1C)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 1D) THE PROPOSED FLOOR PLAN SHOWS THE ADJACENT TENANT
 AS THE PROGRESS PHARMACY. THE FLOOR PLAN ALSO STATES
 THERE IS AN EXISTING 1-HOUR FIRE RATED TENANT
 SEPARATION WALL. WITHIN THIS SAME WALL THERE IS A NOTE
 TO CUT A NEW PASS THROUGH THE WALL 3 FEET X 6 FEET
 8INCHES. IS THIS A NEW DOOR? IS THE DESIGNER OF RECORD
 REQUIRING THE TENANT SEPARATION WALL TO MAINTAIN THE
 ONE-HOUR FIRE RATING? 2020 FBC-B 708.1. & 715.6 OPENING
 PROTECTIVES.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-16 Cont ID  
Sent By equinone Date 2021-04-16 Time 14:00 Rev Time 0.00
Received By equinone Date 2021-04-16 Time 14:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-02-22 Cont ID  
Sent By equinone Date 2021-02-22 Time 10:20 Rev Time 0.00
Received By equinone Date 2021-02-19 Time 10:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-04-14 Cont ID  
Sent By bdolan Date 2021-04-14 Time   Rev Time 0.00
Received By bdolan Date 2021-04-14 Time 10:51 Sent To  
Notes
2021-04-14 10:51:32THE FOLLOWING COMMENTS WERE SUBMITTED BY LIEUTENANT
 BRIAN DOLAN, BUREAU OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE:
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-02-01 Cont ID  
Sent By bdolan Date 2021-02-01 Time 09:24 Rev Time 0.00
Received By bdolan Date 2021-01-28 Time 12:57 Sent To  
Notes
2021-02-01 09:24:06ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-11 Cont ID  
Sent By jesmith Date 2021-05-11 Time 16:57 Rev Time 0.00
Received By jesmith Date 2021-05-11 Time 16:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-02 Cont ID  
Sent By jesmith Date 2021-03-02 Time 15:46 Rev Time 0.00
Received By jesmith Date 2021-01-26 Time 13:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-02-08 Cont ID  
Sent By jwitmer Date 2021-02-08 Time 11:59 Rev Time  
Received By jwitmer Date 2021-02-08 Time 10:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-04-20 Cont ID  
Sent By medwards Date 2021-04-20 Time 10:00 Rev Time 0.00
Received By medwards Date 2021-04-20 Time 08:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By medwards Date 2021-02-25 Time 13:41 Rev Time 0.00
Received By medwards Date 2021-02-25 Time 13:00 Sent To  
Notes
2021-02-25 13:41:431ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21010878
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE IN THIS BUSINESS.I.E. NEW WORK? CONFERENCE
 ROOM, RECEPTION ROOM AND OFFICES BASED ON FBC M
 403.3.1.1 AND TABLE 403.3.1.1. THE CALCULATION IS BASED
 OFF OF THE TABLE NOT THE OCCUPANT LOAD FROM THE
 ARCHITECTURE SHEETS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-05-11 Cont ID  
Sent By jesmith Date 2021-05-11 Time 16:46 Rev Time 0.00
Received By jesmith Date 2021-04-22 Time 08:48 Sent To  
Notes
2021-05-11 16:46:4021010878 8170 OKEECHOBEE BLVD # 4
  
  
 PLAN IS APPROVED WITH PROVISO: A REVISED PLUMBING PLAN
 SHALL BE SUBMITTED AS A REVISION AND SHALL BE APPROVED
 AND ON SITE PRIOR TO THE FIRST INSPECTION. REVISED
 PLANS SHALL REFLECT THE FOLLOWING AS REDLINED IN THE
 PERMIT PLAN SUBMITTED FOR THIS REVIEW.
  
 1.FULL OPEN VALVES SHALL BE REQUIRED AT TOP NOT THE
 BOTTOM OF NEW DOWN-FEED PIPES TO NEW SINK AND DRINKING
 FOUNTAIN AS REQUIRED BY FBC PL 606.1.5
  
 2.REFER TO EWC AND REC PUMP DETAIL THIS PAGE
  
 3.REDRAW RETURN AT POINT OF CONNECTION TO COLD WATER
  
 4.PROVIDE NOTE AT FIXTURE SCHEDULE "MIXING VALVE AT THE
 POINT OF DELIVERY AT THE LAVATORY AS REQUIRED BY FBC PL
 419.5."
  
 5.SEQUENCE OF SHUT OFF VALVE AND CHECK VALVE SHALL BE
 REVERSED FOR SERVICEABILITY WITH CHECK VALVE DOWNSTREAM
 OF SHUT OFF VALVE.
  
 6.PROVIDE A PIPE HANGER DETAIL WITH NOTE STATING "PIPE
 SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE
 308.5."
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 CALL OR EMAIL WITH ANY QUESTION
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
  
 21010878 8170 OKEECHOBEE BLVD # 4
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-02 Cont ID  
Sent By jesmith Date 2021-03-02 Time 15:45 Rev Time 0.00
Received By jesmith Date 2021-03-02 Time 10:08 Sent To  
Notes
2021-03-02 15:36:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21010878 8170 OKEECHOBEE BLVD # 4
 1ST REVIEW
 PLUMBING COMMENTS:
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, PROVIDE OCCUPANCY AND OCCUPANCY
 LOAD. BASED ON SAID OCCUPANCY AND OCCUPANCY LOAD,
 PROVIDE PLUMBING FIXTURE SCHEDULE SHOWING COMPLIANCE
 WITH FBC PL TABLE 403.1.
  
 2.REGARDING SCHEDULED TITAN N120 TANKLESS WATER HEATER
 NOTED ON SHEET 3.1, THE UNIT ELECTRICAL CHARACTERISTICS
 ARE 11.8KW/240V. THE ELECTRICAL SCHEDULE ON SHEET 4.1
 INDICATES 8KW. PER WPB FBC 107.2.1, CLARIFY AND/OR
 RECONCILE. ADDITIONALLY, PROVIDE AN EQUIPMENT SCHEDULE
 FOR THE WATER HEATER PROVIDING SIZE OF PLUMBING
 CONNECTIONS AND ELECTRICAL CHARACTERISTICS. PROVIDE
 MANUFACTURER?S SPECIFICATION/INSTALLATION MANUAL FOR
 THE SAME.
  
 3.PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 SCHEDULE INDICATING PLUMBING FIXTURE TYPE WITH SIZED
 PLUMBING CONNECTIONS.
  
 4.REFER TO SHEET 1.1. SHOW CLEAR SPACE FOR SINK IN NEW
 CONSULT ROOM #3 SHOWING COMPLIANCE WITH SHOWING
 COMPLIANCE WITH FBC ACC SECTION 305.
  
 5.REFER TO SHEET 3.1, FIG. 27 DRINKING FOUNTAIN. PLEASE
 SEE BUILDING COMMENT. 1C)(1) SPOUT OUTLETS/ DRINKING
 FOUNTAINS. 2020 ACCESS. CODE. SPOUT OUTLETS SHALL
 COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
 PER WPB FBC REVISE DETAIL TO REFLECT THE REQUIREMENTS
 OR IF SHOWING COMPLIANCE ON SHEET 1.1 THEN REMOVE
 EXISTING DETAIL TO AVOID CONFUSION.
  
 6.REFER TO SHEET 3.1, WATER DISTRIBUTION; 1/2 INCH HOT
 AND COLD WATER IS NOTED AT THE DRINKING FOUNTAIN. PER
 WPB FBC 107.2.1, CLARIFY.
  
 7. REFER TO SHEET 3.1, WATER DISTRIBUTION; NEW HOT AND
 COLD WATER DISTRIBUTION IS SIZED 5/8 INCH. THERE IS NO
 5/8 INCH (THIS IS AN O.D. SIZE WHICH IS USED FOR
 REFRIGERANT PIPING) NOMINAL SIZE PIPE AVAILABLE FOR
 PLUMBING DESIGNATION. 1/2 INCH NOMINAL IS THE
 DESIGNATION THAT WOULD BE USED FOR 5/8 INCH O.D. IF
 THIS IS THE SIZE YOU INTENDED TO USE, PLEASE INDICATE
 IT ON THE PLANS TO AVOID CONFUSION AS REQUIRED BY WPB
 FBC 107.2.1.
  
 8.PER WPB FBC 107.2.1, PROVIDE FINISH WALL SCHEDULE FOR
 BATHROOM. REFER TO FBC PL 310.3 AND FBC 1210.2.2. WALLS
 AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 STIPULATES THAT
 THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION IS
 THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE
 THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL COULD
 BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 9.PLEASE REFER TO COMMENTS MADE BY BUILDING PLANS
 EXAMINER. 1B) BUILDING PROVISO: PLEASE NOTE IF IN THE
 FIELD THE GRAB BARS ARE EITHER TO HIGH OR TO LOW UNDER
 THE 2020 EXISTING BUILDING CODE, THE EXISTING BUILDING
 CODE REFERS BACK TO THE 2020 ACCESSIBILITY CODE AND THE
 20 % DISPROPORTION COST RULE. UP TO $5,900 DOLLARS IN
 VALUE ABOVE THE CONTRACT VALUE CAN BE REQUIRED FOR
 ACCESSIBILITY UPGRADES. 202.4.1. DISPROPORTIONATE COST.
 PLEASE NOTE, THIS COULD ALSO APPLY TO THE EXISTING
 LAVATORY AND WATER CLOSET IF THEY ARE NOT COMPLIANT.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 21010878 8170 OKEECHOBEE BLVD # 4

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-20 Cont ID  
Sent By medwards Date 2021-04-20 Time 10:11 Rev Time 0.00
Received By medwards Date 2021-04-20 Time 10:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-26 Cont ID  
Sent By medwards Date 2021-01-26 Time 14:34 Rev Time 0.00
Received By medwards Date 2021-01-26 Time 14:34 Sent To  
Notes
2021-01-26 14:36:45PLEASE PROVIDE THE ORIGINAL DIGITALLY SIGNED AND SEALED
 DRAWINGS OR YOU CAN BRING TO OUR OFFICE THE ORIGINAL
 SIGNED AND SEALED PAPER DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-04-12 Cont ID  
Sent By llouie Date 2021-04-12 Time   Rev Time 0.00
Received By llouie Date 2021-04-12 Time   Sent To  
Notes
2021-04-12 08:44:19REFERENCE: SEDONA COMMONS CPD, TRACT C - PER ORDINANCE
 NO. 4166-08, USES PERMITTED IN CPD ARE THOSE USES
 PERMITTED BY-RIGHT AND PXR USES IN THE GC ZONING
 DISTRICT. PROPOSED USE ACCORDING TO PERMIT PLANS IS FOR
 A PHARMACY/MEDICAL OFFICE.

Review Stop Z ZONING
Rev No 1 Status P Date 2021-01-29 Cont ID  
Sent By llouie Date 2021-01-29 Time   Rev Time  
Received By llouie Date 2021-01-29 Time   Sent To  
Notes
2021-01-29 09:55:03REFERENCE: SEDONA COMMONS CPD, TRACT C - PER ORDINANCE
 NO. 4166-08, USES PERMITTED IN CPD ARE THOSE USES
 PERMITTED BY-RIGHT AND PXR USES IN THE GC ZONING
 DISTRICT. PROPOSED USE ACCORDING TO PERMIT PLANS IS FOR
 A PHARMACY/MEDICAL OFFICE.